System Sensor Complete Guide for Wiring and Testing the Sensiscan 1000 Smoke Alarm System

Page 5

For signal wiring, (the wiring between interconnected de- tectors or from detectors to auxiliary devices), it is usually recommended that single conductor wire be no smaller than 18 gauge. The duct smoke detector terminals accom- modate wire sizes up to 12 gauge. The last foot of conduit should be flexible conduit (available in electrical supply houses), which facilitates easier installation and puts less strain on the conduit holes in the housing. Solid conduit connections may be used if desired.

Smoke detectors and alarm system control panels have specifications for allowable loop resistance. Consult the control panel manufacturer’s specifications for the total loop resistance allowed for the particular model control panel being used before wiring the detector loop.

Wiring Instructions

The DH100 detectors are designed for easy wiring. The housing provides a terminal strip with clamping plates. Wiring connections are made by stripping about 3/8-inch of insulation from the end of the wire, sliding the bare end un- der the plate, and tightening the clamping plate screw.

The DH100 duct smoke detector is designed to operate with 12 or 24 VDC UL listed 2-wire compatible control panels. Alarm current must be limited by the control panel to 100mA or less. An example of a UL listed compatible con- trol panel is the Fire-Lite model Sensiscan 1000 using zone card ANC-2 and compatibility identification “A”. Install per installation instruction S1000/801. A maximum of 20 detec- tors may be installed per zone.

[5.7] Perform Detector Check

1.Perform STANDBY AND TROUBLE TEST per Section [6.2.1].

2.Perform MAGNET TEST per Section [6.2.2.1]. The RTS451 test of Section [6.2.2.2] may substitute for this requirement.

3.Perform AIR FLOW TEST per Section [6.1.1].

4.Perform SMOKE RESPONSE TEST per Section [6.1.2].

5.Perform SENSITIVITY TEST per Section [6.2.3].

[5.8] Install The Cover

Install the cover using the four screws that are captured in the housing cover. Be certain filters are installed as speci- fied in Section [5.5]. Make sure that the cover fits into the base groove and that all gaskets are in their proper posi- tions. Tighten the four screws.

[6]Duct Smoke Detector Maintenance And Test Procedures

Test and maintain duct smoke detectors as recommended in NFPA 72. The tests contained in this manual were devised to assist main- tenance personnel in verification of proper detector operation.

Before conducting these tests, notify the proper authorities that the smoke detection system will be temporarily out of service. Disable the zone or system under test to prevent unwanted alarms.

[6.1] Smoke Entry Tests

[6.1.1] Air Flow

To verify sufficient sampling of ducted air, use a manometer to measure the differential pressure created from air flow across the sampling tubes. The pressure should measure no less than 0.03 inches of water and no greater than 1.4 inches of water. The air handler must be operating for this test.

[6.1.2] Smoke Response

To determine if smoke is capable of entering the sensing chamber, visually identify any obstructions. Plug the ex- haust and inlet tube holes to prevent ducted air from carry- ing smoke away from the detector head, then blow smoke such as cigarette, cotton wick, or punk directly at the head to cause an alarm. REMEMBER TO REMOVE THE PLUGS AFTER THIS TEST, OR THE DETECTOR WILL NOT FUNC- TION PROPERLY.

[6.1.3] Filter Replacement

The filters do not substantially affect smoke performance even when up to 90% of the filter is clogged. Quarterly vi- sual inspection usually suffices to determine whether the filters should be replaced because only a high percentage of contamination affects performance. If further testing is re- quired, compare differential pressure readings with and without the filters installed. If the difference exceeds 10% replace the filters. In no case should the pressure differen- tial fall below 0.03 inches of water.

[6.2] Standby, Alarm, And Sensitivity Tests [6.2.1] Standby And Trouble

Standby — Look for the presence of the flashing green LED through the transparent housing cover. The LED should flash approximately every 10 seconds.

Trouble — If the Green LED does not flash, then the de- tector lacks power (check wiring, panel, or power supply), the detector board is missing (replace), or the unit is defective (return for repair)

Test — The trouble condition can be caused inten- tionally to verify correct operation of the sys- tem. Remove the detector board to cause a trouble condition locally and at the system control panel.

D100-67-00

5

I56-1148-04

Image 5
Contents Table of Contents Before InstallingThis device will not operate without electrical power General DescriptionDrill The Mounting Holes Tube Installation Chart Supplemental Duct Tube HolesContents Of The Duct Smoke Detector Kit Outside Duct Width Inlet Tube Required Secure The Detector Housing To The DuctInlet tubes required for different duct Widths Install The Filters Install the inlet tube as followsField Wiring Wiring Installation Guidelines Modifications of Inlet Sampling TubesInstall The Cover Wiring InstructionsDuct Smoke Detector Maintenance And Test Procedures Filter ReplacementLED Detector Cleaning Procedures Alarm Tests 2.1 M02-04-00 Magnet TestBoard Replacement Detector Board Replacement Power Board replacementElectrical Ratings includes base and detector Model DH100 Air Duct Smoke Detector Specifications

D100-67-00, I56-1148-04 specifications

The System Sensor D100-67-00 and I56-1148-04 are advanced devices designed for fire detection and alarm systems, offering a range of features and technologies that cater to the needs of modern safety requirements.

The D100-67-00 is a high-performance photoelectric smoke detector that incorporates innovative sensing technology. It boasts a sophisticated optical chamber that enhances its ability to detect smoke particles effectively. This detector minimizes false alarms commonly caused by non-threatening, everyday activities such as cooking, making it ideal for residential and commercial applications. Its low profile design and sleek aesthetic also allow it to seamlessly blend into various environments. The D100-67-00's sensitivity is adjustable, ensuring that it can be calibrated according to specific needs or building codes, thereby enhancing its versatility.

Moreover, the D100-67-00 features a built-in sounder and visual indicators that provide immediate alerts. The device is equipped with a robust communication protocol that allows it to integrate with other fire alarm control panels and monitoring systems. This capability enhances the overall safety network by ensuring real-time communication of any fire incidents, a crucial feature in high-risk areas.

On the other hand, the System Sensor I56-1148-04 is an advanced heat detector that employs thermal sensing technology. It is designed to respond to rapid temperature increases, ensuring quick detection of potential fire hazards. This device is particularly beneficial in environments where smoke detectors might be prone to false alarms due to dust or steam, like kitchens or garages. The I56-1148-04 features a dual-heat sensing mechanism, allowing it to differentiate between normal temperature fluctuations and dangerous heat spikes, providing an extra layer of protection.

Both devices are engineered with durability in mind, adhering to strict industry standards. They are intended for long-term use, requiring minimal maintenance while still delivering reliable performance. Critical for emergency response, both detectors offer optional connectivity with control panels and monitoring solutions, allowing for comprehensive system integration.

In summary, the System Sensor D100-67-00 and I56-1148-04 are integral components of fire safety systems, with their advanced features and technologies ensuring efficient detection and alerting in diverse settings. These devices exemplify reliability and innovation, essential in safeguarding lives and property against fire hazards.