System Sensor DH100ACDCP Inlet tubes required for different duct widths, Outside Duct Width

Page 3

Figure 3. Installation of foam gaskets over sampling tube bushings:

SCREW HOLES FOR

ATTACHING HOUSING

TO DUCT WORK.

A78-2045-00

[5.4] Sampling Tube Installation for Ducts Greater Than 112 Feet Wide

The sampling tube is identified by a series of air inlet holes on the tube. A plastic tube is included for ducts up to 18in width. All other lengths must be purchased separately. Order the correct length, as specified in Table 1, for width of the duct where it will be installed. The exhaust tube is molded onto the base of the duct housing, and the A2440-00 Exhaust Tube Extension is available as an accessory in those cases where the molded exhaust port does not extend at least 2 inches into the duct.

The inlet tube is always installed with the air inlet holes facing into the air flow. To assist proper installation, the tube’s mounting flange is marked with arrows. Make sure the inlet tube is mounted so that the arrows point into the air flow (see Figure 4). Figure 5 shows the various combi- nations of tube mounting configurations with respect to air flow. Mounting the detector housing in a vertical orienta- tion is acceptable, provided that the air flows directly into the sampling tube holes as indicated in Figure 4.

Table 1. Inlet tubes required for different duct widths:

Outside Duct Width

Inlet Tube Required

1

to 2 ft.

ST-1.5

2

to 4 ft.

ST-3

4

to 8 ft.

ST-5

8 to 12 ft.

ST-10

[5.4.1] Installation For Ducts Greater Than 112 Feet But Less Than 8 Feet Wide

1.If the tube is longer than the width of the air duct, drill a 34hole in the duct opposite the hole already cut for the inlet tube. Make sure the hole is 1″ to 2″ below the inlet hole on the opposite side of the duct to allow moisture drainage away from the detector. If the tube is shorter than the width of the air duct, install the end plug into the inlet tube as shown in Figure 4. Sampling tubes over 3 ft. long must be supported at the end opposite the duct smoke detector.

2.Slide the tube into the housing bushing that meets the air flow first. Position the tube so that the arrows point into the air flow.

3.Secure the tube flange to the housing bushing with two #6 self-tapping screws.

4.For tubes longer than the width of the air duct, the tube should extend out of the opposite side of the duct. If there are more than 2 holes in the section of the tube extending out of the duct, select a different length using Table 1. Otherwise, trim the end of the tube protruding through the duct so that 1to 2of the tube extend out- side the duct. Plug this end with the end plug and tape closed any holes in the protruding section of the tube. Be sure to seal the duct where the tube protrudes.

Figure 4. Air duct detector inlet sampling tube:

FLANGE

AIR HOLES

INLET

 

 

 

TUBE

 

 

END

 

 

PLUG

ARROWS

AIR FLOW DIRECTION

MUST FACE

 

INTO AIR FLOW

 

 

A78-2047-00

Figure 5. Tube mounting configurations with varying air flow direction:

 

DOTS INDICATE POSITION OF

 

 

SAMPLING TUBE HOLES

 

AIR FLOW

 

 

AIR FLOW

 

 

DIRECTION

DIRECTION

 

 

 

 

 

DETECTOR

 

 

DETECTOR

HOUSING

 

 

HOUSING

 

A.

 

B.

INLET

EXHAUST

EXHAUST

INLET

TUBE

TUBE

TUBE

TUBE

 

HORIZONTAL MOUNTING OF HOUSING

 

 

EXHAUST

 

 

 

TUBE

DETECTOR

 

 

 

HOUSING

 

EXHAUST

 

AIR FLOW

TUBE

AIR FLOW

 

 

DIRECTION

 

 

DIRECTION

 

INLET

INLET

 

DETECTOR

TUBE

TUBE

D.

HOUSING

C.

 

VERTICAL MOUNTING OF HOUSING

NOTE: Only metal sampling tubes may be used on ori- entations C and D.

WARNING

In no case should more than 2 air inlet holes be cut off the tube. There must be a minimum of 10 holes in the tube exposed to the air stream.

[5.4.2] Installation For Ducts More Than 8 Feet Wide

NOTE: To install inlet tubes in ducts more than 8 feet wide, work must be performed inside the air duct. Sampling of air in ducts wider than 8 feet is accom- plished by using the ST-10 inlet sampling tube. If the tube is shorter than the width of the air duct, install the end plug into the inlet tube as shown in Figure 4 and support the end opposite the duct smoke detector.

D100-68-00

3

I56-1147-12R

Image 3
Contents Limitations Of Duct Smoke Detectors Before InstallingTable of Contents General DescriptionDrill The Mounting Holes Contents Of The Duct Smoke Detector KitInstallation Sequence Secure The Detector Housing To The DuctInlet tubes required for different duct widths Installation For Ducts More Than 8 Feet WideHorizontal Mounting of Housing Vertical Mounting of HousingWiring Instructions Install the inlet tube as followsInstall The Filters Field Wiring Installation GuidelinesAlarm Tests 2.1 M02-04-00 Magnet Test Install The CoverDuct Smoke Detector Maintenance And Test Procedures Filter ReplacementA78-2352-27 Air Filters 2.3 SSK451 Multi-Signaling AccessoryDetector Cleaning Procedures Sensitivity Tests 3.1 MOD400 or MOD400R TestElectrical Specifications Board ReplacementPower Board replacement Part No. A5064 Model DH100ACDCP Air Duct Smoke Detector Specifications

DH100ACDCP specifications

The System Sensor DH100ACDCP is a versatile and advanced smoke and heat detection device designed to provide reliable fire safety within various environments. With its sophisticated technology, the DH100ACDCP excels in detecting smoke and elevated temperatures, making it an essential component of fire alarm systems in residential, commercial, and industrial settings.

One of the main features of the DH100ACDCP is its dual-sensor technology, which combines both photoelectric and heat detection methods. This feature enhances its ability to detect a wide range of fire types, including smoldering fires that produce dense smoke and fast-flaming fires that generate significant heat. The photoelectric sensor effectively captures smoke particles, while the heat detector activates when it senses a temperature rise beyond a predefined threshold, ensuring comprehensive coverage against fire incidents.

Another significant characteristic of the DH100ACDCP is its intelligent sensing capabilities. The device includes advanced algorithms that allow for real-time analysis of environmental conditions, helping to reduce false alarms. This intelligent approach not only enhances the reliability of the unit but also extends its operational lifespan by minimizing unnecessary activation.

The DH100ACDCP is designed to operate efficiently within a wide temperature range, making it suitable for various applications. Its durability ensures that it can withstand challenging environmental conditions, making it a dependable choice for installations in areas with fluctuating temperatures.

Installation and maintenance of the DH100ACDCP are user-friendly thanks to its compact design and universal mounting options. The device is compatible with a variety of fire alarm control panels, allowing for seamless integration into existing fire safety systems. Additionally, regular maintenance is facilitated by diagnostic features that provide system status updates, ensuring that any issues can be promptly addressed.

Ultimately, the System Sensor DH100ACDCP is engineered for performance and reliability in smoke and heat detection. By incorporating advanced technologies and robust design, it stands out as a crucial component for enhancing fire safety. With its combination of dual-sensor technology, intelligent sensing capabilities, and ease of installation, the DH100ACDCP effectively meets the demands of modern fire detection needs.