INSTALLATION AND MAINTENANCE INSTRUCTIONS
2100D and 2100TD Photoelectronic Smoke Detectors
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
Specifications |
|
|
Diameter: | 5.5 inches (140 mm) | |
Height (including mounting bracket): | 1.7 inches (43 mm) | |
Weight: | 5.3 oz. (150 g) |
|
Operating Temperature Range: | Model 2100D: 32° to 120°F (0° to 50°C) | |
| Model 2100TD: 32° to 100°F (0° to 39°C) | |
Operating Humidity Range: | 10% to 93% Relative Humidity, Noncondensing | |
Latching Alarm: | Reset by momentary power interruption | |
Heat Sensor (Model 2100TD only): | 135°F Fixed Temperature Electronic Thermistor | |
Electrical Ratings |
|
|
System Voltage – | Nominal: | 12 or 24 VDC |
| Minimum: | 8.5 VDC |
| Maximum: | 35 VDC |
Maximum Ripple Voltage: | 30% of nom. Voltage (peak to peak) | |
0.02 µF maximum | ||
Standby Current: | 50 µA maximum | |
Alarm Ratings: | 4.2 VDC minimum at 10 mA. | |
| 6.6 VDC maximum at 100 mA. | |
| (Alarm current must be limited to 100 mA maximum by the control panel. If | |
| used, the RA400Z Remote Annunciator operates within the specified detector | |
| alarm currents.) |
|
Reset Voltage: | 2.5 VDC minimum | |
Reset Time: | 0.3 seconds maximum | |
30 seconds maximum (after 60 second reset) |
Before Installing
Please thoroughly read System Sensor manual
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested and maintained regularly following NFPA 72 requirements. The detector should be cleaned at least once a year.
General Description
Model 2100D is a
Installation of these detectors is simplified by the use of a mounting bracket and a
Models 2100D and 2100TD feature a visual indication that maintenance is required – if the sensing chamber drifts out of its sensitivity limits, the LED ceases to blink.
The detectors also include an output that allows an optional Model RA400Z Remote Annunciator to be connected.
1 |