System Sensor 2100D, 2100TD Mounting, Tamper-resistance Feature, Wiring Installation Guidelines

Page 2

Figure 1. Surface mounting of 2100D smoke detector on 3 1/2-inch and 4-inch octagonal box:

A78-2563-00

Mounting

Each 2100D and 2100TD detector is supplied with a mount- ing bracket that permits the detector to be mounted:

1.To a single gang box, or

2.Directly to a 31/2-inch or 4-inch octagonal box, or

3.To a 4 inch square electrical box by using a plaster ring.

Tamper-resistance Feature

This detector includes a tamper-resistant feature that pre- vents its removal from the bracket without the use of a tool. To make the detector tamper-resistant, remove the smaller tab by breaking it at the scribed line on the tamper- resistant tab on the detector mounting bracket (see Figure 2), then install the detector. To remove the detector from the bracket once it has been made tamper resistant, use a small screwdriver to depress the tamper-resistant tab, located in the slot on the mounting bracket, and turn the detector counterclockwise.

Wiring Installation Guidelines

All wiring must be installed in compliance with the Na- tional Electrical Code, applicable local codes, and any spe- cial requirements of the local authority having jurisdiction. Proper wire gauges should be used. The conductors used to connect smoke detectors to control panels and accessory devices should be color-coded to reduce the likelihood of wiring errors. Improper connections can prevent a system from responding properly in the event of a fire.

The screw terminal block will accept 14 – 22 gauge wire. For best system performance, all wiring should be installed in separate grounded conduit; do not mix fire system wiring in the same conduit as any other electrical wiring. Twisted pair may be used to provide additional protection against extraneous electrical interference.

Wire connections are made by stripping about 1/4 inch of insulation from the end of the feed wire, inserting the wire into the appropriate terminal, and tightening the screw to secure the wire in place.

System Sensor smoke detectors are marked with a compati- bility identifier located as the last digit of a five digit code stamped on the back of the product. Connect detectors only to compatible control units as indicated in System Sensor’s compatibility chart which contains a current list of UL listed compatible control units and detectors. A copy of this list is available from System Sensor upon request.

Installation

WARNING

Remove power from the control unit or initiating-device circuits before installing detectors.

1.Wire the plug-in screw terminal block per Figure 3 and plug the terminal block into the detector.

2.Align the arrows on the detector with the arrows on the mounting bracket.

3.Turn the detector clockwise in the mounting bracket un- til it clicks into place.

4.After all detectors have been installed, apply power to the control unit or initiating-device circuits.

5.Test the detector as described in the following paragraph.

6.Reset the detector at the system control panel.

7.Notify the proper authorities the system is in operation.

Figure 2. 2100D and 2100TD smoke detector mounting bracket:

TAMPER SLOT (DEPRESS TAB TO REMOVE DETECTOR)

TAMPER RESISTANT TAB (CUT OFF SMALL TAB TO ACTIVATE TAMPER-RESIST FEATURE)

ALIGNMENT

ARROWS

A78-2333-01

D200-54-00

2

I56-710-09

Image 2
Contents Electrical Ratings SpecificationsBefore Installing General DescriptionInstallation Tamper-resistance FeatureWiring Installation Guidelines MountingTesting MaintenanceRemoval of cover and screen for cleaning