Tyco 4100U installation manual Appendix J Cable Characteristics, Line Characteristics

Page 177

IDNet

4100 MAPNET II

NETWORK

Appendix J

Cable Characteristics

The IDNet cabling requirements are detailed in Chapter 8 of this manual.

Line Characteristics

Note: In the following paragraphs the term "MAPNET channel" is used to mean those lines connected to any one Mapnet Transceiver board. Parallel runs from the same board do not constitute separate channels. The term "continuous run" refers to the loop distance from the primary output, through all devices and back to the secondary output.

Line characteristics are based on 0.58uF and/or 35 Ohms total line resistance.

Total length of line on one MAPNET channel shall not exceed 3,000 m including all T-taps and parallel runs.

Maximum length for ONE continuous MAPNET run is 1200 m for up to 128 MAPNET devices using 1.5 mm sq cable.

When the run exceeds 850 m it is necessary to use twisted, shielded pair.

Copper Line Characteristics

Network "Wired" (formerly called RS-485) Communication wiring shall be 0.75 mm sq twisted, shielded pair (TSP), or 0.22 mm sq twisted pair (TP). Shielded Cable is recommended for new installations. When shielding is used, the shield shall be connected to Earth Ground, at the Left Port end of span only.

No T-tapping of the Network conductors is allowed. Network wiring is point-to-point, only.

Maximum line length between ports at 57,600 and 9600 bits per second is shown in the table below.

 

Maximum Wiring Distance

 

 

 

 

Communication Speed

0.75mm sq TSP Wire.

0.22mm sq TP Wire.

(Maximum capacitance

(Maximum capacitance

 

 

between conductors is 174

between conductors is 66

 

pf. per meter)

pf. per meter)

57,600 bps

3,000 m

2,300 m

 

 

 

9600 bps

5,600 m

4,000 m

 

 

 

Table J- 1 Network: Maximum Transmission Distances, "Wired" Network

Continued on next page

J-1

Image 177
Contents 4100U Fire Indicator Panel Page Approvals Copyrights and TrademarksManufacture Product / SiteEnd User Liability Disclaimer Non-Disclosure AgreementModel Number & Firmware Revision DocumentAmendment Log Page Table of Contents Installing 4100U Facp Components Installing 4100 Miniplex Components Non-4100U Networking System Power Supply & Alarm Relay Card Installing 4100U IDNet & 4100MXP Cards PC Software Connections Appendix a The Device Configuration DIP Switch Appendix I Power Supply & Battery Capacity Calculations List of Figures Power and Communication Wiring for MotherboardsList of Tables Mounting onto the Power Distribution InterfaceXvi Topic See Page # Chapter Introduction to the 4100U Fire Alarm SystemSystem Configurations Standalone 4100U System Standalone ConfigurationMiniplex Configuration Miniplex 4100U System Hub/Ring Configuration Network ConfigurationInterconnected Loop Configuration PIDs Non-4100U 4100U PIDs 4100U Cabinet Part Identification Numbers PIDsKits Labels Looms Chapter Installing 4100U Facp Components Introduction to FACPs 4100U Master CPU Motherboard Master Controller Daughter Card LED4 LED3 LED2 LED1 Master Controller LEDs 1 throughOperator Interface System Power Supply Power Distribution Interface PDI Mounting Card Bays to Cabinets 4100U Mounting Cabinets 4100UConfiguring Cards 4100U Interconnecting Modules and Bays Interconnecting Modules and Bays Bay-to-Bay Interconnections Power and Communication Wiring for Motherboards Expansion Bay 4x 5 Card Placement Installing Modules into Expansion Bays 4100U10. Expansion Bay Motherboard Placement 11. Mixed Module Placement 12. Slave Card/PDI Connection 13. Installing the Motherboard in a 4100U Expansion Bay Installing LED/Switch Modules into Expansion Bays 4100U 14. LED/Switch Modules Occurs 16. LED/Switch Card Mounting 17. Controller Card Mounting 18. Assembling / Disassembling the LED Display Card 19. LED/Switch Controller Wiring 20. Terminal Block Utility Module Mounting Terminal Block Utility Module 4100UPage Chapter Installing 4100 Miniplex Components Non-4100U Introduction to Miniplex Systems Non-4100U Miniplex System Design Remote Unit Interface Card Miniplex System Components Non-4100URIC II Card Miniplex System Guidelines Non-4100U Installing the RUI Motherboard in the CPU Bay Installing Modules into Cabinets Non-4100UInstalling the RIC II Motherboard into a 4100 Expansion Bay Connecting the 733-525 Harness RIC Miniplex Wiring Non-4100U Miniplex Wiring Chapter Installing 4100U Miniplex Components Introduction to Miniplex Transponders 4100U Not currently available in Australia Transponder Interface Cards Local Mode Specifications Environmental Specifications TIC Specifications Electrical SpecificationsMiniplex System Guidelines 4100U Configuring Cards 4100U TIC Mounting TIC/Riser Mounting 4100UTransponder Cabinet Interconnections TIC/Motherboard Interconnections 4100UFerrite Bead RUI Wiring 4100UPage Chapter Networking Getting Started Introduction to the 4100 Network Interface Card NIC 6014 Network Interface Card UT Motherboard with City Connection 4100/4120-0143 Fiber-Optic Media Card Environmental Specifications All Modules Configuring Network CardsNIC Card Media Card Mounting Mounting Media Cards to the NICMounting Network Cards Installing the Daughter CardWiring Network Cards 8231 mm2 Wiring DistancesFiber Wiring Mifl Dual Fiber Optic Cable Communications Distance ExamplesConnected to the 4100-6014 NIC 10. Coupler Wiring11. Wired Media Interconnections Between 4100U Motherboards 12. Wired Media, Style 7 Wiring 13. Fiber Optic, Style 7 Wiring 14. Wired Media and Fiber Optic, Style 7 Wiring Page Chapter System Power Supply & Alarm Relay Card SPS Input and Output Specifications AC Input Specifications SPS SpecificationsDC Output Specifications Battery Charger SpecificationsAlarm Conditions Current SPS Current Specifications Standby ConditionsR341 Battery Charger Voltage SPS ConfigurationSPS has the following LEDs SPS LED IndicationsTroubleshooting on SPS Alarm Relay Card Alarm Relay CardCard Alarm Relay Card Jumper PositionsChapter SPS Field Wiring 4100U Ferrite Bead SX0005 General Field Wiring GuidelinesSPS NAC Field Wiring Guidelines Class a NAC Wiring Class B Wiring Power Supply Wiring DistancesClass a NAC Wiring Table Class B NAC Wiring Table SPS Auxiliary Power Wiring Auxiliary Power Wiring SPS Relay Wiring Auxiliary Relay & Alarm Relay Card Relays SPS Auxiliary Relay WiringSPS IDNet Wiring Class a Wiring Under AS1670.1 Class B wiring is allowed only for a maximum Chapter Installing 4100U IDNet & 4100MXP Cards IDNet Card IDNet Card36.5V max See below IDNet SpecificationsMounting onto the Power Distribution Interface Installing the IDNet Card onto the PDIMounting into 4100 legacy Bay Installing the ID-Net into a 4100 Card BayDIP Switch SW1 Configuring the CardWiring to IDNet Devices Cable Run Lengths Instructions Troubleshooting on IDNet 4100MXP Page Chapter PC Software Connections Software Modes Service and Diagnostic InterfaceBootloader Interface Page Chapter Australian Version Specifics Summary Of Australian Version Specifics Australian Panel Format Switch/LED Format Switch Status4100U Fan Control Module Fan Control Module Brigade Interfaces Chapter Installation Checklist, Commissioning & Maintenance Cabinet & General Installation ChecklistAlignment & Adjustment Power Up & Placing into Operation Maintenance 11-6 Figure A-1. DIP Switch SWx Appendix a Device Configuration DIP SwitchTable A-1. Card Addresses Appendix B Programming Requirements Required FeaturesFigure D-1. Volt/Ohm Meter Readings Appendix C Checking System WiringTable C-1. Acceptable Zone and Signal Circuit Meter Readings Appendix C Checking System WiringAppendix D Earth Fault Detection General Guidelines Earth Fault Searching from the Front Panel Next and Previous buttons Result not Available Search Results Card 2, Idnet Card 250 Points Figure F-1. Earth Fault Example Earth Fault Search ExampleFind and repair the indicated fault on Transponder Book Part Title Number Appendix E Related DocumentationCont Appendix E Related Documentation4100U SPS/RPS Appendix F Compatible Actuating Devices List of Approved DevicesSimplex Range Conventional Detectors Hochiki Range Conventional Detectors Olsen Range Conventional DetectorsApollo Range Conventional Detectors Brooks Range Conventional Detectors Cerberus Range Conventional DetectorsSimplex Range Analog Addressable Sensors Simplex Mapnet 2 Range Addressable Field Devices Compatible Detectors, IdnetCompatible Addressable Field Devices, IDNet Appendix G Compatible Batteries Appendix H 4100U Specifications LCD Voltage & Current Ratings of Modules & AssembliesAppendix Power Supply & Battery Capacity Calculations Line Characteristics Appendix J Cable CharacteristicsNetwork Fibre Optic Cable CharacteristicsAppendix K List of Drawings
Related manuals
Manual 4 pages 36.11 Kb

4100U specifications

The Tyco 4100 series, which includes the 4100U, 4120, and 4020 models, represents a significant evolution in fire alarm and detection systems. These systems are designed to meet the needs of commercial, industrial, and institutional environments, ensuring reliable safety and compliance with the latest regulatory standards.

One of the primary features of the Tyco 4100 series is its modular design. This allows for easy expansion and customization to meet diverse application requirements. The systems support a wide range of detectors, initiating devices, and notification appliances, providing flexibility for different building layouts and fire protection needs.

The 4100U model is particularly noted for its powerful processing capabilities, utilizing advanced digital technology to enhance the speed and accuracy of fire detection. It includes sophisticated algorithms that optimize response times and reduce false alarms, ensuring that the system is both responsive and reliable during emergencies.

The 4120 model is tailored for larger facilities, incorporating advanced networking features that enable communication between multiple control panels. This interconnectedness is crucial for managing complex building systems, allowing for centralized monitoring and control. It integrates with a variety of life-safety systems and can be configured to accommodate a vast number of addressable points, making it ideal for expansive installations.

The 4020 model serves as a cost-effective solution for smaller establishments while maintaining essential functionalities. It focuses on delivering essential fire alarm capabilities without compromising on performance. Despite its more compact design, the 4020 still offers support for numerous devices and can be integrated into larger systems if needed.

All models in the 4100 series leverage modern communication technologies, offering network integration capabilities that enhance their usability. They support various communication protocols, including Ethernet, which facilitates remote monitoring and maintenance options via web-based interfaces. This ensures that system administrators can manage alerts and notifications from anywhere, streamlining incident response.

In summary, the Tyco 4100 series, featuring the 4100U, 4120, and 4020 models, stands out for its adaptability, technological advancements, and versatility. Their robust design caters effectively to diverse environments, making them a preferred choice for fire alarm and safety solutions in various sectors. Companies can rely on these systems not only for compliance but also for enhanced safety and operational efficiency.