Tyco installation manual Miniplex 4100U System

Page 23

MINIPLEX Configuration, Continued

RUI Communication

The 4100 internal comms bus may be used to carry data from the CPU in the main cabinet

 

to expansion equipment in a co-located cabinet. 4100 data from the CPU may be routed to

 

remote cabinets (RTUs) in a MINIPLEX system by using the external RUI comms bus.

 

An RUI line, routed from either the CPU Motherboard in the 4100U, or the RUI card in

 

the 4100, allows the data to travel long distances. Once the RUI line terminates at a

 

remote cabinet, the TIC (4100U) or RIC (4100) in that cabinet distributes the CPU’s data

 

to the other modules within the cabinet.

 

Power has to be supplied locally within each RTU, or routed from the main FIP.

 

Figure 1-2, below, outlines this process in a typical MINIPLEX setup.

from 4100U to Transponders

RUI

 

 

 

 

 

 

 

 

 

 

 

RUI I/F

 

Slave

 

9th Floor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Transponder

 

 

 

 

 

 

 

 

 

 

Slave

 

Slave

 

Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RUI I/F

 

Slave

 

6th Floor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Transponder

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit

 

 

Slave

 

Slave

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Transponders may be located further apart (within the 2500' limit) as called for by the application requirements.

 

 

 

 

 

 

 

 

 

 

 

RUI I/F

 

Slave

 

3rd Floor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Transponder

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit

 

 

Slave

 

Slave

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4100U

RUI Risers - 4 MAX (same channel) (from CPU Motherboard or Remote Unit Interface Card)

Note:

Although not shown, nested RUI is supported up to one level deep.

Figure 1-2. MINIPLEX 4100U System

1-5

Image 23
Contents 4100U Fire Indicator Panel Page Product / Site Copyrights and TrademarksApprovals ManufactureEnd User Liability Disclaimer Non-Disclosure AgreementAmendment Log Model Number & Firmware RevisionDocument Page Table of Contents Installing 4100U Facp Components Installing 4100 Miniplex Components Non-4100U Networking System Power Supply & Alarm Relay Card Installing 4100U IDNet & 4100MXP Cards PC Software Connections Appendix a The Device Configuration DIP Switch Appendix I Power Supply & Battery Capacity Calculations List of Figures Power and Communication Wiring for MotherboardsList of Tables Mounting onto the Power Distribution InterfaceXvi Topic See Page # Chapter Introduction to the 4100U Fire Alarm SystemSystem Configurations Standalone 4100U System Standalone ConfigurationMiniplex Configuration Miniplex 4100U System Hub/Ring Configuration Network ConfigurationInterconnected Loop Configuration PIDs Non-4100U 4100U PIDs 4100U Cabinet Part Identification Numbers PIDsKits Labels Looms Chapter Installing 4100U Facp Components Introduction to FACPs 4100U Master CPU Motherboard Master Controller Daughter Card LED4 LED3 LED2 LED1 Master Controller LEDs 1 throughOperator Interface System Power Supply Power Distribution Interface PDI Mounting Card Bays to Cabinets 4100U Mounting Cabinets 4100UConfiguring Cards 4100U Interconnecting Modules and Bays Interconnecting Modules and Bays Bay-to-Bay Interconnections Power and Communication Wiring for Motherboards Expansion Bay 4x 5 Card Placement Installing Modules into Expansion Bays 4100U10. Expansion Bay Motherboard Placement 11. Mixed Module Placement 12. Slave Card/PDI Connection 13. Installing the Motherboard in a 4100U Expansion Bay Installing LED/Switch Modules into Expansion Bays 4100U 14. LED/Switch Modules Occurs 16. LED/Switch Card Mounting 17. Controller Card Mounting 18. Assembling / Disassembling the LED Display Card 19. LED/Switch Controller Wiring 20. Terminal Block Utility Module Mounting Terminal Block Utility Module 4100UPage Chapter Installing 4100 Miniplex Components Non-4100U Introduction to Miniplex Systems Non-4100U Miniplex System Design Remote Unit Interface Card Miniplex System Components Non-4100URIC II Card Miniplex System Guidelines Non-4100U Installing the RUI Motherboard in the CPU Bay Installing Modules into Cabinets Non-4100UInstalling the RIC II Motherboard into a 4100 Expansion Bay Connecting the 733-525 Harness RIC Miniplex Wiring Non-4100U Miniplex Wiring Chapter Installing 4100U Miniplex Components Introduction to Miniplex Transponders 4100U Not currently available in Australia Transponder Interface Cards Local Mode Specifications Environmental Specifications TIC Specifications Electrical SpecificationsMiniplex System Guidelines 4100U Configuring Cards 4100U TIC Mounting TIC/Riser Mounting 4100UTransponder Cabinet Interconnections TIC/Motherboard Interconnections 4100UFerrite Bead RUI Wiring 4100UPage Chapter Networking Getting Started Introduction to the 4100 Network Interface Card NIC 6014 Network Interface Card UT Motherboard with City Connection 4100/4120-0143 Fiber-Optic Media Card Environmental Specifications All Modules Configuring Network CardsNIC Card Media Card Mounting Mounting Media Cards to the NICMounting Network Cards Installing the Daughter CardWiring Network Cards 8231 mm2 Wiring DistancesFiber Wiring Mifl Dual Fiber Optic Cable Communications Distance ExamplesConnected to the 4100-6014 NIC 10. Coupler Wiring11. Wired Media Interconnections Between 4100U Motherboards 12. Wired Media, Style 7 Wiring 13. Fiber Optic, Style 7 Wiring 14. Wired Media and Fiber Optic, Style 7 Wiring Page Chapter System Power Supply & Alarm Relay Card Battery Charger Specifications SPS SpecificationsSPS Input and Output Specifications AC Input Specifications DC Output SpecificationsAlarm Conditions Current SPS Current Specifications Standby ConditionsR341 Battery Charger Voltage SPS ConfigurationSPS has the following LEDs SPS LED IndicationsTroubleshooting on SPS Alarm Relay Card Alarm Relay CardCard Alarm Relay Card Jumper PositionsChapter SPS Field Wiring 4100U Ferrite Bead SX0005 General Field Wiring GuidelinesSPS NAC Field Wiring Guidelines Class a NAC Wiring Class B Wiring Power Supply Wiring DistancesClass a NAC Wiring Table Class B NAC Wiring Table SPS Auxiliary Power Wiring Auxiliary Power Wiring SPS Relay Wiring Auxiliary Relay & Alarm Relay Card Relays SPS Auxiliary Relay WiringSPS IDNet Wiring Class a Wiring Under AS1670.1 Class B wiring is allowed only for a maximum Chapter Installing 4100U IDNet & 4100MXP Cards IDNet Card IDNet Card36.5V max See below IDNet SpecificationsMounting onto the Power Distribution Interface Installing the IDNet Card onto the PDIMounting into 4100 legacy Bay Installing the ID-Net into a 4100 Card BayDIP Switch SW1 Configuring the CardWiring to IDNet Devices Cable Run Lengths Instructions Troubleshooting on IDNet 4100MXP Page Chapter PC Software Connections Software Modes Service and Diagnostic InterfaceBootloader Interface Page Chapter Australian Version Specifics Summary Of Australian Version Specifics Australian Panel Format 4100U Fan Control Module Switch/LED FormatSwitch Status Fan Control Module Brigade Interfaces Chapter Installation Checklist, Commissioning & Maintenance Cabinet & General Installation ChecklistAlignment & Adjustment Power Up & Placing into Operation Maintenance 11-6 Figure A-1. DIP Switch SWx Appendix a Device Configuration DIP SwitchTable A-1. Card Addresses Appendix B Programming Requirements Required FeaturesFigure D-1. Volt/Ohm Meter Readings Appendix C Checking System WiringTable C-1. Acceptable Zone and Signal Circuit Meter Readings Appendix C Checking System WiringAppendix D Earth Fault Detection General Guidelines Earth Fault Searching from the Front Panel Next and Previous buttons Result not Available Search Results Card 2, Idnet Card 250 Points Figure F-1. Earth Fault Example Earth Fault Search ExampleFind and repair the indicated fault on Transponder Book Part Title Number Appendix E Related DocumentationCont Appendix E Related Documentation4100U SPS/RPS Simplex Range Conventional Detectors Appendix F Compatible Actuating DevicesList of Approved Devices Apollo Range Conventional Detectors Hochiki Range Conventional DetectorsOlsen Range Conventional Detectors Simplex Range Analog Addressable Sensors Brooks Range Conventional DetectorsCerberus Range Conventional Detectors Simplex Mapnet 2 Range Addressable Field Devices Compatible Detectors, IdnetCompatible Addressable Field Devices, IDNet Appendix G Compatible Batteries Appendix H 4100U Specifications LCD Voltage & Current Ratings of Modules & AssembliesAppendix Power Supply & Battery Capacity Calculations Line Characteristics Appendix J Cable CharacteristicsNetwork Fibre Optic Cable CharacteristicsAppendix K List of Drawings
Related manuals
Manual 4 pages 36.11 Kb

4100U specifications

The Tyco 4100 series, which includes the 4100U, 4120, and 4020 models, represents a significant evolution in fire alarm and detection systems. These systems are designed to meet the needs of commercial, industrial, and institutional environments, ensuring reliable safety and compliance with the latest regulatory standards.

One of the primary features of the Tyco 4100 series is its modular design. This allows for easy expansion and customization to meet diverse application requirements. The systems support a wide range of detectors, initiating devices, and notification appliances, providing flexibility for different building layouts and fire protection needs.

The 4100U model is particularly noted for its powerful processing capabilities, utilizing advanced digital technology to enhance the speed and accuracy of fire detection. It includes sophisticated algorithms that optimize response times and reduce false alarms, ensuring that the system is both responsive and reliable during emergencies.

The 4120 model is tailored for larger facilities, incorporating advanced networking features that enable communication between multiple control panels. This interconnectedness is crucial for managing complex building systems, allowing for centralized monitoring and control. It integrates with a variety of life-safety systems and can be configured to accommodate a vast number of addressable points, making it ideal for expansive installations.

The 4020 model serves as a cost-effective solution for smaller establishments while maintaining essential functionalities. It focuses on delivering essential fire alarm capabilities without compromising on performance. Despite its more compact design, the 4020 still offers support for numerous devices and can be integrated into larger systems if needed.

All models in the 4100 series leverage modern communication technologies, offering network integration capabilities that enhance their usability. They support various communication protocols, including Ethernet, which facilitates remote monitoring and maintenance options via web-based interfaces. This ensures that system administrators can manage alerts and notifications from anywhere, streamlining incident response.

In summary, the Tyco 4100 series, featuring the 4100U, 4120, and 4020 models, stands out for its adaptability, technological advancements, and versatility. Their robust design caters effectively to diverse environments, making them a preferred choice for fire alarm and safety solutions in various sectors. Companies can rely on these systems not only for compliance but also for enhanced safety and operational efficiency.