First Alert FA168C-CN, FA168CP-CN manual Entry, Entries for Fields *182 and *184

Page 8

Configurable Zone Types Worksheets

Configurable zone types 90 and 91 can be programmed via downloader software or from a keypad using data fields*182-*185. Configurable zone types 92 and 93 (FA168C only) can only be programmed using the downloader software.

Programming Configurable Zone Type options involves making 10 entries in data field *182 for zone type 90 and

field *184 for zone type 91, where each entry represents the sum of the values of the various options shown in the tables below. Use fields *183 and *185 to program Contact ID report codes for these zone types.

ENTRY 1

(see note 5 for RF zones)

 

 

 

 

ENTRY 2

(see note 5 for RF zones)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Response when system disarmed and zone is:

 

 

Auto

 

 

 

 

Intact EOL

 

 

Open

 

 

 

 

 

Shorted

 

 

Restore

 

Vent Zone

 

 

RF zone normal

 

 

RF zone N/A

 

 

 

 

RF zn off-normal

 

 

 

 

 

 

0

= normal

 

 

0 = normal

 

 

 

0

= normal

0 = no

 

0 = no

 

1

= alarm

 

 

4

= alarm

 

 

 

1

= alarm

 

 

4 = yes

 

8 = yes

 

2

= trouble

 

 

8

= trouble

 

 

 

2

= trouble

 

 

 

 

 

 

3

= fault

 

 

12

= fault

 

 

 

3

= fault

 

 

 

 

 

 

Entry 1 = EOL + Open

 

 

Entry 2 =

 

Short + auto restore

+ vent zone

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ENTRY 3

(see note 5 for RF zones)

 

 

 

 

ENTRY 4

(see note 5 for RF zones)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Response when armed STAY and zone is:

 

 

 

 

Byp. when

 

Byp. when

 

 

Intact EOL

 

 

Open

 

 

 

 

 

Shorted

 

 

disarmed

 

armed

 

 

RF zone normal

 

 

RF zone N/A

 

 

 

 

RF zn off-normal

 

 

 

 

 

 

0

= normal

 

 

0 = normal

 

 

 

0

= normal

0 = no

 

0 = no

 

1

= alarm

 

 

4

= alarm

 

 

 

1

= alarm

 

 

4 = yes

 

8 = yes

 

2

= trouble

 

 

8

= trouble

 

 

 

2

= trouble

 

 

 

 

 

 

3

= fault

 

 

12

= fault

 

 

 

3

= fault

 

 

 

 

 

 

Entry 3 = EOL + Open

 

 

Entry 4

= Short + byp. disarmed

+ byp. armed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ENTRY 5

(see note 5 for RF zones)

 

 

 

 

ENTRY 6

(see note 5 for RF zones)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Response when armed AWAY and zone is:

 

 

 

 

Dial Delay

 

Fault Delay

 

 

Intact EOL

 

 

Open

 

 

 

 

 

Shorted

(see field *50)

 

(see field *87)

 

 

RF zone normal

 

 

RF zone N/A

 

 

 

 

RF zn off-normal

 

 

 

 

 

 

0

= normal

 

 

0 = normal

 

 

 

0

= normal

0 = no

 

0 = no

 

1

= alarm

 

 

4

= alarm

 

 

 

1

= alarm

 

 

4 = use delay

 

8 = use delay

 

2

= trouble

 

 

8

= trouble

 

 

 

2

= trouble

 

 

 

 

 

 

3

= fault

 

 

12

= fault

 

 

 

3

= fault

 

 

 

 

see note 1

 

Entry 5 = EOL + Open

 

 

Entry 6 =

 

Short + dial delay +

fault delay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ENTRY 7

 

 

 

 

 

 

 

 

 

ENTRY 8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Display Faults

 

 

Power Reset/

 

 

 

 

 

Use Entry

 

 

Use Exit

 

Respond as

 

 

 

 

 

Verification

 

 

 

 

 

Delay 1/2

 

 

Delay

 

Interior Type

 

0

= show alarms

 

0 = no

 

 

 

 

 

0 = no

 

 

 

 

0 = no

 

0 = no

 

 

when armed

 

 

4

= power reset

 

 

 

 

 

1 = delay 1

 

 

4 = use exit

 

8 = yes

 

 

& disarmed

 

 

after fault

 

 

 

 

 

2 = delay 2

 

 

delay

 

 

 

1

= don’t show

 

 

(by code + OFF)

 

 

 

 

 

 

 

 

 

 

 

 

see note 2

 

 

alarms when

 

12

= verification

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

armed

(show

 

 

(see zone

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

alarms, trbles,

 

 

type 16)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

faults when

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

disarmed)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

= never show

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

any alarms,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

trbles, faults

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Entry 7 = fault display

 

+ power

 

 

 

 

 

Entry 8 = entry delay 1/entry delay 2 + exit delay +

 

reset/verification

 

 

 

 

 

 

 

 

interior zone type

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ENTRY 9

 

 

 

 

 

 

 

 

 

 

 

 

ENTRY 10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarm Sounds

 

 

Use Bell

 

 

 

 

 

Respond as

 

 

 

Trouble

 

Chime when

 

 

 

 

 

 

Timeout

 

 

 

 

 

Fire Zone

 

 

 

Sounds

 

Chime Mode On

 

0

= none

 

 

0 = no

 

 

 

0 = no

 

 

0 = none

 

0 = no

 

1

= steady

 

 

4

= yes

 

 

8

= yes

 

 

1 = periodic

 

4 = yes

 

 

keypad

 

 

 

 

 

 

 

 

 

 

 

 

 

 

beep

 

 

 

2

= steady bell

 

see fields *32,

 

 

 

see zone type

 

2 = trouble

 

 

 

 

and keypad

 

*33

 

 

 

09; see note 4

 

 

 

beeps

 

 

 

3

= pulsing bell

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and keypad

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Entry 9 = alarm sounds + bell timeout + fire zone

Entry 10 = trouble sounds + chime

 

 

 

Entries for Fields *182 and *184

Entry Zone Type 90

Zone Type 91

(field *182)

(field *184)

1

2

3

4

5

6

7

8

9

10

To calculate the value for each entry:

Simply add the values of the selected options in each of the entry’s columns (one option per column). For example, to program Entry 2 for “alarm response to short,” “auto restore on,” but not a “vent zone,” enter 5 (“1” for alarm short + “4” for auto restore yes + “0” for vent zone no).

INTACT

OPEN

SHORTED

EOL

 

 

ZONE-003-V0

Zone Conditions Represented

in Entries 1-6

NOTES:

1.Do not use the “fault delay” option with a configurable zone type if it is set for an entry or exit delay, otherwise unpredictable results may occur.

2.To create an interior type zone, select “respond as interior zone type” (Entry 8, interior type = yes), and set zone

response to “fault” in entries 3-4 to ensure fault displays; do not set as “normal,” “alarm,” or “trouble.”

3.Do not set fire zones to respond as a

“fault” (entries 1-6), otherwise faults will

not display unless the [

] key is pressed.

4.4219/4229 modules must use EOLRs or unpredictable results may occur.

5.RF Zones: The “open” option in entries 1, 3, and 5 is not applicable for RF zones. Use the “intact EOL” option for normal RF zone conditions and “shorted” for off- normal RF zone conditions.

6.Zone-Doubling/Double-Balanced: A short

on either zone of a zone-doubled pair or on a double-balanced zone causes a tamper condition.

8

Image 8
Contents $&$&&1 $&3$&3&1 To Enter Programming Mode To Exit Programming ModeSystem Setup Power UP in Previous State Dialer ProgrammingField Function Programmable ValuesDynamic Signaling Priority Phone System SelectReport Format ARM AWAY/STAY RPT CodeRestore Report Codes Output and System SetupDownload Information Miscellaneous System Fields *174-*181Configurable Zone Type Zone Type 90 Report Codes Configurable Zone Type Zone Type 91 Report CodesKeypad Options *190-*196 ECP Fail DisplayZone Conditions Represented Entries EntryEntries for Fields *182 and *184 Zone Programming Worksheet Keypad Keypad ∗ / #Zone Lists for Output Devices Tampers of expansion units cannot be used to operate devices Alarm by Night Hour Silent AlarmAuxiliary Alarm Interior w/DelayKeyswitch Types Installer DefinedArm-Away Disarm000 061004 005UL installations RF Supervised RF TypeUR Unsupervised RF Type BR Unsupervised Button RF Type¬.35l
Related manuals
Manual 56 pages 7.94 Kb

FA168C-CN, FA168CP-CN, FA168CP, FA168C specifications

The First Alert FA168CP-CN, FA168C-CN, FA168C, and FA168CP are standout models in the realm of fire alarm technology, presenting an effective blend of advanced features, reliable performance, and user-friendly design.

A hallmark of these models is their dual-sensor technology, which combines both photoelectric and ionization sensors. This innovative approach allows for quicker detection of a wide range of fire types, from smoldering fires that typically produce more smoke to fast-flaming fires that generate more heat. This dual capability enhances the efficiency and response time of the alarm, ensuring users receive timely alerts.

Another prominent characteristic of these First Alert models is their comprehensive connectivity. Most models are equipped with a wireless interconnect feature, which allows multiple alarms throughout the home to communicate with one another. When one unit detects smoke or carbon monoxide, all interconnected alarms will sound, maximizing alertness across the property. This feature is particularly beneficial in larger homes or multi-story buildings, where sound may not travel freely.

The FA168 series also includes a built-in, non-replaceable lithium battery, providing up to 10 years of power. This design not only eliminates the need for constant battery replacements but also ensures that the unit remains functional for an extended period without hassle. A convenient low battery notification alerts users when it’s time to replace the entire unit, adding an extra layer of safety.

In terms of installation, these models offer a user-friendly design that makes setup and maintenance straightforward. The unit typically features a single test/silence button, allowing users to quickly test the alarm's functionality or silence false alarms with ease.

Furthermore, the clear LED indicators provide visual confirmation of the alarm status, keeping users informed about potential threats. Design-wise, the FA168 series models boast a sleek and modern aesthetic that can seamlessly blend into various interior environments.

Overall, the First Alert FA168CP-CN, FA168C-CN, FA168C, and FA168CP serve as reliable guardians against fire hazards, employing cutting-edge technology to offer peace of mind to users. With their formidable features, easy installation, and efficient power management, these fire alarm models stand as excellent choices for both homes and businesses seeking enhanced safety measures.