Combustion Air and Ventilation for Appliances Located in Unconfined Spaces

Unconfined Space is a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed, through openings not furnished with doors, are considered a part of the unconfined space

In unconfined spaces in buildings, infiltration may be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in buildings of tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), additional air may need to be provided using the methods described in Combustion Air and Ventilation for Appliances Located in Confined Spaces, b.

1.When directly communicating with the outdoors, each open- ing shall have a minimum free area of 1 square inch per 4,000 BTU per hour of total input rating of all equipment in the endusure. (See Figure 3.)

2.When communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4,000 BTU per hour of total input rating of all equipment'in the enclosure. (See Figure 4.)

_4_qEY OR OA8 gZhT

Combustion Air and Ventilation

for Appliances Located in Confined Spaces

Con.rmed Space is a space whose volume is less than 50 cubic feet per 1,000 Btu per hour off,the aggregate input rating of all appliances installed in that space.

a. ALL AIR FROM INSIDE BUILDINGS:

(See Page 9 Figure 1, and Figure 2 below)

The confined space shall be provided with two permanent openings communicating directly with an additional room(s) oF suff*lcient volume so that the combined volume of all spaces meets the criteria for an unconfined space. The total input of all gas utilization equipment installed in the com-

bined space shall be considered in making this determination. Each opening shall have a minimum free area of one square

inch per 1,000 BTU per hour of the total input rating ofail gas utilization equipment in the confined space, but not less than 100 square inches. One opening shall commence within 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure.

_SRT

Figure 2 ]

[ [ , ....

b. ALL AIR FROM OUTDOORS: (see Figures 3-5)

The confined space shall be provided with two permanent openings, one commencing within 12 inches of the top and one commencing within 12 inches from the bottom of the enclosure. The openings shall communicate directly, or by

ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.

Figure 3 ]

Figure 4 ]

3.When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1

square inch per 2,000 BTU per hour of total input rating of all equipment in the enclosure. (See Figure 5.)

Figure 5 1

4.When ducts are used, they sha_ be of the same cruss-sectlonal area as the free area of the openings to which they connect. The minimum short side dimension of rectangular air ducts shall not be less than 3 inches. (See Figure5.)

. Louvers and Grilles: In calculating free area, consideration shall be given to the blocking effect of louvers, grilles or screens protecting openings. Screens used shall not be smaller than ¼ inch mesh. If the free area through a design of louver or grille is known, it should be used in calculating the size opening required to provide the free area specified. If the design and free area is not known, it may be assumed that wood louvers will be 20-25 percent free areaand metal louvers and grilles will have 60-75percent free area. Louvers and grilles shall be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation.

. Special Conditions Created by Mechanical Exhausting or Fireplaces: Operation of exhaust fans, ventilation systems, clothes dryers or firephcea may create conditions requiring special attention to avoid unsatisfactory operation of ii_talled gas utilization equipment.

10

Image 10
Contents What to do if YOU Smell GAS For Your SafetyAN Odorant is Added to the GAS Used by this Water Heater AwarningSafety Precautions IwarningSafety Precautions Burner Contents Product Specifications Customer ResponsibilitiesMaterials Needed Materials and Basic Tools NeededBasic Tools Installation Instructions Removing the Old Water HeaterInstallation Instructions contd Facts to Consider About LocationALL AIR from Inside Buildings Installation Instructions contdALL AIR from Outdoors see Figures Hotter Water can SCALD.Water heatersare intendedto Water PipingRs. Theseincludetheelder,children,the infirm,or physical BTU/Hr. rate Iraln unlessa 6 air gapisprovided,To preventbodilyinjury,hazIAWARNING1 Filling the Water HeaterVenting Healthrisk or asphyxiationGas Piping ContdVenting contd Be surevent pipeisproperly connectedto preventescapeofSediment Trap GAS Piping with Flexible ConnectorGAS Piping with ALL Black Iron Pipe to GAS Control Contd Installation InstructionsInstallation Checklist Venting instructionsLighting Operating InstructionsCheck for Leaks Operating Instructions contd Set the thermostatto lowest setting by turningReplaceouterdoorif removed Temperature Regulation Hotter Watercan SCALDWater heatersare intendedtoTank Sediment Cleaning Service and AdjustmentBurner Cleaning Venting System InspectionGas Control Valve & Burner Service and Adjustment contdAssembly Replacement InformationContact Sears Repair Services at 1-800-4-MY-HOME Service and Adjustment contdDrain Valve Washer Replacement HousekeepingStart Up Conditions Troubleshooting GuideThermal Expansion SMOKE/ODOR Start Up Conditions contdCondensation Smelly WaterNot Enough or no HOT Water Troubleshooting Guide contdHigh Temperature Shut OFF System Water is TOO HOTLeakage Checkpoints Page Page Page 3O Gal Gal. Short High AltitudeGal. Short Gal. High AltitudeParts Order List contd Parts Order List contd 153.337514 50 Gal. High Altitude 153.337563 50 Gal9000071 153.337463 40 Gal 153.337514 50 Gal. High Altitude153.337614 65 Gal. High Altitude Model Ratin Plate t O27O118153.337663 65 Gal 153.337763 50 Gal. High Recovery Manifold Cover Restrictor Ring # Manual # Mag-EradWarranty Improperventing

153.337363, 153.337463, 153.337563, 153.337863, 153.337214 specifications

The Kenmore line of appliances has long been synonymous with reliability and performance. Among its popular products are the Kenmore models 153.337214, 153.337663, 153.337563, 153.337463, and 153.337863. Each of these models offers a set of features designed to enhance the user experience and provide superior functionality.

One of the defining characteristics of these Kenmore models is their advanced technology. These units integrate innovative features such as smart connectivity, allowing users to monitor and control their appliances remotely via smartphone apps. This integration not only provides convenience but also aids in energy management, helping users save on energy costs while ensuring that their appliances are operating at peak efficiency.

The design of the Kenmore models also emphasizes user-friendly interfaces. Many of the units come equipped with touch controls and LED displays, making them simple to operate and program. This intuitive design is coupled with features like delayed start options and multiple cooking modes, catering to the diverse needs of modern households.

In terms of performance, Kenmore's 153.337214, 153.337663, 153.337563, 153.337463, and 153.337863 models showcase impressive energy efficiency ratings. Each model is engineered to minimize power consumption while maintaining high levels of performance, making them an eco-friendly choice for savvy consumers. Furthermore, these appliances often include features such as self-cleaning capabilities and noise-reduction technologies, ensuring that they are not only effective but also considerate of the user's comfort.

Safety is another priority in the design of these models. They come equipped with features such as auto shut-off, child locks, and safety sensors to ensure peace of mind for families. This commitment to safety, combined with a reputation for durability, means that Kenmore appliances are a trusted choice for many households.

In summary, Kenmore models 153.337214, 153.337663, 153.337563, 153.337463, and 153.337863 represent the brand's dedication to quality, innovation, and user satisfaction. With advanced technology, user-friendly designs, energy efficiency, and safety features, these appliances are well equipped to meet the demands of contemporary living while providing a reliable solution for everyday household tasks. Whether for cooking, cleaning, or other chores, these models are a testament to Kenmore's legacy of excellence in home appliances.