All installations and services must be performed by qualified service personnel.

APPENDIX C: TROUBLESHOOTING FLOWCHARTS

A. Heating System

Set thermostat subbase to "HEAT".

Does thermostat make contact?

No

Is room temperature

above thermostat setting?

Yes

Turn thermostat setting

above room temp.

No

Yes

Is the transformer supplying

Yes

 

24 VAC to the thermostat ?

Replace thermostat.

No

 

Are the thermostat wires connected

No

Correct wire

properly?

connections.

Yes

Is the control transformer

receiving 120 VAC?

No

Check input power,control system fuse,disconnecting switch and fuses (if equipped).

Yes

Replace control transformer.

Is the inducer

blower operating?

No

Is there 24 VAC across

"TH" & "TR" terminals of the

ignition control module.

No

Check for continuity & proper connections

Yes

Yes

45

Page 48
Image 48
Thermo Products MDA1-50N, MHA1-75N, MHA1-100N, MHA1-50N, MHA1-125N Appendix C Troubleshooting Flowcharts, Heating System