All installations and services must be performed by qualified service personnel.
Yes
Does system run until thermostat is satisfied?
Yes
No |
| No |
|
Is LED light on ignition |
| ||
| control module flashing? |
|
|
|
|
| |
|
|
|
|
Yes
If LED Light Flashes: |
| |
1 | Flash, then pause | System lockout |
2 | Flashes, then pause | Pressure switch stuck closed |
3 | Flashes, then pause | Pressure switch stuck open |
4 | Flashes, then pause | Open high limit, aux. limit, or |
6 | Flashes, then pause | 115 Volt AC power reversed |
7 | Flashes, then pause | Low flame sense signal |
8 | Flashes, then pause | Check ignitor or improper grounding |
Continuous flashing | Flame has been sensed when no flame | |
| (no pause) | should be present (no call for heat) |
Check all wiring for loose connections.
Does burner shut off | No |
when thermostat is |
|
| |
satisfied? |
|
|
|
Yes |
Does the circulating air | No |
blower turn off after | |
thermostat is satisfied |
|
within 180 seconds? |
|
Yes
Troubleshooting Complete.
Check for short in wire to
thermostat. Replace
thermostat if necessary.
Check DIP switch settings on ignition control module against those on connection diagram. Reset if necessary.
48