All installations and services must be performed by qualified service personnel.

Yes

Does system run until thermostat is satisfied?

Yes

No

 

No

 

Is LED light on ignition

 

 

control module flashing?

 

 

 

 

 

 

 

 

 

Yes

If LED Light Flashes:

 

1

Flash, then pause

System lockout

2

Flashes, then pause

Pressure switch stuck closed

3

Flashes, then pause

Pressure switch stuck open

4

Flashes, then pause

Open high limit, aux. limit, or roll-out switch

6

Flashes, then pause

115 Volt AC power reversed

7

Flashes, then pause

Low flame sense signal

8

Flashes, then pause

Check ignitor or improper grounding

Continuous flashing

Flame has been sensed when no flame

 

(no pause)

should be present (no call for heat)

Check all wiring for loose connections.

Does burner shut off

No

when thermostat is

 

 

satisfied?

 

 

 

Yes

Does the circulating air

No

blower turn off after

thermostat is satisfied

 

within 180 seconds?

 

Yes

Troubleshooting Complete.

Check for short in wire to

thermostat. Replace

thermostat if necessary.

Check DIP switch settings on ignition control module against those on connection diagram. Reset if necessary.