All installations and services must be performed by qualified service personnel.

Yes

No

After gas valve opens, do the burners ignite?

Measure gas supply pressure

No

at inlet to gas valve. Is it at

least 4.5" W.G. for natural gas

 

or 11" W.G. for L.P. gases?

 

Yes

Check ignitor voltage.

No

during 20 second warm-up,

it should be at least 105

 

VAC.

 

Check gas supply. Open all manual gas control valves serving the unit.

Correct low line voltage

problem or replace ignition

control module.

Yes

Is ignitor positioned

correctly?

Yes

No

Reposition to correct location.

Do burners stay lit

No

past proof of flame

 

check?

 

 

 

Yes

Does the ignition control

module energize the circulating air blower after the 45 second time delay?

Check for blocked or severely

corroded burners or burner orifices.

Clean or replace as required.

Yes

 

 

 

 

Measure supply & manifold

No

 

 

 

 

pressures. Are they constant

 

 

over time and within the allowable

 

 

 

 

 

 

 

ranges?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check DIP switch settings on

 

 

 

 

 

 

 

 

ignition control module against

 

 

 

 

No

 

 

those on connection diagram.

 

 

 

 

 

 

Is blower still inoperable after

 

 

 

 

 

 

 

 

time delay with DIP switches

 

 

 

 

 

 

 

 

set correctly?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Measure voltage on the

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

circulating air blower

 

 

 

 

 

 

 

terminals "CIR N " &

 

 

 

 

 

 

 

 

 

"HEAT". Is it 120 VAC?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Adjust supply pressure to 4.5" W.G. for natural & 11" W.G. for LP gases. Adjust manifold pressure to 3.5" W.G. for natural gas or 10" W.G. for LP gases. If gas pressure fluctuates, a pressure regulator may be required or gas piping

may be too small for flow.

Check wiring to blower. If okay,

replace the ignition control

module.

Yes

 

Yes

Does the circulating

 

air fan come on

 

when energized?

Check for blower wheel

No

Does blower wheel

spin freely?

Yes

No

rubbing against housing or motor shaft spinning freely. Adjust or replace as necessary.

Is blower motor capacitor

No

working properly?

 

Yes

Replace Motor

Replace blower motor capacitor

47