Thermo Products MHA1-125N, MDA1-50N, MHA1-75N, MHA1-100N, MHA1-50N, MDA1-75N, MDA1-125N Range of

Models: MDA1-100N MDA1-125N MDA1-75N MHA1-125N MHA1-50N MHA1-100N MHA1-75N MDA1-50N

1 61
Download 61 pages 24.2 Kb
Page 36
Image 36

All installations and services must be performed by qualified service personnel.

3.The following formula may be used to calculate the heat input rate for the appliance:

Gas heating value x Amount of gas consumed = Heat input rate, or Amount of time required to consume the gas

BTU/cu ft x Number of cu ft x 3600 seconds = Input rate (BTU/hr). Seconds for one revolution x 1 hour

In cases where a gas meter is not installed on the fuel gas supply line, the input rate can be assumed to be approximately correct if the burner manifold pressure is the same as that shown on the rating label.

Make sure the gas supply pressure at the appliance falls within the allowable range for the type of fuel gas. See table 8. The pressure to the furnace must be checked while the burner, and any other gas appliances, on the same supply system are operating. Measure the pressure using a pressure gauge, or manometer, at the 1/8 in. NPT plugged tap on the inlet side of the appliance gas control valve, shown in the General Gas Piping Requirements section of this manual. An Allen wrench is normally required to remove the plug from the valve.

Make sure the fuel gas is shut off before removing this plug and installing a pressure test gage.

Table 8: Allowable Gas Pressures for All MHA1/MDA1 Models

 

Range of

Manifold

Type of

Supply

Pressure

Fuel Gas

Pressure

(in. W.G.)

 

(in. W.G.)

 

 

Natural

14.0 - 4.5

3.5 (± .3)

 

 

 

Propane

14.0 - 11.0

10.0 (±. 3)

 

 

 

This appliance is equipped with multiple, identical, fixed, main burner orifices sized for the fuel gas and manifold pressure shown on the rating label. The input rate can only be increased, or decreased, by adjusting the manifold pressure.

To adjust the manifold gas pressure to the main burners:

a.With the gas shutoff, remove the 1/8 in. NPT threaded pipe plug located on the front side of the main burner gas manifold. Use a U-tube manometer or pressure gage, capable of measuring pressure in inches of water column, to measure the gas pressure at this point.

33

Page 36
Image 36
Thermo Products MHA1-125N, MDA1-50N, MHA1-75N, MHA1-100N, MHA1-50N, MDA1-75N, MDA1-125N, MDA1-100N service manual Range of