Thermo Products MDA1-125N Mode of Operation, Control System Action, Standby At any time the gas

Models: MDA1-100N MDA1-125N MDA1-75N MHA1-125N MHA1-50N MHA1-100N MHA1-75N MDA1-50N

1 61
Download 61 pages 24.2 Kb
Page 46
Image 46
Mode of Operation

All installations and services must be performed by qualified service personnel.

APPENDIX B: SEQUENCE OF OPERATIONS

A. Sequence of Operations for Heating System

Mode of Operation

Standby (At any time the gas

valve is not energized)

Control System Action

Continous safe operation check. If flame simulation condition present or roll-out switch opens,system energizes inducer fan and circulator blower at high speed until situation correction occurs.

Start

Start trial for ignition

Thermostat calls for heat,

contacts close

Ignition control module

energized,draft inducer starts.

Pressure switch senses

adequate pressure,

contacts close.

 

 

 

 

 

 

 

 

Power is applied to the hot

 

On power interruption, system

surface ignitor. Ignitor warms-

 

 

shuts off, restarts when

 

up for 20 seconds.

 

 

power is restored.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

After ignitor warm-up, the

 

 

 

 

 

 

automatic gas control valve

 

 

 

 

 

 

 

is energized to open.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If flame is not detected, the

Flame must be detected

 

 

 

 

 

gas valve is de-energized,

within 4 seconds. If flame

 

 

 

 

 

 

the ignitor is turned off and

detected, the delay-to-fan-

 

 

 

 

 

 

the ignition control module

on time begins (45 seconds)

 

 

 

 

 

goes into the "Retry" sequence.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The retry sequence provides a 60 second wait before ignition retry.

43

Page 46
Image 46
Thermo Products MDA1-125N Mode of Operation, Control System Action, Standby At any time the gas, valve is not energized