All installations and services must be performed by qualified service personnel.
Yes | Yes |
Is there 120 VAC across draft inducer power terminals "IND"
&"IND N" at the ignition control module?
No
Yes
After
hot surface ignitor energize
and glow?
Yes
After hot surface ignitor
Yes
Check wiring to draft inducer.
If okay, replace inducer assembly.
| No |
|
|
|
|
| |
| Is there voltage present at the | No | |
|
| ||
|
| hot surface ignitor terminals |
|
|
|
| |
|
| "IGN" & "IGN N" at the ignition |
|
|
| control module? |
|
|
|
|
|
|
|
|
|
Yes
Check wiring to hot surface ignitor. If okay, replace hot surface ignitor assembly.
| No | Check across "MV" terminals |
| ||
|
| on ignition control module for 24 |
|
| VAC during the 4 second flame |
|
| proving period after ignitor |
|
| |
|
|
|
Yes
Check the ignition control module diagnostic LED lamp. Reset the module by interrupting power to system for more than one second. If LED stays on continuously, replace ignition control module.
No
Check wiring to gas valve. If okay, Replace gas valve.
46