All installations and services must be performed by qualified service personnel.
Mode of Operation | Control System Action |
Main Burner
Operation
Repeated Trials for Ignition.
Call for Heat
Satisfied
System Lockout
After
When thermostat is satisfied, contacts open and the gas valve is
If ignition attempt is unsuccessful, one more retry will be made before the ignition control module goes into system lockout.
If flame is detected,then lost, the ignition control module will repeat the initial ignition sequence for a total of four recycles. After four unsuccessful recycle attempts, the control will go into system lockout. The ignition control module will reset automatically in 60 minutes.
If system is in lockout, try to reset by interrupting the power
to the furnace at the disconnecting switch or interrupting the call for heat at the thermostat. If this does
not restart the system, refer to the troubleshooting section of this manual.
End of Cycle | After the |
| period ends, the circulating |
| air fan and {optional) |
| electronic air cleaner are |
|