dIXEL | Operating Instructions XWA11V | 1598003200 |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
14. | PARAMETER LIST |
|
|
| |
Ot | Thermostat probe calibration: |
| |||
|
| thermostat probe. |
|
|
|
CF | T measurement unit: °C = Celsius; °F = Fahrenheit. When the measurement unit is changed the Set |
| |||
|
| Point and the values of some parameters have to be modified. |
|
| |
rES | Resolution (for °C): (in = 1°C; dE = 0.1 °C) allows decimal point display. |
|
| ||
Ut | Display update: The time delay of the T readout (0÷255s) |
|
| ||
onF | Off function enabling: n = off function disabled; y = off function enabled; |
|
| ||
ALU | High T° alarm setting: (ALL ⎟ 150°C or 302°F); |
|
| ||
|
| when this T° is reached and after the ALd delay time the HA alarm is enabled. |
|
| |
ALL | Low T° alarm setting: (- 50°C or |
|
| ||
|
| when this T° is reached and after the ALd delay time, the LA alarm is enabled,. |
|
| |
AFH | T° alarm differential: (0,1÷25,5°C; 1÷45°F) differential for T° alarm Set Point and fan regulation Set |
| |||
|
| Point, always a positive value |
|
| |
ALd | T° alarm delay: (0÷255 min) time interval between the detection of an alarm condition and the |
| |||
|
| corresponding alarm signaling. |
|
| |
dAO | Delay of T° alarm at |
| |||
|
| condition after the instrument power on and the alarm signaling. |
|
| |
EdA | Alarm delay at the end of defrost: (0⎟255 min) Time interval between the detection of the T° alarm |
| |||
|
| condition at the end of defrost and the alarm signaling. |
|
| |
dot | Delay of T° alarm after closing the door: (0⎟255 min) Time delay to signal the T° alarm | condition |
| ||
|
| after closing the door. |
|
|
|
LHt | Light timer: |
| |||
doA | Open door alarm delay:(0÷255 min) delay between the detection of the open door condition and its |
| |||
|
| alarm signaling: the flashing message “dA” is displayed. |
|
| |
oA1 | First relay configuration: |
|
| ||
oA2 | Second relay configuration: |
|
| ||
AOP | Alarm relay polarity: cL = closing contacts; oP = opening contacts. |
|
| ||
i1P | Digital input 1 polarity |
|
| ||
OP | the digital input is activated by opening the contact |
|
| ||
i1L | Door switch to turn light |
| |||
|
| The light will turn off based on LHt . Keyboard switch must be turned ON first. |
|
| |
i1F | Digital input 1 operating |
| |||
|
| running; LHt = keep light ON (signal from occupancy sensor) override LHt.; |
|
| |
i2P | Digital input 2 polarity |
|
| ||
OP | the digital input is activated by opening the contact |
|
| ||
i2F | Digital input 2 operating mode: configure the digital input function: |
|
| ||
EAL | = External alarm; |
|
|
| |
PAn | =Panic alarm; |
|
|
| |
dFr = A defrost is running; |
|
|
| ||
LHt = Keep light ON (signal from occupancy sensor) override LHt. |
|
| |||
did | Time interval/delay for digital input alarm:(0⎟255 min.) If I2F=EAL or PAn (external alarms), “did” |
| |||
|
| parameter defines the time delay between the detection and the successive signaling of the alarm. |
| ||
tbA | Alarm relay & Buzzer disabling: (y ; no) |
|
| ||
Pbc | Type of probe (PTC, NTC) |
|
|
| |
dP1 | Probe 1 T |
|
|
| |
rEL | Software release for internal use. |
|
| ||
Ptb | Parameter table code: read only. |
|
|
Weiss Instruments, Inc. 905 Waverly Ave. Holtsville, NY 11742 | 8 |