Carrier 58MCA instruction manual ÐElectrical Controls and Wiring, Furnace

Page 8

Allow ignitor to cool before removal. Normal operation temperatures exceed 2000°F.

a.Do not remove ignitor from retainer while assembly is in furnace. Using a small pocket straight-blade screwdriver, slowly pry 1 edge of the spring retainer from burner box housing. While working ignitor assembly loose, grasp white ceramic block to wiggle assembly (ignitor and retainer) from its location.

13 32"

BURNER

BURNER BOX

11 32"

CELL

PANEL

IGNITOR

ASSEMBLY

The ignitor is fragile. DO NOT allow it to hit the side of the burner box opening while removing or replacing it.

b.Inspect ignitor for a white area indicating a crack may be present. If found, replace ignitor.

NOTE: A small crack cannot be seen on a new ignitor. After a period of operation, a white area will be visible around the crack.

c. If replacement is required, replace ignitor on ignitor re- tainer external to furnace to avoid damage as the silicon portion is very brittle and will easily crack or shatter.

d.To remove ignitor from ignitor retainer, apply pressure on bottom/side clips to release pressure on ignitor ceramic block. Slowly work ceramic block out of spring retainer.

6.To replace ignitor/ignitor assembly, reverse items 5a through 5d. (See Fig. 11.)

7.Reconnect ignitor wire connection.

8.Turn on gas and electrical supplies to furnace.

9.Verify ignitor operation by initiating control board self-test feature or by cycling thermostat.

10.Replace main furnace door.

C IGNITOR

L

7 8"

C BURNER

L

IGNITOR

ASSEMBLY

A93260

Fig. 11ÐHot Surface Ignitor Location and Burner

Assembly

Step 7ÐElectrical Controls and Wiring

There may be more than 1 electrical supply to the unit. Check accessories and cooling unit for additional electrical supplies.

The electrical ground and polarity for 115-v wiring must be maintained properly. Refer to Fig. 12 for field wiring information and to Fig. 16 for unit wiring information.

FIELD 24-VOLT WIRING

FIELD 115-, 208/230-, 460-VOLT WIRING

FACTORY 24-VOLT WIRING

FACTORY 115-VOLT WIRING

 

 

 

NOTE 2

 

 

 

THERMOSTAT

 

 

 

FIVE

W

C R

G

Y

FIELD-SUPPLIED

 

 

TERMINALS

 

 

 

 

 

 

 

 

WIRE

 

 

 

 

 

FUSED DISCONNECT

 

 

THREE-WIRE

 

 

 

 

 

208/230- OR

 

 

HEATING-

 

 

 

 

 

 

 

ONLY

 

 

 

 

 

460-VOLT

 

 

 

 

 

 

 

 

THREE

BLK

BLK

 

W

 

 

 

 

PHASE

 

 

 

 

 

 

 

 

 

 

 

 

 

WHT

WHT

 

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-

GND

 

GND

 

 

 

 

 

VOLT

115-VOLT FUSED

AUXILIARY

G

 

 

 

 

SINGLE

 

 

 

 

 

PHASE

DISCONNECT

J-BOX

C

NOTE 1

 

 

 

GND

SWITCH

 

CONTROL

Y

 

 

CONDENSING

(WHEN

 

BOX

 

 

 

UNIT

 

 

 

 

 

 

 

REQUIRED)

 

24-VOLT

 

 

 

TWO

 

 

 

 

 

 

 

 

 

TERMINAL

 

 

 

WIRE

 

 

 

 

BLOCK

NOTES: 1.

Connect Y-terminal as shown for proper operation.

 

 

FURNACE

 

 

 

2.￿ Some thermostats require a "C" terminal connection as shown.

 

 

 

 

 

3.If any of the original wire, as supplied, must be replaced, use same type or equivalent wire.

A96415

Fig. 12ÐField Wiring

8

Image 8
Contents Service and Maintenance Instructions ÐMultipoise Orientations ÐCleaning and/or Replacing Air Filter ÐBlower Motor and Wheel MaintenanceÐCleaning Burners ÐSpeed SelectorÐCleaning Heat Exchangers Primary Heat ExchangersInstallation ÐFlushing Collector Box and Drainage System ÐServicing Hot Surface IgnitorÐElectrical Controls and Wiring FurnaceÐTroubleshooting Component Test SequenceÐChecking Heat Tape Operation If Applicable ÐWinterizingÐInducer Housing Drain Tube ÐWiring Diagram Service Troubleshooting Guide A96219 Service Training
Related manuals
Manual 12 pages 2.11 Kb