Allow ignitor to cool before removal. Normal operation temperatures exceed 2000°F.
a.Do not remove ignitor from retainer while assembly is in furnace. Using a small pocket
13 32"
BURNER |
BURNER BOX
11 32"
CELL |
PANEL |
IGNITOR |
ASSEMBLY |
The ignitor is fragile. DO NOT allow it to hit the side of the burner box opening while removing or replacing it.
b.Inspect ignitor for a white area indicating a crack may be present. If found, replace ignitor.
NOTE: A small crack cannot be seen on a new ignitor. After a period of operation, a white area will be visible around the crack.
c. If replacement is required, replace ignitor on ignitor re- tainer external to furnace to avoid damage as the silicon portion is very brittle and will easily crack or shatter.
d.To remove ignitor from ignitor retainer, apply pressure on bottom/side clips to release pressure on ignitor ceramic block. Slowly work ceramic block out of spring retainer.
6.To replace ignitor/ignitor assembly, reverse items 5a through 5d. (See Fig. 11.)
7.Reconnect ignitor wire connection.
8.Turn on gas and electrical supplies to furnace.
9.Verify ignitor operation by initiating control board
10.Replace main furnace door.
C IGNITOR
L
7 8"
C BURNER
L
IGNITOR
ASSEMBLY
A93260
Fig. 11ÐHot Surface Ignitor Location and Burner
Assembly
Step 7ÐElectrical Controls and Wiring
There may be more than 1 electrical supply to the unit. Check accessories and cooling unit for additional electrical supplies.
The electrical ground and polarity for
FIELD
FIELD
FACTORY
FACTORY
|
|
| NOTE 2 |
|
|
| THERMOSTAT |
|
|
| FIVE | W | C R | G | Y | ||
|
| TERMINALS | ||||||
|
|
|
|
|
| |||
|
| WIRE |
|
|
|
|
| FUSED DISCONNECT |
|
|
|
|
|
|
| 208/230- OR | |
|
| HEATING- |
|
|
|
|
| |
|
| ONLY |
|
|
|
|
| |
|
|
|
|
|
|
|
| THREE |
BLK | BLK |
| W |
|
|
|
| PHASE |
|
|
|
|
|
| |||
|
|
|
|
|
|
| ||
WHT | WHT |
| R |
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| 208/230- |
GND |
| GND |
|
|
|
|
| VOLT |
AUXILIARY | G |
|
|
|
| SINGLE | ||
|
|
|
|
| PHASE | |||
DISCONNECT | C | NOTE 1 |
|
|
| GND | ||
SWITCH |
| CONTROL | Y |
|
| CONDENSING | ||
(WHEN |
| BOX |
|
|
| UNIT |
| |
|
|
|
|
|
| |||
REQUIRED) |
|
|
|
| TWO |
| ||
|
|
|
|
|
| |||
|
| TERMINAL |
|
|
| WIRE |
| |
|
|
| BLOCK | NOTES: 1. | Connect | |||
|
| FURNACE | ||||||
|
|
| 2. Some thermostats require a "C" terminal connection as shown. | |||||
|
|
|
|
|
3.If any of the original wire, as supplied, must be replaced, use same type or equivalent wire.
A96415
→Fig. 12ÐField Wiring