15
11NO PREVIOUS FAULT - Faults are erased after 48 hrs or whenever power (115v or 24v) is interrupted. Run system through a heating or cooling cycle to check system.
12BLOWER ON AFTER POWER UP (115V OR 24V) - Normal operation. Blower will run for 90 sec when furnace power is interrupted during a call for heat,
13LIMIT OR FLAME ROLLOUT SWITCH LOCKOUT -
Limit switch was open longer than 3 minutes.
See No. 33
14IGNITION LOCKOUT - System failed to ignite gas and prove flame in 4 attempts. Control will
See No. 34
21GAS HEATING LOCKOUT - Turn off power and wait 5 minutes to retry.
Check for:
•Stuck closed gas valve relay on control.
•Miswire or short to gas valve wire.
22ABNORMAL FLAME PROVING SIGNAL - Flame was sensed while gas valve was
Check for:
•Stuck open gas valve solenoid or leak.
•Defective control center.
23PRESSURE SWITCH WILL NOT OPEN - Check for:
•Disconnected or obstructed pressure tubing.
•Defective pressure switch.
24LOW-VOLTAGE FUSE IS OPEN - Check for:
•Short in
31PRESSURE SWITCH WILL NOT CLOSE OR REOPEN - If open longer than 5 minutes, inducer shuts off for 15 minutes before retry.
Check for:
•Proper vent sizing or pitch or sag.
•Vent restrictions or high winds.
•Defective inducer motor.
•Low line voltage (115v).
•Motor start capacitor.
•Low inlet gas pressure.
•Defective pressure switch or connections. If it opens after trial for ignition period, blower will come on for 90 sec recycle delay.
•Inadequate combustion air.
33 LIMIT OR FLAME ROLLOUT |
| ||
SWITCH IS OPEN - If |
| ||
limit switch is open longer than 3 |
| ||
minutes, code changes to No. 13. |
| ||
Check for: |
| ||
• | Blower motor failure. |
| |
• | Motor start capacitor. |
| |
• Open flame rollout switch, |
| ||
| manual reset. |
| |
• | Inadequate combustion air |
| |
| supply (flame rollout switch |
| |
| only). |
| |
• | Dirty filter. |
| |
• Defective limit switch or |
| ||
| connections. |
| |
• | Loose blower wheel. |
| |
|
| ||
|
| ||
34 IGNITION PROVING FAILURE - |
| ||
If flame is not sensed during the |
| ||
trial for ignition period, the control |
| ||
will repeat the ignition sequence |
| ||
3 more times before going into |
| ||
lockout, No. 14. |
| ||
If flame signal is lost after trial for |
| ||
ignition period, blower will come |
| ||
on for |
| ||
Check for the following items first |
| ||
before proceding to the next step. |
| ||
• Gas valve turned off. |
| ||
• Manual | NO | ||
• Green wire must be connected | |||
| |||
| to furnace sheet metal. |
| |
To determine whether the |
| ||
problem is in the gas valve, |
| ||
ignitor, or flame sensor, the |
| ||
system can be operated in the |
| ||
component test mode to check |
| ||
the ignitor. First, remove the |
| ||
R thermostat connection from the |
| ||
control center and initiate the |
| ||
component test sequence. Does |
| ||
the ignitor glow orange/white hot |
| ||
by the end of the |
| ||
period? |
| ||
|
|
| |
| YES |
|
Unplug ignitor harness from control |
| |
center and inititate another |
| |
component test sequence. Check | NO | |
for 115v between pins 1 and 2 on |
| |
the control center. Was 115v present |
| |
for the |
| |
|
|
|
| YES |
|
|
|
|
Check for continuity in the harness |
| |
and ignitor. Replace defective |
| |
component. |
| |
|
|
|
Reconnect the R thermostat lead |
| ||
and set thermostat to call for heat. | NO | ||
Connect voltmeter across gas valve | |||
| |||
connections. Does gas valve |
| ||
receive 24v? |
| ||
|
|
| |
| YES |
|
Does gas valve open and allow gas | NO | ||
to flow? |
| ||
|
|
| |
| YES |
| |
|
| NO | |
Do main burners ignite? | |||
| |||
|
|
| |
| YES |
| |
|
| NO | |
Do main burners stay on? | |||
| |||
|
|
| |
| YES |
| |
|
|
| |
Allow blower to come on and repeat |
| ||
test to check for intermittent |
| ||
operation. |
| ||
|
|
|
Replace control center.
Check connections. If OK, replace control center.
Check that all gas valves are turned on. Replace valve.
Check for:
•Inadequate flame carryover on rough ignition.
•Low inlet gas pressure.
Repeat call for heat and check flame sensor current during trial for ignition NO period. Is the DC microamps
below 0.5?
YES
Check connections and retry. If current is near typical value and control will not stay on, replace control center.
Clean flame sensor with fine sandpaper and recheck current.
Current is nominally 4.0 to 6.0 microamps.
Is current near typical value? | NO | Replace electrode. |
|
| ||
|
|
|
| |||
|
|
|
|
|
|
|
| YES |
|
|
|
|
|
|
| NO |
|
|
| |
|
|
|
|
| ||
Will main burner ignite and stay on? | Replace control center. |
| ||||
|
|
| ||||
|
|
|
|
|
|
|
| YES |
|
|
|
|
|
|
|
|
|
| A96219 | |
|
|
|
|
| ||
Fixed. |
|
|
| |||
|
|
|
|
|
|
|