Troubleshooting Guide
START
Is red LED status light on?
YES
NO
Is there 115v at L1 and L2? | NO | |||
|
| |||
|
|
|
| |
| YES |
|
| |
|
| NO | ||
|
| |||
Is there 24v at | ||||
|
| |||
|
|
|
| |
| YES |
|
| |
|
|
|
| |
Replace control center. |
|
| ||
|
|
|
| |
|
|
|
|
Is door switch closed?
YES
Is there 115v going to switch?
YES
Replace door switch.
Replace transformer.
NO
NO
Close door switch and go to start.
Is circuit breaker closed? |
| NO | ||
|
|
| ||
|
|
|
|
|
| YES |
|
|
|
|
|
|
|
|
|
| Close circuit breaker and | ||
|
| go back to start. | ||
|
|
|
|
|
|
|
|
|
|
14
Is red LED status light blinking | YES | Check for correct line voltage |
| ||||
rapidly without a pause? |
|
| polarity. If units are twinned, |
| |||
|
|
|
|
| check for proper |
| |
| NO |
|
|
| |||
|
|
| (24v) transformer phasing. |
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Is red LED status light blinking |
|
| Check for previous fault by |
| |||
ON/OFF slowly with a | NO | momentarily shorting the TEST |
| ||||
combination of short and long |
|
| terminal and the C terminal until |
| |||
flashes? |
|
| the LED goes out. LED will flash |
| |||
|
|
|
|
| the status code of any previous |
| |
| YES |
|
|
| |||
|
|
| fault or the code No. 11 (1 short |
| |||
|
|
|
|
|
| ||
|
|
|
|
| and 1 long flash) if no previous |
| |
Determine status code. The |
|
|
| ||||
|
| fault. After the control repeats the |
| ||||
status code is a 2 digit number |
|
|
| ||||
|
| code 3 times, the control will go |
| ||||
with the first digit determined by |
|
|
| ||||
|
| through a brief component test |
| ||||
the number of short flashes and |
|
|
| ||||
|
| sequence. The inducer will start |
| ||||
the second digit by the number of |
|
|
| ||||
|
| and run for the entire component |
| ||||
long flashes. |
|
|
| ||||
|
| test. The HSI, blower motor heat |
| ||||
Once status code is determined, |
|
|
| ||||
|
| speed, and blower motor cool |
| ||||
the control will go through a brief |
|
|
| ||||
|
| speed will run for |
| ||||
component test sequence. The |
|
|
| ||||
|
|
|
|
| |||
inducer will start and run for the |
|
|
|
|
| ||
entire component test. The HSI, |
|
|
|
| NO | ||
blower motor heat speed, and |
|
| Was there a previous fault code | ||||
blower motor cool speed will run |
|
| other than No. 11? |
| |||
for |
|
|
|
|
| ||
|
|
| YES |
| |||
|
|
|
|
|
|
| |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Go to section with status code |
|
|
|
|
| ||
determined. |
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Does control respond to W, Y, or G
YES
Run system through a heating or cooling cycle to check operation. Status codes are erased after 48 hrs or whenever power (115v or 24v) is interrupted.
NO
Check for continuity in wire from circuit breaker to furnace.
Check room thermostat or interconnecting cable.
NO
Is 24 vac present at W, Y, or G terminals on the control?
YES
Replace control if it does not respond to