Goodman Mfg CPG SERIES installation instructions Natural Gas Connection, Proper Piping Practice

Page 11

The rating plate is stamped with the model number, type of gas and gas input rating. Make sure the unit is equipped to operate on the type of gas available. The gas line installation must comply with local codes, or in the absence of local codes, with the latest edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1.

Natural Gas Connection

Natural Gas Capacity of Pipe

in Cubic Feet of Gas Per Hour (CFH)

Length of

 

Nominal Black Pipe Size (inches)

 

 

 

 

 

 

 

 

Pipe in Feet

1/2

 

3/4

1

1 1/4

 

1 1/2

10

132

 

278

520

1050

 

1600

20

92

 

190

350

730

 

1100

30

73

 

152

285

590

 

980

40

63

 

130

245

500

 

760

50

56

 

115

215

440

 

670

60

50

 

105

195

400

 

610

70

46

 

96

180

370

 

560

80

43

 

90

170

350

 

530

90

40

 

84

160

320

 

490

100

38

 

79

150

305

 

460

Pressure = .50 PSIG or less and Pressure Drop of 0.3" W.C. (Based

on 0.60 Specific Gravity Gas)

CFH =

BTUH Furnace Input

Heating Value of Gas (BTU/Cubic Foot)

 

Refer to the Proper Piping Practice drawing for the general layout at the unit. The following rules apply:

1.Use black iron pipe and fittings for the supply piping. The use of a flex connector and/or copper piping is permitted as long as it is in agreement with local codes.

2.Use pipe joint compound on male threads only. Pipe joint compound must be resistant to the action of the fuel used.

3.Use ground joint unions.

4.Install a drip leg to trap dirt and moisture before it can enter the gas valve. The drip leg must be a minimum of three inches long.

5.Use two pipe wrenches when making connection to the gas valve to keep it from turning.

6.Install a manual shut-off valve in a convenient location (within six feet of unit) between the meter and the unit.

7.Tighten all joints securely.

8.The unit must be connected to the building piping by one of the following methods:

Rigid metallic pipe and fittings

Semirigid metallic tubing and metallic fittings (Aluminum alloy tubing must not be used in exterior locations)

Listed gas appliance connectors used in accordance with the terms of their listing that are completely in the same room as the equipment

In the prior two methods above the connector or tubing must be protected from physical and thermal damage. Aluminum alloy tubing and connectors must be coated to protect against external corrosion when in contact with masonry, plaster or insulation or are subject to repeated wettings by liquids (water - not rain water, detergents or sewage).

DOOR

 

PROVIDE CLEARANCE

 

FOR REMOVAL OF

 

ACCESS PANELS

 

MANUAL

 

SHUTOFF VALVE

 

GROUND JOINT

DRIP LEG

UNION

 

PROPER PIPING PRACTICE

NOTE: The unit gas supply entrance is factory sealed with plugs. Keep plugs in place until gas supply is ready to be installed. Once ready, replace the plugs with the supplied grommets and install gas supply line.

GAS PIPING CHECKS

CAUTION

TO PREVENT PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, THE FOLLOWING INSTRUCTIONS MUST BE PERFORMED REGARDING GAS CONNECTIONS AND PRESSURE TESTING:

THE UNIT AND ITS GAS CONNECTIONS MUST BE LEAK TESTED BEFORE PLACING IN OPERATION. BECAUSE OF THE DANGER OF EXPLOSION OR FIRE, NEVER USE A MATCH OR OPEN FLAME TO TEST FOR LEAKS. NEVER EXCEED SPECIFIED PRESSURES FOR TESTING. HIGHER PRESSURE MAY DAMAGE GAS VALVE AND CAUSE OVERFIRING WHICH MAY RESULT IN PREMATURE HEAT EXCHANGE FAILURE.

THIS UNIT AND ITS SHUTOFF VALVE MUST BE DISCONNECTED FROM THE GAS SUPPLY DURING ANY PRESSURE TESTING OF THAT SYSTEM AT TEST PRESSURES IN EXCESS OF 1/2 PSIG (3.48 KPA).

THIS UNIT MUST BE ISOLATED FROM THE GAS SUPPLY SYSTEM BY CLOSING ITS MANUAL SHUTOFF VALVE DURING ANY PRESSURE TESTING OF THE GAS SUPPLY PIPING SYSTEM AT TEST PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG (3.48 KPA).

WARNING

TO AVOID PROPERTY DAMAGE OR PERSONAL INJURY, BE SURE THERE IS NO OPEN FLAME IN THE VICINITY DURING AIR BLEEDING.

There will be air in the gas supply line after testing for leaks on a new installation. Therefore, the air must be bled from the line by loosening the ground joint union until pure gas is expelled. Tighten union and wait for five minutes until all gas has been dissipated in the air. Be certain there is no open flame in the vicinity during air bleeding procedure. The unit is placed in operation by closing the main electrical disconnect switch for the unit.

11

Image 11
Contents Recognize this Symbol AS a Safety Precaution Safety Instructions Replacement PartsGeneral Information High VoltageUnit Location Electrical Entrance Locations Roof TOP Duct Connections Roof Curb POST-INSTALLATION ChecksRoof Curb Installation ClearancesHorizontal Discharge Duct Connections Rigging DetailsCorner & Center of Gravity Locations Electrical WiringPower and LOW Voltage Block Locations CPG 090 Through 300 GAS Heat GAS Supply PipingProper Piping Practice Natural Gas ConnectionTypical Propane GAS Piping Propane GAS InstallationsDrain Connection STARTUP, ADJUSTMENTS, and ChecksCirculating AIR and Filters Venting Condensate Drain ConnectionMoving Machinery Hazard Recommended Pounds of Force PER Belt Drive Belt Tension AdjustmentRollout Protection Control Manifold Pressure Check Burn Hazard Normal Sequence of Operation Heat Exchanger and Burner Orifice SpecificationsCheck rollout limit TroubleshootingInput Rating AIR Flow AdjustmentsMotor Sheave Adjustments WHITE-RODGERS 36H54 Pressure AdjustmentsMaintenance Burner Flame CPG090 Standard Belt Drive Horizontal CPG090 Standard Belt Drive Down Shot CPG090 High Static Belt Drive Down Shot Appendix B Electrical Data Vertical Discharge Bottom of Unit Horizontal Discharge0140L00550 REV a INSTALLER/SERVICEMAN 0140L00552 REV B 208-240/3/60 0140L00553 REV B
Related manuals
Manual 56 pages 48.63 Kb

CPG SERIES specifications

Goodman Manufacturing has long been a trusted name in the HVAC industry, known for delivering reliable and efficient heating and cooling solutions. Among its impressive lineup is the CPG series, a collection of packaged units that cater to a wide range of residential and commercial applications. The CPG series is designed with the latest technologies and features, making it an ideal choice for those seeking comfort and performance.

One of the most significant characteristics of the CPG series is its energy efficiency. Engineered to meet rigorous energy standards, these units utilize advanced refrigerant technologies that not only lower energy consumption but also contribute to reducing environmental impact. The high-efficiency scroll compressor within the CPG series is designed to operate quietly and smoothly, ensuring that homeowners enjoy a comfortable indoor environment without disruptive noise.

The CPG series also stands out with its robust construction. Each unit is crafted from durable materials that can withstand various weather conditions, ensuring longevity and reliability. The all-aluminum evaporator coil enhances corrosion resistance, prolonging the unit's lifespan and maintaining optimal performance throughout its operation.

In terms of features, the CPG series offers an integrated microprocessor control system that optimizes performance based on real-time environmental data. This smart technology allows for accurate temperature control and improved efficiency by adapting to changing conditions. Furthermore, the series provides multiple capacity options, making it flexible for various building sizes and requirements.

Ease of installation and maintenance is another hallmark of the CPG series. These packaged units are designed for quick setup, reducing labor costs and installation time. Additionally, the access panels on the units are strategically placed, facilitating easier maintenance and servicing. This advantage not only enhances user convenience but also ensures that the units operate efficiently for years to come.

Moreover, the CPG series supports various accessories and enhancements, such as advanced filtration systems and programmable thermostats, allowing users to customize their HVAC system based on specific needs and preferences.

In conclusion, the Goodman CPG series embodies a perfect blend of efficiency, durability, and technology. With its focus on energy savings and user-friendly design, it represents a sound investment for those seeking superior HVAC solutions for their homes or commercial spaces. Whether it's for new construction or an upgrade to an existing system, the CPG series offers performance and reliability that customers can depend on.