Heat & Glo LifeStyle HST-42D owner manual Install Outside Air Kit, AK14/AK18 Installation

Page 23

E. Install Outside Air Kit

Keep duct runs short and straight to minimize restriction. A small dip is acceptable for a cold air trap.

The outside air kit must be installed.

Locate the outside air hood in a clear area, preferably into prevailing wind during the heating season. Refer to Figure 5.2.

Install as shown in Figures 7.3, 7.4 and 7.5.

The air duct may be run vertically.

The outside air hood must be at least 3 ft (.91 m) below the top of the uppermost chimney section.

Caution! Risk of Fire or Asphyxiation! Do not draw outside combustion air from wall, floor or ceiling cavity, or enclosed spaces such as an attic or garage.

Do not place outside air hood close to exhaust vents or chimneys. Fumes or odor could be drawn into the room through the fireplace.

Locate outside air inlet to prevent blockage from leaves, snow/ice, or other debris. Blockages could cause combustion air starvation.

AK14/AK18 Installation

The hinge will be toward the front of the fireplace.

Insert the narrow end of the handle into the upper slot.

Pivot the handle in the slot toward the hinge.

Remove the cover plate or knockout from the side of the fireplace and discard. Remove the semi-perforated piece of insulation covering the opening (insulated fireplaces only).

Partly open the air kit door and insert the handle into the appropriate hole in the side column of the fireplace. The hinge on the door assembly should be located toward the front of the fireplace. If the hinge and the handle are not positioned in this manner, the door will not function correctly.

Attach the door assembly to the fireplace using the screws provided.

Check operation by pulling the handle out to open and pushing it in to close.

Mark and cut out a 4 1/2 in. (114 mm) hole in the building side for air entry. This hole should allow some framing (two sides) so the 4 in. (102 mm) diameter inlet tube assembly may be fastened properly.

Assemble flexible duct (not supplied) between the door assembly and the inlet tube assembly. Secure it in position with the supplied wire ties.

 

Flexible Duct

 

 

(not supplied)

 

 

 

Outside Air

Outside Air

 

Plate

 

Assembly

Hood

2 Wire Ties

 

Figure 7.5 Outside Air Installation

 

Heat & Glo • HST-42D • 27177 • Rev AG • 7/12

23

Image 23
Contents Fire Risk Wood Burning FireplaceHot screen/mesh and glass doors will cause burns Number Listing Label Information/LocationGrate User Guide Table of ContentsInstaller Guide Limited Lifetime Warranty Warranty Hearth & Home Technologies IncThis warranty is void if Warranty ConditionsCombustible Materials Listing and Code ApprovalsAppliance Certification Non-Combustible MaterialsHot glass will cause burns Operating InstructionsYour Fireplace Firescreen Seasoned WoodStarting a Fire GrateOptional Components Glass DoorsOutside Air optional Vented Gas Log Sets & Gas Log LightersWood Fuel Creosote Formation and Need for Removal Maintenance and ServiceChimney Inspection/Cleaning Disposal of AshesFrequency As desired Glass CleaningCheck Firebox Refractory Inspect GrateStart Fire Problems Possible Cause Solution Troubleshooting GuideTypical Fireplace System Getting StartedNegative Pressure Design and Installation ConsiderationsDraft Frequently open doors Central heat outlets or returns Locating Fireplace & ChimneyInspect Fireplace and Components Tools and Supplies NeededFireplace System Requirements Select Fireplace Location Framing & ClearancesClearances to Combustible Materials ClearancesFrame the Fireplace Sidewalls/SurroundsPlace Protective Metal Hearth Strips Installation of FireplaceThings to Consider Position the FireplaceFt min. from top of uppermost chimney section to air inlet AK14/AK18 Installation Install Outside Air KitChimney Assembly Height of Chimney Components Chimney RequirementsExample Using Offsets/ReturnsAssemble Chimney Sections Install Chimney Air KitInstalling the Ceiling Firestop Install Ceiling FirestopsPrepare Attic Insulation Shield Install Attic Insulation ShieldCut out Hole in Roof Complete InstallationInstall Flashing Following steps should be skipped if using a chaseFlat Roofs Chimney Termination RequirementsConstruct the Chase Chase InstallationsInstall Chase Top Install Fireplace & ChimneyST375 Square Termination Cap Install Termination CapTS345/TS345P Square Termination Cap Open Top Shroud TR342 caps require radiation shield ShroudsRadiation Shield Field Constructed ShroudsRoofed Style Shroud radiation shield required Mailbox Style Shroud radiation shield required= 1/k x inches of thickness FinishingHearth Extension Non-combustible Facing Finishing MaterialMantel Combustible MantelMm squares 4 in mm Gas Code, Ansi Z223.1 AccessoriesGas Log/Lighter Provision Wood Burning InsertsReference Materials Fireplace DimensionsCatalog# Chimney Components14-1/2 10-7/8 276 mm Stocked Service PartsAt Depot 1415 StockedDo not Discard this Manual