Heat & Glo LifeStyle HST-42D Accessories, Gas Log/Lighter Provision, Wood Burning Inserts

Page 42

12 Accessories

A. Gas Log/Lighter Provision

Warning! Fire and/or Asphyxiation Risk! Use with solid wood fuel or decorative gas appliance only. Gas fire generates fumes.

DO NOT install unvented gas logs

Damper must be locked fully open when gas logs are installed

A certified gas log lighter or decorative gas log set can be installed in this fireplace.

Maximum input is 100,000 BTU/hr.

Decorative gas appliance must be certified to ANSI Z21.60 “Standard for Decorative Gas Appliances for Installation in Vented Fireplaces”.

Must be installed in accordance with the National Fuel

Gas Code, ANSI Z223.1.

A gas log set must incorporate a gas shutoff.

Gas Log set requires the damper to be locked fully open.

A listed automatic damper system with safety interlock may be used in this fireplace with only compatible, listed gas log sets. See damper system manufacturer’s insturctions.

Knockouts are provided on both sides of the fireplace and in refractories for 1/2 in. (13 mm) iron pipe.

Seal refractory around pipe with fireplace mortar or a non-combustible sealant.

B. Wood Burning Inserts

Warning! Risk of Fire! Improper installation of wood in- serts may cause fireplace or chimney system to overheat.

If a wood burning insert is being installed in this fireplace, Hearth & Home Technologies recommends full reline of the chimney.

Cooling air openings at the top of the chimney must not be obstructed in any manner.

Hearth & Home Technologies recommends securing the reline at the top of the flue and using the cap certified for use with this fireplace system.

Firebox

Refractory

Seal with fireplace mortar or non-combust- ible sealant

Outer shell of fireplace

Maintain air clearance to combustibles.

Combustible materials

Gas line

Repack insulation knockout

Gas line

4 in. (102 mm)

1 1/2 in. (38 mm) air space around

pipe

Combustible materials may be located at zero clearance to gas line beyond 4 in. (102 mm) from fireplace side.

Figure 12.1 Gas Line Installation

42

Heat & Glo • HST-42D • 27177 • Rev AG • 7/12

Image 42
Contents Wood Burning Fireplace Hot screen/mesh and glass doors will cause burnsFire Risk Listing Label Information/Location GrateNumber Table of Contents Installer GuideUser Guide Warranty Hearth & Home Technologies Inc Limited Lifetime WarrantyWarranty Conditions This warranty is void ifNon-Combustible Materials Listing and Code ApprovalsAppliance Certification Combustible MaterialsOperating Instructions Your FireplaceHot glass will cause burns Grate Seasoned WoodStarting a Fire FirescreenVented Gas Log Sets & Gas Log Lighters Glass DoorsOutside Air optional Optional ComponentsWood Fuel Disposal of Ashes Maintenance and ServiceChimney Inspection/Cleaning Creosote Formation and Need for RemovalInspect Grate Glass CleaningCheck Firebox Refractory Frequency As desiredTroubleshooting Guide Start Fire Problems Possible Cause SolutionGetting Started Typical Fireplace SystemDesign and Installation Considerations DraftNegative Pressure Locating Fireplace & Chimney Frequently open doors Central heat outlets or returnsTools and Supplies Needed Fireplace System RequirementsInspect Fireplace and Components Framing & Clearances Select Fireplace LocationClearances Clearances to Combustible MaterialsSidewalls/Surrounds Frame the FireplacePosition the Fireplace Installation of FireplaceThings to Consider Place Protective Metal Hearth StripsFt min. from top of uppermost chimney section to air inlet Install Outside Air Kit AK14/AK18 InstallationChimney Assembly Chimney Requirements Height of Chimney ComponentsUsing Offsets/Returns ExampleInstall Chimney Air Kit Assemble Chimney SectionsInstall Ceiling Firestops Installing the Ceiling FirestopInstall Attic Insulation Shield Prepare Attic Insulation ShieldFollowing steps should be skipped if using a chase Complete InstallationInstall Flashing Cut out Hole in RoofChimney Termination Requirements Flat RoofsChase Installations Construct the ChaseInstall Fireplace & Chimney Install Chase TopInstall Termination Cap ST375 Square Termination CapTS345/TS345P Square Termination Cap Field Constructed Shrouds ShroudsRadiation Shield Open Top Shroud TR342 caps require radiation shieldMailbox Style Shroud radiation shield required Roofed Style Shroud radiation shield requiredFinishing Hearth Extension= 1/k x inches of thickness Finishing Material Non-combustible FacingCombustible Mantel MantelMm squares 4 in mm Wood Burning Inserts AccessoriesGas Log/Lighter Provision Gas Code, Ansi Z223.1Fireplace Dimensions Reference MaterialsChimney Components Catalog#14-1/2 10-7/8 276 mm Service Parts At DepotStocked Stocked 1415Do not Discard this Manual