Heat & Glo LifeStyle 6000GL-IPI-R Vent Information and Diagrams, Approved Pipe, Vent Table Key

Page 23

7 Vent Information and Diagrams

A. Approved Pipe

This appliance is approved for use with Hearth & Home Technologies DVP or SLP venting systems. Refer to Sec- tion 16.B for vent component information.

DO NOT mix pipe, fittings or joining methods from differ- ent manufacturers.

The pipe is tested to be run inside an enclosed wall. There is no requirement for inspection openings at each joint within the wall.

WARNING! Risk of Fire or Asphyxiation. This appli- ance requires a separate vent. DO NOT vent to a pipe serving a separate solid fuel burning appliance.

B. Vent Table Key

The abbreviations listed in this vent table key are used in the vent diagrams.

Symbol

Description

 

 

V1

First section (closest to appliance) of vertical length

 

 

V2

Second section of vertical length

 

 

H1

First section (closest to appliance) of horizontal length

 

 

H2

Subsequent sections of horizontal length

 

 

C. Use of Elbows

Diagonal runs have both vertical and horizontal vent as- pects when calculating the effects. Use the rise for the vertical aspect and the run for the horizontal aspect (see Figure 7.1).

Two 45º elbows may be used in place of one 90º elbow. On 45º runs, one foot of diagonal is equal to 8-1/2 in. (216

mm)horizontal run and 8-1/2 in. (216 mm) vertical run. A length of straight pipe is allowed between two 45º elbows (see Figure 7.1).

Vertical in.1/2 -8

8-1/2 in.

Horizontal

Figure 7.1

D. Measuring Standards

Vertical and horizontal measurements listed in the vent diagrams were made using the following standards.

Pipe measurements are shown using the effective length of pipe (see Figure 7.2).

Horizontal terminations are measured to the outside mounting surface (flange of termination cap) (see Figure 6.3).

Vertical terminations are measured to bottom of termination cap.

Horizontal pipe installed level with no rise.

 

Pipe

Effective Length

 

Inches

Millimeters

 

 

 

DVP4

4

102

 

DVP6

6

152

Effective

DVP12

12

305

Height/Length

DVP24

24

610

 

 

DVP36

36

914

 

DVP48

48

1219

 

DVP6A

3 to 6

76 to 152

 

DVP12A

3 to 12

76 to 305

 

DVP12MI

3 to 12

76 to 305

 

DVP24MI

3 to 24

76 to 610

Figure 7.2 DVP Pipe Effective Length

 

 

Heat & Glo • 6000GL-IPI-R, 6000GL-IPI-S2102-900 Rev. R • 6/09

23

Image 23
Contents Hot glass will cause burns What to do if you smell gasHOT Surfaces Xxxxxxxx CongratulationsHomeowner Reference Information User Guide Table of ContentsReference Materials Appliance SetupTroubleshooting FinishingLimited Lifetime Warranty Limited Lifetime Warranty Listing and Code Approvals Requirements for the Commonwealth of Massachusetts Installation of Carbon Monoxide DetectorsYour Fireplace Gas Fireplace SafetyOperating Instructions User Guide Clear Space Fixed Glass AssemblyRemote Controls, Wall Controls and Wall Switches Fan Kit optionalGAS Valve Lighting Instructions IPIFinal inspection by What to do if YOU Smell GASAfter Fireplace is Lit Frequently Asked QuestionsIssue Solutions Remote Control Maintenance and ServiceMaintenance Tasks-Homeowner Glass CleaningLogs Maintenance Tasks-Qualified Service TechnicianGasket Seal and Glass Assembly Inspection VentingIPI Pilot Flame Patterns Typical Appliance System Getting StartedAny such action may cause a fire hazard Design and Installation ConsiderationsTools and Supplies Needed Inspect Appliance and ComponentsSelecting Appliance Location Framing and ClearancesClearances Constructing the Appliance ChaseCombustible Mantel Legs or Wall Projections Mantel and Wall ProjectionsCombustible Mantels Vent Termination Minimum Clearances Termination Locations= Vent Terminal = AIR Supply Inlet = Area Where Terminal is not PermittedUse of Elbows Vent Information and DiagramsApproved Pipe Vent Table KeyV1 Minimum H1 Maximum Vent Diagrams Top Vent Horizontal TerminationOne Elbow Two ElbowsMin Max Top Vent Horizontal Termination Three ElbowsBreak Here Maximum + V 2 Min Top Vent Vertical TerminationH1 + H2 V1 + V2 Minimum H1 + H2 Maximum Top Vent Vertical Termination Three ElbowsHeat & Glo 6000GL-IPI-R, 6000GL-IPI-S 2102-900 Rev. R 6/09 H1 Maximum V1 Minimum H2+ H3 H1+ H2+ H3 Max Rear Vent Horizontal Termination Two ElbowsH1 Maximum V1 Minimum H1 + H2 Maximum H1 + H2 Maximum V1 Minimum Rear Vent Vertical Termination One ElbowV1 Minimum H1 + H2 + H3 Rear Vent Vertical Termination Three ElbowsCombustible Wall Penetration Vent Clearances and FramingPipe Clearances to Combustibles Wall Penetration FramingPipe DVP SLP Install the Ceiling FirestopVaulted Ceiling Installation Install Attic Insulation ShieldInstalling the Optional Heat-Zone-Gas Kit Flat Ceiling InstallationTop Vent Appliance PreparationCut the metal retaining band and fold the sides out Rear VentHeader Installing the Non-combustible BoardSecuring and Leveling the Appliance Assemble Pipe Sections Installing Vent Pipe DVP and SLP PipeAttach Vent to the Firebox Assembly Assemble Vent Sections DVP Pipe OnlyAssemble Slip Sections Assemble Vent Sections SLP Pipe OnlyDisassemble Vent Sections Secure the Vent SectionsInstall Decorative Ceiling Components SLP only Assemble and Install Storm Collar Install Metal Roof FlashingHeat Shield Requirements for Horizontal Termination Install Vertical Termination CapInstall Decorative Wall Components SLP only Refer to of this manual Install Horizontal Termination Cap DVP and SLP PipeAnsi Z223.1 and CAN/CGA-B149 installation codes Gas Connection Gas InformationFuel Conversion Gas PressureElectrical Information Wiring RequirementsIntelliFire Ignition System Wiring Optional Accessories RequirementsIntelliFire Pilot Ignition IPI Wiring Diagram Electrical Service and RepairWall Switch Installation for Fan Optional Junction Box InstallationFacing Material FinishingFinish Door FIT Material See Maximum Thickness DoorsAppliance Setup Ember Material Ember PlacementInstall the Log Assembly Log Assembly LOGS-6000GL10 Front View Air Shutter Settings Install the MeshInstall Trim and/or Surround Air Shutter SettingIntelliFire Ignition System TroubleshootingSymptom Possible Cause Corrective Action Ues to spark, and main Location Inches Millimeters Appliance Dimension DiagramReference Materials DVP vent components Vent Components DiagramsHorizontal Termination Cap DVP-TRAPCOOL-ADD RF6M RF12MBEK DVP-BEK2 DVP-TRAPFLDVP-TVHW DVP-HRC-SS DVP-HRC-ZC-SS Horizontal Termination CAP 251 mm 165 mm165 mm 222 mm 235 mm 152 mm 168 mm ElbowSLP-DCF-BK SLP-WT-BK SLP-SNKD SLP-CCS-BK SLP-TVHWDVP-2SL DVP-HSM-B Contact Information

6000GL-IPILP-R, 6000GL-IPI-R, 6000GL-IPILP-S, 6000GL-IPI-S specifications

The Heat & Glo LifeStyle 6000 series, including models 6000GL-IPI-S, 6000GL-IPILP-R, 6000GL-IPI-R, and 6000GL-IPILP-S, epitomizes modern innovation in the realm of gas fireplaces. These units are designed to create a captivating focal point in any living space while being both functional and aesthetically pleasing.

One of the key features of the LifeStyle 6000 series is its versatility in configurations. These models offer multiple options for installation, whether you prefer a linear or traditional look. The linear fireplace design provides a contemporary touch, making these units suitable for both modern and traditional homes. The ability to customize the dimensions and installation style allows homeowners and designers to create a cohesive look that fits their interior vision.

Energy efficiency is another hallmark of the LifeStyle 6000 series. All models are equipped with advanced direct vent technology, which ensures optimal combustion and heating. The direct vent system draws air from outside for combustion while expelling exhaust, thus maintaining indoor air quality. This feature not only provides peace of mind regarding safety but also helps reduce energy consumption.

The LifeStyle 6000 series includes impressive heating capabilities, with outputs designed to warm spaces comfortably without excessive energy use. The adjustable flame height control allows users to customize the ambiance, whether seeking a soothing glow or a robust fire.

Technologically, these models stand out with their IntelliFireā„¢ ignition system. This innovative technology enhances the ease of use, providing a simple way to start and control the flames. The smart control systems often come with remote access options, enabling users to manage their fireplace with ease from the comfort of their seat.

Another defining characteristic of the LifeStyle 6000 series is its aesthetic appeal. Each model features a range of media options, including contemporary glass crystals and traditional logs, allowing users to personalize the look of their fireplace. The elegant LED lighting enhances the ambiance, creating a warm and inviting atmosphere for any occasion.

In summary, the Heat & Glo LifeStyle 6000 series, encompassing models 6000GL-IPI-S, 6000GL-IPILP-R, 6000GL-IPI-R, and 6000GL-IPILP-S, combines cutting-edge technology with stylish design. With versatile installation options, exceptional energy efficiency, intuitive controls, and customizable aesthetics, this series is a perfect choice for homeowners seeking a sophisticated and efficient heating solution.