White Rodgers 1F95-0680 specifications Applications, Specifications

Page 1

Save these instructions for future use!

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATINGTHIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.

Blue Commercial Thermostat with Automatic Heat/Cool Changeover Option and Damper Control

Single Stage, Multi-Stage, Heat Pump

Installation and Operating Instructions for Model:

Model

 

Programming Choices

 

 

 

1F95-0680

7 Day

5/1/1 Day

Non-Programmable

 

 

 

 

APPLICATIONS

THERMOSTAT APPLICATION GUIDE

 

 

 

1F95-0680 Commercial Thermostat

Description

 

 

 

 

 

 

 

Heat Pump (No Aux. or Emergency Heat)

Yes

 

 

 

 

 

Heat Pump (with Aux. or Emergency Heat)

Yes

 

 

 

 

 

Systems with up to 4 Stages Heat, 2 Stages Cool

Yes

 

 

 

 

 

Heat Only Systems

Yes

 

 

 

 

 

Millivolt Heat Only Systems – Floor or Wall Furnaces

Yes

 

 

 

 

 

Cool Only Systems

Yes

 

 

 

 

 

Gas or Oil Heat

Yes

 

 

 

 

 

Electric Furnace

Yes

 

 

 

 

 

Hydronic (Hot Water) Zone Heat – 2 Wires

Yes

 

 

 

 

 

Hydronic (Hot Water) Zone Heat – 3 Wires

Yes

 

 

 

 

 

Wired Remote Temperature Sensor (Indoor or Outdoor)

Yes

 

 

 

 

 

Dual Fuel Damper Control Feature (Heat Pump Mode

Yes

 

Outdoor Remote Required)

 

 

SPECIFICATIONS

 

 

 

 

 

 

Electrical Rating:

Battery Power . . . . . . . . . . . . . . . . . . . . . . . . . . mV to 30 VAC, NEC Class II, 50/60 Hz or DC Input-Hardwire . . . . . . . . . . . . . . . . . . . . . . . . . 20 to 30 VAC

Terminal Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.5A per terminal, 2.5A maximum all terminals combined Setpoint Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 to 99°F (7 to 32°C)

Differential (Single Stage) . . . . . . . . . . . . . . . . . . . . Heat 0.6°F; Cool 1.2°F Differential (Multi-Stage) . . . . . . . . . . . . . . . . . . . . . Heat 0.6°F; Cool 1.2°F Differential (Heat Pump) . . . . . . . . . . . . . . . . . . . . . Heat 1.2°F; Cool 1.5°F Operating Ambient. . . . . . . . . . . . . . . . . . . . . . . . . . 32°F to +105°F (0 to +41°C) Operating Humidity . . . . . . . . . . . . . . . . . . . . . . . . . 90% non-condensing max. Shipping Temperature Range . . . . . . . . . . . . . . . . . -40 to +150°F (-40 to +65°C) Dimensions Thermostat. . . . . . . . . . . . . . . . . . . . . . 4.2"H x 6.4"W x 1.7"D

!CAUTION

To prevent electrical shock and/or equipment damage, disconnect electric power to system at main fuse or circuit breaker box until installation is complete.

Index

Page

Installation

2

Wiring Connections

2

Wiring Diagrams

3

Thermostat Quick Reference

4

Installer Confi guration Menu

5

Operating Your Thermostat

8

Programming

9

Troubleshooting

13

ATTENTION: MERCURY NOTICE

This product does not contain mercury. However, this prod- uct may replace a product that contains mercury.

Mercury and products containing mercury must not be discarded in household trash. Do not touch any spilled mercury. Wearing non-absorbent gloves, clean up any spilled mercury and place in a sealed container. For proper disposal of a product containing mercury or a sealed container of spilled mercury, place it in a suitable shipping container. Refer to www.white-rodgers.comfor location to send product containing mercury.

PART NO. 37-6819A

www.white-rodgers.com

0811

Image 1
Contents Applications SpecificationsSave these instructions for future use Wiring Connections InstallationHeat Pump Systems Wiring DiagramsHome Screen Description Thermostat Quick ReferenceProgramming and Configuration Items Menu INSTALLER/CONFIGURATION MenuValid Code Press Menu after selecting the type of lockout Check Thermostat Operation Operating Your ThermostatFan Operation Heating SystemProgramming Planning Your Program Important Energy Saving Factory Pre-ProgramWorksheet for Re-Programming 5+1+1 and 7 Day Program Programming Tip Copy Program Automatic Daylight Saving CalculationEnter the Heating Program Enter the Cooling ProgramDual Fuel Temperature Setpoint Wired Remote Temperature SensingWeighing of Remote Reading Blower Balance PointReset Operation TroubleshootingSymptom Possible Cause Corrective Action Page Page St. Louis, Missouri Markham, Ontario Homeowner Help Line