UNVENTED NATURAL GAS LOG HEATER
INSTALLATION
Continued
INSTALLING DAMPER CLAMP ACCESSORY FOR VENTED OPERATION
Note: When used as a vented heater, appli- ance must be installed only in a
You may use this heater as a vented product. There are three reasons for operating your heater in the vented mode:
1.The fireplace does not meet the clear- ance to combustibles requirements for
2.State or local codes do not permit vent- free operation
3.You prefer vented operation
If reasons number 1 or 2 above apply to you, you must permanently open chimney flue damper. You must install the damper clamp accessory (to order, see Accessories, page 21). This will insure vented operation (see Figure 10). The damper clamp will keep damper open. Installation instructions are included with clamp accessory.
See chart below for minimum permanent flue opening you must provide. Attach damper clamp so the minimum permanent flue opening will be maintained at all times.
Chimney | Minimum Permanent |
Height (ft.) | Flue Opening (sq. ins.) |
|
|
6' to 15' | 39 sq. inches |
15' to 30' | 29 sq. inches |
|
|
Area of Various Standard
Round Flues
Diameter (ins.) | Area (sq. ins.) |
|
|
5" | 20 sq. inches |
6" | 29 sq. inches |
7" | 39 sq. inches |
8" | 51 sq. inches |
|
|
INSTALLING HEATER BASE ASSEMBLY
WARNING: You must secure this heater to fireplace floor. If not, heater will move when you adjust controls. Moving heater may cause a gas leak.
WARNING: If installing in a sunken fireplace, special care is needed. You must raise the fire- place floor to allow access to heater control panel. This will in- sure adequate air flow and guard against sooting. Raise fireplace floor with noncombustible mate- rial. Make sure material is secure.
CAUTION: Do not pick up heater base assembly by the burner. This could damage heater. Only handle base assem- bly by grates.
CAUTION: Do not remove the data plates attached to the heater base assembly. The data plates contain important warranty and safety information.
Damper
Clamp
Damper
Damper
Clamp
Damper
Damper
Masonry Fireplace | Manufactured Fireplace |
Figure 10 - Attaching Damper Clamp
IMPORTANT: Make sure the heater burner is level. If heater is not level, heater will not work properly.