AIR FOR COMBUSTION AND VENTILATION Providing Adequate Ventilation (Cont.)

Determining Fresh-Air Flow for Appliance Location Ventilation Air

5

AIR FOR COMBUSTION AND VENTILATION

Continued

Confined and Unconfined Space

The National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appli- ances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconfined space.

*Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.

DETERMINING FRESH-AIR FLOW FOR APPLIANCE LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install appliance plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height). Length x Width x Height = ____________cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or open- ings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

____________(volume of space) x 20 = (Maximum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) x 20 = 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free appliance

 

_____________ Btu/Hr

Gas water appliance*

 

_____________ Btu/Hr

Gas furnace

 

_____________ Btu/Hr

Vented gas appliance

 

_____________ Btu/Hr

Gas fireplace logs

 

_____________ Btu/Hr

Other gas appliances* +

_____________ Btu/Hr

Total

=

_____________ Btu/Hr

*Do not include direct-vent gas appliances. Direct-vent draws com- bustion air from the outdoors and vents to the outdoors.

Example:

 

40,000

Gas water appliance

 

 

_____________ Btu/Hr

Vent-free appliance

+

33,000

_____________ Btu/Hr

Total

=

73,000

_____________ Btu/Hr

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

____________________Btu/Hr (maximum the space can support)

____________________Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support) 73,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C.Install a lower Btu/Hr appliance, if lower Btu/Hr size makes room uncon- fined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can sup- port, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the appliance may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 Section 5.3 or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceil- ing and one within 12" of the floor. Connect these items directly to

For more information, visit www.desatech.com

111826-02F

Image 5
Contents Ansi Z21.60-2003 CSA What to do if YOU Smell GASSafety Information Table of ContentsProduct Identification Local CodesProduct Features Optional Remote Control AccessoriesUnpacking AIR for Combustion and VentilationVentilation AIR Determining FRESH-AIR Flow for Appliance LocationVentilation Air from Outdoors Installation Installation Items Needed Installing Appliance AssemblyConnecting to GAS Supply Checking GAS Connections Pressure Testing gas Supply Piping systemValve Pressure Testing Appliance Gas ConnectionsLighting Instructions For Your Safety Read Before LightingOperating Appliance To Turn OFF GAS to Appliance Manual Lighting ProcedureRemote Control Operation Operating Appliance Inspecting Burner Cleaning and MaintenancePilot Flame Pattern Burner Flame PatternObserved Problem Possible Cause Remedy TroubleshootingRefer to Air for Combustion and Venti Observed Problem Possible Cause VTD-18N-PDG/VTD-18N-BTB SpecificationsReplacement Parts Wiring DiagramService Hints Technical ServiceThis page Intentionally Left Blank Illustrated Parts Breakdown Illustrated Parts BreakdownParts List Accessories Owners Registration Form Postage Required 111826-02F Warranty Information

VTD-24P-BTB, VTD-18P-BTB, VTD-24P-PDG, VTD-18N-BTB, VTD-18N-PDG specifications

Desa VTD-18N-BTB, VTD-18P-BTB, VTD-24P-PDG, VTD-24P-BTB, and VTD-18N-PDG are notable offerings in the realm of heaters, designed to provide efficient and effective heating solutions for various environments. Each model boasts a range of features and technologies that cater to different needs and preferences, promoting comfort and convenience.

Starting with the VTD-18N-BTB and VTD-18P-BTB, these models are engineered with a focus on reliability and performance. They come equipped with advanced heating technology that ensures rapid warmth distribution in residential or commercial spaces. Featuring adjustable heat settings, users can customize the temperature according to their comfort levels. The BTB designation indicates that these models possess a robust build quality, designed to withstand heavy use, while maintaining aesthetic appeal.

The VTD-24P-PDG and VTD-24P-BTB are designed for larger areas, delivering an increased heat output to accommodate more substantial spaces. These models incorporate energy-efficient technology, which aids in reducing overall energy consumption while providing consistent heat. Moreover, the programmable thermostat feature available in these units allows users to set specific heating schedules, significantly enhancing energy efficiency and convenience.

The VTD-18N-PDG stands out with its unique design and advanced features. This model combines a sleek and modern aesthetic with high functionality, making it suitable for contemporary interiors. It utilizes a dual-fuel technology option, providing the flexibility to operate on either gas or electric power, thus enhancing versatility in use. This feature is particularly beneficial for areas with fluctuating energy availability.

In terms of safety, all models incorporate essential safety mechanisms, including overheating protection and tip-over switches, ensuring peace of mind for users. The combination of portability and performance allows for seamless placement in various settings, from home living rooms to workshops and garages.

Overall, Desa's VTD series reflects a commitment to quality and innovation, promoting efficient heating solutions that cater to varying space and user requirements. These models are ideal for users seeking dependable heating options without compromising on style, functionality, or safety.