UNVENTED (VENT-FREE) LOGMATE® FIREBOX
INSTALLATION
Continued
Mantel Clearances for Projected Built-In Installation
Wall board or facing material (above firebox) may be of combustible material, including decorative mantel ornaments or other similar projections off of the facing material.
If placing custom mantel above
CAUTION: Do not allow the
Note: Fireplace
shown as cross- 7" Min. section for clarity. Mantel material
Top Frame (Combustible Material)
Firebox Top
Mantel Shelf
9 1/4"
6" |
|
|
| |
3" |
|
|
| |
Combustible |
|
|
| |
Material 1 1/2" | 12" | 15" | 18" | |
Max Thickness | ||||
|
|
|
screen.
If your installation does not meet the mini- mum clearances shown in Figure 7, you must:
•raise the mantel to an acceptable height,
OR
•remove the mantel.
BUILT-IN OR INTERNAL WALL FIREBOX INSTALLATION
may not be less than 7" from top of hood. Do not cover louver openings.
| Note: All vertical |
measurements are | |
Screen | minimum distances |
Supplied Firebox | from top of fireplace |
Hoods Must Be | hood to bottom of mantel |
Used at All Times | shelf. These minimum |
| clearances replace any |
| other recommended |
| clearances supplied with |
| your ANS Z21.11.2 |
| approved gas logs. |
1.Frame in rough opening. The firebox framing should be constructed of 2 x 4 lumber or heavier. Construct framing using dimensions shown in Figure 8 and Figure 9, page 9. It is recommended that the framing be constructed first and the unit be placed in position. After sliding the unit into place, the flanges may be nailed to the framing before applying the wallboard to the exterior framing.
2.If the
Figure 7 - Minimum Mantel Clearances for Projected or Built-In Installation
22 3/4" Min.
Wallboard
Gas Line
Facing | 4" Min. |
| |
Wall |
|
40 1/4" Min.
36" Min. to
Board
Facing Wall
Base
Facing Wall | 43 3/4" Min. |
(Base line) |
|
Figure 8 - Framing for Built-In or Internal Wall Firebox Installation
8 | 105163 |
|