STEP 5: Before securing fireplace to prepared framing, the ember protector (provided), must be placed between the hearth extension (not supplied), and under the bottom front edge of the fireplace to protect against glowing embers falling through. If the fireplace is to be installed on a raised platform,
a
STEP 6: Using screws or nails, secure the fireplace to the framing through flanges located on the sides of the fireplace (see figure 4).
Figure 1 | FRAMING DIMENSION |
Figure 2 CORNER INSTALLATIONS
HEARTH EXTENSION:
A hearth extension projecting a minimum of 16” in front of and a minimum of 8” beyond each side of the fireplace opening is required to protect combustible floor construction in front of the fireplace. Fabricate a hearth extension using a material which meets the following specifications: a layer of
extension from shifting and seal the gap between the fireplace frame and hearth extension with a
MODELS36WSAND 36WIS | MODELS36WL AND 36WIL |
STANDARD HEARTH | STANDARD HEARTH |
Figure 3 HEARTH EXTENSIONS
WARNING: HEARTH EXTENSION IS TO BE INSTALLED ONLY AS ILLUSTRATED.
Figure 4 |
OPTIONAL OUTSIDE AIR KIT (MODEL AK4 / AK4F) The installation of an outside air kit should be installed during the rough framing of the fireplace due to the nature of its location. Outside combustion air can be accessed through a vented crawl space (AK4F) or through a sidewall (AK4). See accessories on page 10 for details.
Figure 5 |