FLASHING INSTALLATION:
DO NOT NAIL THROUGH FLASHING CONE.
Figure 14 |
INSTALLING FLASHING ON A METAL ROOF:
When installing the flashing on a metal roof it is required that putty tape be used between the flashing and the roof. The flashing must be secured to the roof using #8 x ¾” screws and then sealed with roof coating to prevent leakage through the screw holes. A roof coating must also be applied around the perimeter of the flashing to provide a proper seal.
STORM COLLAR INSTALLATION: (SC1 or SC2)
Place storm collar over pipe and slide down until it is snug against the open edge of the flashing (see figure 15). Use SC1 for all round terminations and SC2 for all terminations with slip sections.
Figure 15 |
TERMINATIONS / SPARK ARRESTOR:
The fireplace system must be terminated with the listed round top or chase terminations. In any case, refer to the installation instructions supplied with the termination. The terminations approved for this fireplace are the
that can be used for flashing or chase and
Figure 16 |
CAUTION: Do not seal openings on the rooftop flashing. Follow the installation instructions provided with the termination being used.
Terminations with 16” slip pipe sections are available. The
NOTE: In the rare instance there is a problem with side driven rain or wind or the chimney is not drafting properly, an ADS- 8DM Anti Draft Shield can be used with round terminations.
CHASE INSTALLATIONS:
Instructions for chase installations are included with the chase style termination chosen. In a multiple chase installation, be sure to provide adequate distance between terminations to prevent smoke spillage from one termination to another. We suggest that terminations be separated at least 24 inches, center to center and stacked at vertical height difference of 18 inches (see figure 17).
Figure 17
6 | For more information, visit www.desatech.com |