Desa VCGF30NR installation manual Installations, Mantel Clearances for BUILT-IN Installation

Page 10

®

UNVENTED NATURAL GAS FIREPLACE

INSTALLATIONS

Continued

MANTEL CLEARANCES FOR BUILT-IN INSTALLATION

If placing mantel above built-in fireplace, you must meet minimum clearance between mantel shelf and top of fireplace opening.

If your installation does not meet the below minimum clearances, you must:

raise the mantel to an acceptable height,

OR

remove the mantel.

Note:

Mantel Shelf

All Vertical

10"

 

 

 

measurements

 

 

 

are from top of

8"

 

 

 

 

 

 

fireplace

6"

 

 

 

 

 

 

opening to

2 1/2"

 

 

 

 

 

 

bottom of

 

 

 

 

 

 

 

mantel shelf.

 

 

 

 

Minimum Non-

 

 

 

 

Combustible

 

 

 

 

Material

13"

16"

19"

21"

 

 

 

 

 

 

Supplied Firebox

Hood Must Be

Used at All Times

Figure 16 - Minimum Mantel Clearances for Built-In Installation

INSTALLING GAS PIPING TO FIREPLACE LOCATION

WARNING: This appliance re- quires a 1/2" NPT (National Pipe Thread) inlet connection to the pressure regulator.

WARNING: A qualified ser- vice person must connect fire- place to gas supply. Follow all local codes.

Installation Items Needed

Before installing fireplace, make sure you have the items listed below.

piping (check local codes)

sealant (resistant to LP/propane gas)

equipment shutoff valve *

test gauge connection *

sediment trap

tee joint

pipe wrench

*An CSA/AGA design-certified equipment shutoff valve with 1/8" NPT tap is an accept- able alternative to test gauge connection. Purchase the optional CSA/AGA design- certified equipment shutoff valve from your dealer. See Accessories, pages 22 and 23.

WARNING: Never connect fireplace to private (non-utility) gas wells. This gas is commonly known as wellhead gas.

CAUTION: Use only new, black iron or steel pipe. Inter- nally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2" diameter or greater to allow proper gas volume to fireplace. If pipe is too small, undue loss of pressure will occur.

Installation must include an equipment shutoff valve, and a plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from fireplace (see Figure 17).

IMPORTANT: Install equipment shutoff valve in an accessible location. The equip- ment shutoff valve is for turning on or shutting off the gas to the appliance.

Check your building codes for any special requirements for locating equipment shutoff valve to fireplaces.

Apply pipe joint sealant lightly to male pipe threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged fireplace valves. Never use thread sealant on flare threads.

CAUTION: Use pipe joint seal- ant that is resistant to liquid pe- troleum (LP) gas.

We recommend that you install sediment trap in supply line as shown in Figure 17. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and fireplace. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps mois- ture and contaminants. This keeps them from going into fireplace gas controls. If sediment trap is not installed or is installed wrong, fireplace may not run properly.

CSA/AGA Design-

Certified Equipment

Shutoff Valve With

1/8" NPT Tap*

Approved

 

Flexible Gas

 

Line

From Gas

 

 

Meter

 

(5" W.C. to

3" Minimum

10.5" W.C.

Pressure)

 

Pipe Nipple Cap Tee Joint

Sediment Trap

Figure 17 - Gas Connection

*Purchase the optional CSA/AGA design- certified equipment shutoff valve from your dealer. See Accessories, pages 22 and 23

10

104636

Image 10
Contents OWNER’S Operation and Installation Manual What to do if YOU Smell GASSafety Information Unvented Natural GAS FireplaceLocal Codes Remote Control AccessoriesProduct Identification UnpackingProduct Features AIR for Combustion and VentilationDetermining FRESH-AIR Flow for Fireplace Location AIR for Combustion VentilationDetermining if You Have a Confined or Unconfined Space Building Ventilation AIRVentilation Air From Inside Ventilation Air From OutdoorsCheck GAS Type InstallationInstalling Deflector and Hood Electrical HookupInstallation Clearances Conventional Fireplace InstallationBUILT-IN Fireplace Installation Location of Nailing FlangesInstalling GAS Piping to Fireplace Location InstallationsMantel Clearances for BUILT-IN Installation Installation Items NeededConnecting Fireplace to GAS Supply Attaching Flexible Gas Lines TogetherPressure Testing Fireplace Gas Connections Pressure Testing Gas Supply Piping SystemChecking GAS Connections Installing Logs Will create sootOperating Fireplace For Your Safety Read Before LightingLighting Instructions To Turn OFF GAS To Appliance Manual Lighting ProcedureOptional Remote Operation Pilot Flame Pattern Inspecting BurnersOptional Blower Operation Burner Primary AIR HolesTroubleshooting Observed Problem Possible CauseObserved Problem Possible Cause Remedy Gas leak. See Warning statement Service Hints Wiring Diagram Replacement PartsSpecifications Technical ServiceLogs Cleaning and MaintenanceCleaning Burner Injector Holder and Pilot AIR Inlet Hole Front Window GlassAccessories Receiver and HAND-HELD Remote Control KIT Ghrc Series Brass Trim Accessory GA6090Cleaning KIT CCK WALL-MOUNT Thermostat Switch GWMT1Illustrated Parts Breakdown Remote Ready Catalytic Model VCGF30NRParts List KEY Part Number Description QTYFireplace VCGF30NR Parts List Warranty Information