CHECKING GAS

CONNECTIONS

WARNING: Test all gas pip- ing and connections for leaks after installing or servicing. Cor- rect all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1. Disconnect appliance with its appliance

main gas valve(control valve) and

equipment shutoff valve from gas sup-

ply piping system. Pressures in excess

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Fig- ure 21).

2.Pressurize supply piping system by ei- ther using compressed air or opening main gas valve located on or near gas meter.

3.Check all joints from gas meter to equipment shutoff valve (see Figure 22). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

4.Correct all leaks at once.

Open

Equipment

Shutoff

Valve

Closed

Figure 21 - Equipment Shutoff Valve

Pressure Testing Fireplace Gas Connections

1.Open equipment shutoff valve (see Fig- ure 21).

2.Open main gas valve located on or near gas meter.

3.Make sure control knob of fireplace is in the OFF position.

4.Check all joints from equipment shutoff valve to the gas control valve (see Fig- ure 22). Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak.

5.Correct all leaks at once.

6.Light fireplace (see Operating Fire- place, pages 14 through 16). Check all other internal joints for leaks.

7.Turn off fireplace (see To Turn Off Gas to Appliance, page 15).

 

of 1/2 psig will damage fireplace gas

 

regulator.

2.

Cap off open end of gas pipe where

 

equipment shutoff valve was con-

 

nected.

3.

Pressurize supply piping system by ei-

 

ther using compressed air or opening

 

main gas valve located on or near gas

 

meter.

4.

Check all joints of gas supply piping

 

system. Apply mixture of liquid soap

 

and water to gas joints. Bubbles form-

 

ing show a leak.

5.

Correct all leaks at once.

6.

Reconnect fireplace and equipment

 

shutoff valve to gas supply. Check re-

 

connected fittings for leaks.

,Q¢,,,,,,,,QQQQQQQQ¢¢¢¢¢¢¢¢,Q¢

Gas Control Valve

Figure 22 - Checking Gas Joints

Equipment

Shutoff

Valve

Gas Meter

12

104636

Image 12
Contents OWNER’S Operation and Installation Manual What to do if YOU Smell GASSafety Information Unvented Natural GAS FireplaceRemote Control Accessories Product IdentificationLocal Codes UnpackingProduct Features AIR for Combustion and VentilationAIR for Combustion Ventilation Determining FRESH-AIR Flow for Fireplace LocationDetermining if You Have a Confined or Unconfined Space Ventilation AIR Ventilation Air From InsideBuilding Ventilation Air From OutdoorsInstallation Installing Deflector and HoodCheck GAS Type Electrical HookupInstallation Clearances Conventional Fireplace InstallationBUILT-IN Fireplace Installation Location of Nailing FlangesInstallations Mantel Clearances for BUILT-IN InstallationInstalling GAS Piping to Fireplace Location Installation Items NeededConnecting Fireplace to GAS Supply Attaching Flexible Gas Lines TogetherPressure Testing Gas Supply Piping System Pressure Testing Fireplace Gas ConnectionsChecking GAS Connections Installing Logs Will create sootFor Your Safety Read Before Lighting Operating FireplaceLighting Instructions Manual Lighting Procedure To Turn OFF GAS To ApplianceOptional Remote Operation Inspecting Burners Optional Blower OperationPilot Flame Pattern Burner Primary AIR HolesTroubleshooting Observed Problem Possible CauseObserved Problem Possible Cause Remedy Gas leak. See Warning statement Wiring Diagram Replacement Parts SpecificationsService Hints Technical ServiceCleaning and Maintenance Cleaning Burner Injector Holder and Pilot AIR Inlet HoleLogs Front Window GlassAccessories Brass Trim Accessory GA6090 Cleaning KIT CCKReceiver and HAND-HELD Remote Control KIT Ghrc Series WALL-MOUNT Thermostat Switch GWMT1Illustrated Parts Breakdown Remote Ready Catalytic Model VCGF30NRParts List KEY Part Number Description QTYFireplace VCGF30NR Parts List Warranty Information