valve must be marked with maximum set pressure not to exceed the marked maximum allowable working pressure of the water heater (150psi). Install the valve into the opening provided and marked for this purpose in the water heater, and orient it or provide the tubing so that any discharge from the valve will exit only within 6 inches above, or at any distance below the structural floor and cannot contact any live electrical parts. The discharge opening must not be blocked or reduced in size under any circumstances.
qCAUTION: A relief valve is designed to discharge excessively hot water. THE CUSTOMER IS
RESPONSIBLE TO PROTECT PROPERTY AND PERSONNEL FROM HARM WHEN THE VALVE FUNCTIONS.
qInstall the T&P provided on hot water outlet of tank as shown in Figures 1 and 2.
qCare must be taken to be sure that the stem of the
qThe drain line from the relief valve must not be concealed or blocked and must be protected from freezing.
qWARNING: IF THE WATER SUPPLY IS FROM A WELL, OR KNOWN TO HAVE HARD WATER, IT IS RECOMMENDED TO USE A PRESSURE RELIEF VALVE IN THE COLD WATER LINE AS WELL AS A T&P VALVE IN THE HOT WATER LINE.
E.INSTALLING THE REMOVABLE HEAT EXCHANGER
qHeat exchanger is installed at the factory except for the AL119SL which is shipped loose. The following is provided for servicing or removing the heat exchanger.
qInsert heat exchanger with plastic
qWARNING: Plastic
•Insert and secure the bolts to the nuts one at a time in the following manner:
•Place the nut beneath the flange opening.
•Hold the nut in place with one hand – insert the bolt with the other.
•Thread the bolt into the nut and tighten in proper order.
NOTE: Be sure to place bolts in all of the openings.
qHeat exchanger connections are 3/4” male threaded fittings, except for the AL119SL which has 1 inch male threaded fittings.
qConnect the supply line (from the boiler) to the “Hx In” fittings of the heat exchanger. It is recom- mended to use a union as per Figures 1 and 2.
qConnect the return line (back to the boiler) to the “Hx Out” fittings on the flange of the heat exchanger. It is recommended to use a union as per Figures 1 and 2.
WARNING: Plastic
F.WATER SUPPLY CONNECTIONS
q WARNING: Some local codes mandate the use of a backflow preventer or check valve or
q All water supply fittings on this heater are brass – do not over tighten or strip threads. q It is recommended to use a union as per Figures 1 and 2.