Weil-McLain 550-141-826/1201 manual Connect Wiring, General wiring requirements, Thermostat wiring

Page 19

Connect Wiring

General wiring requirements:

Electric shock hazard. Can cause severe personal injury or death if

power source, including service switch on boiler, is not disconnected before installing or servicing.

Installations must follow these codes:

National Electrical Code, ANSI/NFPA 70, latest edition and any additional national, state or local codes.

In Canada, CSA C22.1 Canadian Electrical Code Part 1 and any local codes.

Wiring must be N.E.C. Class 1. If original wire as supplied with boiler must be replaced, type 105°C wire or equivalent must be used. Supply wiring to boiler and additional control wiring must be 14 ga. or heavier.

Provide electrical ground at boiler as required by codes.

Thermostat wiring:

Install thermostat on inside wall away from influences of drafts, hot or cold water pipes, lighting fixtures, television, sun rays or fireplaces.

Follow instructions with thermostat. If it has a heat anticipator, set heat anticipator in thermostat to match power requirements of equipment connected to it. Boiler wiring diagrams give setting for standard equipment.

Junction box (furnished):

Junction box houses electrical connections for all boiler components.

“P” boilers have harnesses furnished.

“A” boilers are furnished with burner and limit harnesses.

All field-provided high voltage wiring must be sheathed in flexible metal conduit.

Connect incoming line voltage “HOT” wire to service switch, and neutral wire to white wire. Field-install equipment ground wire to green wire with wire nut.

Service switch (15 amp) is provided with boiler. “A” boilers — install switch as shown.

Some local codes may require an emergency shut-off switch installed at a location away from boiler. Follow local codes.

Burner wiring:

Burner harness incorporates a disconnect plug, providing a convenient way to disconnect wiring when burner mounting door is opened.

All “P” boilers have a power disconnect plug installed on burner.

On “A” boilers, mount the plug (provided in water trim carton) on the burner housing as shown in FIGURE 15. For Carlin burners, screw burner plug into threaded conduit coupling, then mount this assembly to the burner housing using the chase nipple. Route wires through housing and make connections in burner junction box as shown in boiler wiring diagram.

19

Image 19
Contents This Manual Includes Installation Start-Up Boiler Parts Hazard Definitions Symbol DefinitionsWhen Calling or Writing About the Boiler Read This Page FirstTable of Contents Provide clearances around boiler see Figure Before Installing BoilerInstallations must comply with Before selecting boiler locationLay a foundation, if needed Provide air for combustion and ventilationBoiler Foundation Size Table Go to page 12 to connect breeching and venting Install Packaged BoilerPlace boiler Perform hydrostatic pressure testChange From Back Flue Outlet to Top Flue Outlet Optional Fiberglass wool and ceramic fiber materials Install Non-Packaged BoilerFlue Collector Hood Control Tapping Table Install Packaged and Non-Packaged BoilerInstall jacket sizes 7 through 9 only Install boiler controlsInstall burner also refer to instructions packed with burner General chimney requirements Connect BreechingMinimum Chimney Size Table Connect Breeching Diaphragm expansion tank Figure Install pipingConnect Water Piping General piping informationIsolation Zoning with circulators Piping Multiple ZonesPiping for systems requiring temperatures below 140F Use with refrigeration systems Burner wiring Connect WiringGeneral wiring requirements Thermostat wiringConnect Wiring Connect Wiring General oil piping requirements Connect Oil PipingOil piping connection at burner To place in operation Start-UpFill the system Tips for water systemsCheck off steps as completed Check-Out ProcedureAppendix Burner adjustments for P and a boilersClose clearance installation Dimension a Description Parts ListParts Drawing Dimensions DimensionsIntermediate DIA WGO Gold OIL Water Boiler Ratings Ratings

550-141-826/1201 specifications

The Weil-McLain 550-141-826/1201 is a high-efficiency boiler designed for commercial applications, providing unmatched performance, reliability, and advanced technology features. This model is specifically engineered to cater to a range of heating needs, making it suitable for various settings, such as schools, hospitals, and large commercial spaces.

One of the key features of the Weil-McLain 550-141-826/1201 is its impressive thermal efficiency. With a high AFUE (Annual Fuel Utilization Efficiency) rating, this boiler maximizes energy usage, resulting in lower utility costs for end-users. The efficient performance not only translates to better energy savings but also contributes to a reduced carbon footprint, aligning with modern sustainability goals.

The powerful burner technology incorporated in the Weil-McLain 550-141-826/1201 ensures precise control over the combustion process. This results in consistent heating performance and minimizes emissions, meeting stringent environmental regulations. The unit utilizes advanced modulation technology, which allows the burner to adjust its output according to the demand, providing significant energy savings and enhanced comfort.

Another standout characteristic of this boiler is its robust construction. Built with high-quality materials, the Weil-McLain 550-141-826/1201 is designed to endure demanding conditions, ensuring longevity and reduced maintenance needs. The boiler features a durable heat exchanger, which optimizes thermal transfer efficiency while resisting corrosion and thermal stress.

The user-friendly controls and monitoring systems enhance the operational experience, allowing for easy adjustments and status checks. The integrated diagnostic capabilities provide valuable insights for troubleshooting, making maintenance straightforward and reducing downtime.

Furthermore, the versatility of the Weil-McLain 550-141-826/1201 allows for multiple installation configurations, accommodating different system requirements and space limitations. Its compact design makes it an ideal choice for facilities where space is a premium.

In summary, the Weil-McLain 550-141-826/1201 stands out in the commercial boiler market with its high efficiency, innovative burner technology, robust construction, user-friendly controls, and versatile installation options. This model exemplifies Weil-McLain's commitment to energy-efficient heating solutions, setting a benchmark for performance and reliability in the industry.