Patterson-Kelley MACH-05 manual Air Inlet Requirements, Electrical Connections at Rear of Boiler

Page 11

MACH® Series Gas-Fired Boiler

An external electrical disconnect (not supplied with the boiler) with adequate overload protection is required. The boiler must be grounded in accordance with local codes or in the absence of such requirements, in the U.S. with National Electrical Codes, ANSI/NFPA No. 70 latest edition and in Canada to the current Canadian Electrical Code, Part I, CSA C22.1.

Note: A dedicated earth ground (green wire) is required to avoid nuisance shutdowns. Do not ground through the conduit. It is also important that proper polarity be maintained.

Note: Refer to Terminal Block Assignments (Section 6.1.1).

120 Volt

Low Voltage

Control Junction

Electrical Control

Box

Junction Box

 

Electrical Connections at Rear of Boiler

3.5COMBUSTION AIR

Combustion air must be free from dust, lint, etc. The presence of such materials in the air supplied to the burner could cause nuisance "Low Air" shutdowns or premature burner failure. The boiler should not be operated during construction while the possibility of drywall dust, demolition dust, etc. exists.

The combustion air supply must be completely free of chemical fumes which may be corrosive when burned in the boiler. Common chemicals which must be avoided are fluorocarbons and other halogenated compounds, most commonly present as refrigerants or solvents, such as freon, trichlorethylene, perchlorethylene, chlorine, etc. These chemicals,

Page 7

Installation

when burned, form acids which quickly attack the boiler and the boiler stack. The result is improper combustion and premature boiler failure.

Provisions for combustion and ventilation air must be in accordance with Section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1, latest edition, or applicable provisions of the local building codes. In Canada, combustion air openings shall comply with CSA B.149 Installation Code. The formula is 1 sq. in. per 1,000 Btu/hr of gas input not less than 100 sq. in. The location shall be neither more than 18", nor less than 6" above the floor level.

The boiler room shall be provided with two openings to ensure adequate combustion air and proper ventilation. One opening should be 6 to 12 inches above the floor and the other 6 to 12 inches below the ceiling, preferably on opposite walls. The size of each opening is determined by whether air is taken from inside or outside the building. In Canada, ventilation air openings shall be at least 10% of the cross sectional area required for combustion air, but not less than 10 square inches. It is to be located at the highest practical point communicating with outdoors.

WARNING!

Under no circumstances shall the boiler room ever be under a negative pressure. Particular care should be taken when exhaust fans, compressors, air-handling units or other equipment may rob air from the boiler.

3.5.1 Air Inlet Requirements

If air is taken directly from outside the building, each opening (minimum of two) should have a net free area of 1 square inch for each 4,000 Btu per hour of total boiler input. For instance, 112.5 square inches are required for 450,000 Btu per hour input.

When air is taken from the outdoors through a vertical duct, 1 square inch per 4,000 Btu per hour is required. If a horizontal duct is used, 1 square inch per 2,000 Btu per hour is required, i.e., 225 square inches for 450,000 Btu per hour input.

Image 11
Contents PATTERSON-KELLEY Mach Series Gas-Fired Boiler Operation What to do if you smell gas Introduction SafetyElectrical Hazards Burn, Fire, and Explosion HazardsBoiler Size Weight in PoundsCrush Hazards Chemical HazardsSlip, Fall Hazards Pressure HazardsInitial Inspection InstallationStorage Prior to Installation PlacementClearances Adjustable Legs for Leveling and Floor ClearanceElectrical Connections at Rear of Boiler Air Inlet RequirementsFlue Connection at Boiler Required ClearancesVenting for Multiple Boilers Sidewall InstallationsRooftop Installations Vent TerminationsIntake/Exhaust Layout Sealed Combustion Air/Venting SystemRemoving an Existing Boiler Sidewall Inlet, Roof Vent Roof Inlet and Vent Intake Duct Connection to Boiler Intake Duct TerminationsIntake Duct Materials and Sizes Sealing the Intake DuctGas Piping Vent ElbowsTape on gas line threads Intake Termination DetailsInches Gas Supply Piping by InstallerPiping Design FeetBoiler Inlet and Outlet Connections Boiler Inlet and Outlet ConnectionsFlushing and Filling Boiler Water Piping by InstallerInspection Mach C300 & C450 Test of Ignition Safety SystemTest of High-Limit Control Test of Gas Pressure SwitchTest of Low Water Cut-out Operating Temperature Controller Step Value UpperDescription Lower Limit Parameter Value Parameter Value Allowable RangeParameter Value Allowable Range F Outdoor AIR vs Boiler SetpointGas Pressure Adjustment Gas Pressure Test Port Air Flow AdjustmentsGas Valve Setup and Adjustment CO2 C300/450 Adjusting Low and High FireMach C750, C900 & C450 C750/900/10500 Adjusting Low and HighControl Panel Front Lighting ProceduresNormal Shut Down Procedures OperationRate Emergency Shut-OffEmergency Shut-Off Daily MaintenanceWeekly Monthly During OperationAnnually Semi-Annually every 6 monthsLoss of Power Loss of Water Level Code Lockout Manual Reset Service CodesDo not Auto-reset Service CodesPARTS/TECHNICAL Support Terminal Number Label Description Terminal Block Assignments High Voltage Circuit TB21a Terminal Block Assignments Low Voltage Circuit TB1 Wiring Series C-300 Wiring Series C-450 Wiring Series C-750/900/1050 Mach Series 300/450 Main AssemblyMark Description Control PanelDisplay Panel 4 C-300/450 Heat Engine Mark Description Mark Description 5 C-750/900/1050 Heat EngineMark Description 6 C-300 Boiler Gas Train7 C-450 Boiler Gas Train 8 C-750/900/1050 Boiler Gas Train Mark Description Remedy Limited WarrantyThird Party Warranties CO2 AppendixParameter Settings for Mcba Controls Description Lower Limit Upper Limit Installed 2X = 3 way valve normally closed

MACH-05 specifications

The Patterson-Kelley MACH-05 is an innovative high-efficiency boiler designed to meet the demanding needs of today’s commercial and industrial applications. Known for its remarkable performance and advanced technologies, the MACH-05 stands out in the market with its ability to provide reliable heating solutions while minimizing energy consumption and environmental impact.

One of the key features of the MACH-05 is its cascading capability. This allows multiple units to be linked together for enhanced capacity and redundancy. By operating in a modular system, users can achieve optimal energy efficiency by adjusting the number of active units based on real-time demand. This ensures that the system operates at peak efficiency, increasing overall reliability and reducing operational costs.

The MACH-05 is equipped with a fully modulating burner system, which ensures precise control of output and efficiency across a broad range of operating conditions. This advanced burner technology facilitates a significant reduction in fuel usage compared to traditional fixed-output systems. Combined with its high thermal efficiency rating, the MACH-05 is not only environmentally friendly but also economically advantageous for facilities looking to lower energy expenses.

In terms of construction, the MACH-05 features a compact, lightweight design that allows for easy installation and integration into existing systems. Its stainless steel heat exchanger is built to provide superior durability and resistance to corrosion, ensuring a long operational lifespan and reducing maintenance requirements. This design advantage translates into lower lifecycle costs for end-users.

The boiler also incorporates intelligent control systems that enhance operational efficiency. These controls can monitor and adjust parameters in real-time, optimizing performance and offering detailed diagnostics to anticipate maintenance needs. The user-friendly interface makes it easy for operators to manage the system and access vital information regarding performance metrics.

Additionally, the MACH-05 is designed with safety in mind, featuring multiple safety controls and alarms that function to protect both the equipment and personnel. This commitment to safety ensures that facilities can operate with peace of mind, knowing that they have a reliable and secure heating solution.

In summary, the Patterson-Kelley MACH-05 combines advanced engineering, efficiency, and safety features to provide a versatile and dependable heating solution. Its key advantages, including cascading capabilities, fully modulating burner technology, and intelligent controls make it an ideal choice for commercial and industrial applications, paving the way toward sustainable and cost-effective heating systems.