(1)FIELD CONVERSION OF A NHDI/SC SERIES HUMIDIFIER WITH NORTEC LINKS 2

BACNET, LONWORKS AND N2 MODULES:

Router Power

 

LINKS 2

 

Module

 

 

 

 

Supply

 

 

 

OnLine

Module

LAN Router or Switch (BACnet/IP)

Figure 1. Component Identification

A.MOUNT THE LINKS 2 ASSEMBLY

(1)Refer to Figure 2 for the mounting location of the Nortec LINKS 2 Bracket on the NHDI or NHSC unit. If pilot holes for the mounting screws are not already present on the humidifier frame follow steps 2 and 3. If pilot holes are present then disregard steps 2 and 3.

(2)Using the bracket assembly as a template, mark locations of pilot holes on the NHDI/SC humidifier cabinetry.

(3)Using 1/8” drill bit, drill pilot holes for the bracket mounting screws.

(4)Install the bracket assembly using the provided #8-32 screws. Note that 2 #8-32 nuts have been supplied to secure the 2 top mounts. The third screw will thread into the humidifier cabinet itself.

10-30

Page 2 2008-02-15

Image 15
Contents Retrofit Instructions for Gstc / Setc / Nhtc Nhdi / Nhsc Proprietary Notice Liability Notice Table of Contents A SE-50 Links Field InstallationConfiguring the Humidifiers Links Field Conversion GSTC/SETC LAN Mounting the Links 2 Assembly Configuring the Humidifiers Links Field Conversion Nhtc Module Hook Position Configuring the Humidifiers Links Field Conversion NHDI/SC Supply OnLine Module LAN Router or Switch BACnet/IP Use 8-32 screws Use 8-32with nuts screw Only Nhdi Links 2 Slave Installation 10-30 Warranty Authorized Agent