Nortec Industries NHSC, SETC, NHDI installation manual Use 8-32 screws Use 8-32with nuts screw Only

Page 16

Use 8-32 screws

Use 8-32with nuts screw

only.

Figure 2. LINKS 2 Bracket Placement

B.WIRING THE NORTEC LINKS 2 MODULE

(1)Most of the wiring connections for the Nortec LINKS 2 module will have already been finished at the factory, however, there are a few connections that will need to be made to connect the module to the NHDI/SC series humidifier. Refer the LINKS 2 wiring diagram included in the package for details.

(2)Module Wire Connections:

(a)There will be a wire harness provided that will consist of a red and blue wire, each terminated with a bare end. These wires should already be connected to the 24VAC and GND terminals on the LINKS 2 terminal strip. Both wires will be connected to the 5-pole connector labelled X1 (Main Supply) located on the humidifier support board. The red wire is to be connected to the terminal labelled L1. The blue wire is to be connected to the terminal labelled N.

(b)A loose ribbon cable with a 10-pin header plug and a 20-pin header plug will be included with the kit. The 20-pin header plug should be connected to the J2 connector on the TTL-to-RS485 converter located on the back of the LINKS 2 mounting bracket. The 10-pin header plug should be connected to the COM PORT connector located on the NHDI/SC Logic Board.

10-30

Page 3 2008-02-15

Image 16
Contents Retrofit Instructions for Gstc / Setc / Nhtc Nhdi / Nhsc Proprietary Notice Liability Notice Table of Contents Links Field Installation A SE-50Configuring the Humidifiers Links Field Conversion GSTC/SETC LAN Mounting the Links 2 Assembly Configuring the Humidifiers Links Field Conversion Nhtc Module Hook Position Configuring the Humidifiers Links Field Conversion NHDI/SC Supply OnLine Module LAN Router or Switch BACnet/IP Use 8-32 screws Use 8-32with nuts screw Only Nhdi Links 2 Slave Installation 10-30 Warranty Authorized Agent