Lifebreath 155MAX RX, 200MAX RX, 155ECM Model 200ERV, Dimensions 200ERV inches mm

Page 14

 

 

Model 200ERV

ENGINEERING DATA

 

 

 

 

 

PERFORMANCE

 

LATENT RECOVERY/MOISTURE TRANSFER CORE

 

The cross-flow energy recovery core transfers heat and water vapour

 

 

 

 

 

Net supply airflow in cfm (L/s) against external static pressure

between the two airstreams. It is easily removed for cleaning or service.

E.S.P

cfm

L/s

MOTORS AND BLOWERS

@ 0.1” (25 Pa)

232

(109)

Each air stream has one centrifugal blower driven by a common PSC

 

 

 

 

 

motor. 5 speed fan operation. High speed - 120 VAC.

@ 0.2” (50 Pa)

223

(105)

FILTERS

@ 0.3” (75 Pa)

215

(102)

Washable air filters in exhaust and supply air streams.

 

 

 

 

 

MOUNTING THE ERV

@ 0.4” (100 Pa)

195

(92)

Four threaded inserts at corners of case designed to accept four PVC

@ 0.5” (125 Pa)

189

(89)

reinforced polyester straps that are supplied with the unit.

 

 

 

 

 

CASE

Sensible Effectiveness

 

 

67%

Twenty gauge prepainted galvanized steel (G60) for superior corrosion

 

 

@ 127 cfm (60 L/s) (CSA C439M)

resistance. Insulated to prevent exterior condensation.

 

 

 

 

 

 

CONTROLS

Sensible Efficiency

32°F (0

O

C)

60%

ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode, Recirculation

 

 

 

 

 

 

mode (on compatible units), (each mode has 5 speeds). Control pad can

Total Efficiency

 

 

 

55%

be removed from HRV and remotely mounted.

 

 

 

Weight 63 lbs. (28.7 kg) Shipping Weight 65 lbs. (29.6 kg)

 

 

 

 

 

VAC @ 60HZ

 

 

 

120

 

 

 

 

 

 

 

 

 

 

 

WATTS / Low speed

 

 

 

87

 

 

 

 

 

 

DIMENSIONS 200ERV inches (mm)

*All Duct Connections 6"(150mm)

ENTHALPIC CORE

STALE AIR

MOTOR

FROM INSIDE

 

BALANCING

 

DAMPER

 

FILTERS

 

FRESH AIR

 

FROM OUTSIDE

 

 

33-5/8"

 

(850)

FRESH AIR TO INSIDE

BALANCING

DAMPER

STALE AIR

TO OUTSIDE

BLOWERS

19"

(483)

*NOTE: Front clearance of 25 inches (635 mm) is recommended

for servicing unit.

143/4"

(375)

OPTIONS

99-104 Digital Electronic Timer - 20/40/60 min. (3 wire)

99-109 Air Sentry™ Air Quality Monitor designed to accept remote-

ly mounted Control Pad

99-186 Weatherhoods, Two - 6” (150mm) c/w 1/4” (6mm) mesh screen

WARRANTY

Units carry a 5 year warranty on the energy recovery core and replace- ment parts.

ERVs are not recommended for regions where the design temperature is below 25°F (-4°C)

200ERV FANCURVE

5 HIGH SPEED*

 

200

 

 

 

 

4

MEDIUM HIGH SPEED

 

 

5

 

 

 

 

 

?

Manufacturers Data

3

MEDIUM SPEED

 

175

 

*

 

 

2

MEDIUM LOW SPEED

 

 

 

 

 

 

 

150

4

 

 

 

1

LOW SPEED

 

 

 

 

 

 

 

 

 

(cfm)

 

3

 

 

 

 

 

 

125

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

Flow

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

Air

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

 

 

 

 

 

 

 

 

25

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

Static Pressure (in H2O)

All units conform to

CSA and UL standards.

TI-98E

14

0805

Image 14
Contents 155MAX 155ECM 200MAXMaintenance Table of ContentsInstallation WarrantySo why use an ERV? Where do you use an ERV instead of an HRV?Why transfer moisture in the summer cooling season? What is the maintenance?Page Dimensions 95MAX inches mm Model 95MAXDimensions 155MAX inches mm Model 155MAXDimensions 155ECM Performance Model 155ECMDimensions 155MAX RX inches mm Model 155MAX RXDimensions 200MAX inches mm Model 200MAXDimensions 200MAX RX inches mm Model 200MAX RX Dimensions Maxtop inches mm Model MaxtopDimensions 195DCS inches mm Model 195DCSDimensions 300DCS inches mm Model 300DCSDimensions 200ERV inches mm Model 200ERVDimensions 200ERVD inches mm Model 200ERVDSelf Test GlossaryFunction and Controls Operating the ControlAir Automatic Defrost Operation20 on / 40 OFF Which Mode of Operation is Best for Me?Modes of Operation LED Indication To select speedControl Pad Mounted in the Control Module ControlAirCrank Timer Optional TimersDigital Electronic Timer DET Ventilation DehumidistatUsing the Dehumidistat Variable Port Location MAX Port SpecificationsRound port bent to oval MAX Air FlowInstalling the Drain Line and P-Trap Installation LocationConnecting Appliances to the HRV/ERV MountingWarmside Ducting Indirect Connection to Ductwork Supply Air DuctingDirect Connection to Furnace Ductwork Stale Air Exhaust SystemInstallation Diagrams Partially Dedicated SystemSimplified Installation Supply/Return Method Fully Dedicated System Balancing Procedure Pitot Tube Air Flow BalancingBalancing Collar Instructions Hard/Rigid DuctingGeneral Maintenance Twice a Year Clean Core Twice a Year a open access doorTo install the clean core Cleaning the FansMotors Maintenance Free Symptom Cause Solution Troubleshooting your HRV/ERV SystemWire Residential Wiring Diagram Residential Wiring Diagram For All Models Except 155ECMResidential Wiring Diagram Residential Wiring Diagram 155ECM