KMC BAC-10000 manual Advanced BACnet Device Properties, Advanced Inputs Advanced Motion Sensor

Page 8

(Advanced) BACnet Device Properties

(Advanced) Temp. Setpoint Limits

DEVICE

INSTANCE: 1

NAME: FlexStat_101

LOCATION: KMC Controls

RESTART: NO

RESTORE FACTORY: NO

LIMITS OCC MIN CLG: 71° F OCC MAX HTG: 76° F UNOCC MIN CLG: 77° F UNOCC MAX HTG: 65° F

To set the BACnet device instance, name, and location, press:

1.Up/Down to move among entries.

2.Enter to select.

The FlexStat can also be restarted or restored to factory defaults from this menu. See Resetting the FlexStat on page 14 for more information about that function.

To set the minimum and maximum allowed user/ operator setpoint values, press:

1.Up/Down to move among entries.

2.Enter to select.

3.Right/Left to move among value fields.

4.Up/Down to increment/decrement value.

(Advanced) Inputs

(Advanced) Motion Sensor

MOTION SENSOR

MOTION OCC: ENABLE

INPUTS

1:SPACE TEMP

2:DISCH AIR TEMP

3:MIXED AIR TEMP

4:OUTSIDE AIR TEMP

4:SPACE HUMIDITY

INPUT #2

DISCH AIR TEMP

VALUE: 60.0° F

CAL. OFFSET: 0.0

OUT-OF-SERVICE: FALSE

SENSOR: 10K TYPE III

STATE: OCCUPIED

In BAC-11xxx models, a motion/occupancy sensor may be enabled to trigger occupancy override. During scheduled “off” times, the motion sensor will start occupancy override (for 1 hour as a default)

Inputs vary according to model, selected application, and selected application options. See (Advanced) Ap- plication Options on page 5.

To change sensor type and calibration offset, press:

1.Up/Down to move among entries.

2.Enter to select.

3.Right/Left to move among value fields.

4.Up/Down to increment/decrement value.

Value will show a temperature reading or a voltage (0.0 to 3.0), depending on the sensor. Analog sensors can be calibrated using the Calibration Offset option.

when it detects motion. Occupancy override will end (with the default setting) 1 hour after motion was last detected. The length of occupancy override is configurable in the System menu. See System Setup on page 13.

To enable/disable or monitor the motion/occupancy sensor (if installed), press:

1.Enter to select.

2.Right/Left to move among value fields.

3.Up/Down to increment/decrement value.

The State field monitors whether motion has been detected during the last scan of the motion sensor input (BI6). Detected motion will show an “occu- pied” state. This can be used during troubleshooting to determine if motion is being detected.

BAC-10000 Series

8

Operation Guide, Rev. J

Image 8
Contents Operation Guide Overview Applications and Installation Operation Basic About the FlexStat Configuration Initial SetupMain Menu Overview Advanced Menu Advanced Application OptionsSensor Setup Staging SetupValve Setup Advanced CB Control Basic ProgramsAdvanced BACnet Communications Advanced Date/TimeAdvanced Temp. Setpoint Limits Advanced BACnet Device PropertiesAdvanced Inputs Advanced Motion Sensor Advanced Security Levels and Passwords Menu Items Access LevelsAdvanced Trend Logs Advanced TestAlarms Date/TimeSchedules Trend Viewer System SetupSetpoints Warm and Cold Starts Resetting the FlexStatTypes of Reset Restore Factory PC Data Port Connection Network ConnectionBACnet MS/TP Network Communication Communication Issues TroubleshootingAlarm Issues Cover and Display Issues Custom Programming and Web IssuesInput, Sensor, and Value Issues Temperature Reading Is IncorrectTemperature Setpoint Is Not Maintained Input Values Are Outside the Expected RangeOutput, Fan, and Relay Issues Analog Output Does Not WorkFan Does Not Run Relay Internal Does Not WorkWiring Issues Relay External Does Not WorkMaintenance Firmware UpgradeAccessories Programming CustomSupport Important NoticesReference Acronyms and AbbreviationsDefinitions of Terms For this document are included on thisSymbols IndexBAC-10000 Series KMC Controls, Inc

BAC-10000 specifications

The KMC BAC-10000 is a cutting-edge building automation controller designed to offer exceptional performance in monitoring and controlling HVAC systems, lighting, and various other building systems. This advanced controller is engineered to enhance energy efficiency, improve occupant comfort, and provide streamlined building management capabilities.

One of the main features of the KMC BAC-10000 is its versatility. It supports a wide variety of communication protocols, including BACnet, Modbus, and LonWorks. This multi-protocol capability allows for seamless integration with existing building systems, ensuring that users can easily incorporate the BAC-10000 into their building management setup without the need for additional hardware or extensive modification.

The controller is equipped with an intuitive user interface that simplifies the management of building systems. It includes a graphical display that provides real-time data, enabling operators to monitor system performance, adjust settings, and troubleshoot issues with ease. This user-friendly design promotes efficient operation and reduces the learning curve for new users.

In terms of technical specifications, the BAC-10000 boasts a powerful microprocessor and an extensive range of I/O points, allowing it to handle large and complex building automation tasks. With support for both digital and analog inputs and outputs, users can customize their setup to meet specific operational requirements.

Another standout feature of the KMC BAC-10000 is its advanced data logging capabilities. The controller can record historical data for various parameters, which can be crucial for performance analysis and optimization. This functionality enables facility managers to identify patterns, predict maintenance needs, and ultimately enhance the overall efficiency of their systems.

Security is also a priority with the BAC-10000, as it includes multiple layers of security protocols to protect against unauthorized access and tampering. This ensures that sensitive building management data remains safe and that users can operate the controller confidently.

In conclusion, the KMC BAC-10000 is a robust and flexible building automation controller that offers extensive features and technologies for effective building management. Its multi-protocol support, user-friendly interface, advanced data logging, and emphasis on security make it a top choice for modern building automation needs. By choosing the BAC-10000, facility managers can optimize energy usage, improve occupant comfort, and streamline operations within their buildings.