GSW Gas Fired Water Heater warranty III GAS Connections, IV Water Pipe Connections, Gas Pressure

Page 5

FIGURE 4

III) GAS CONNECTIONS

Install the gas piping as shown in Figure 4. Use only new pipe and fittings with clean-cut threads. Sealing compounds used on the pipe threads shall be approved for use with natural and propane gas.

Use gas piping of adequate sizing to ensure full gas input. Gas piping material must be approved for use with natural gas and propane fuels. All piping must comply with all local codes or , in the absence of local codes, the latest edition of CAN/CGA B149.1 installation code in Canada / National Fuel Code ANSI Z223•1 (NFPA 54) in the USA. The final connection to the water heater is made using 1/2” N.P.T.

Before connecting to the gas service, check that a properly sized gas meter and regulator are available to service the water heater. If other appliances are using the same meter and regulator, ensure that the capacity of the meter and regulator matches that of the combined input of all appliances connected to it.

Ensure that the piping is large enough to satisfy the requirements of all appliances connected to the gas service. Undersize piping can restrict gas flow causing the water heater to perform poorly. Improperly sized piping may pose a safety hazard.

A manual gas shut-off valve shall be installed in the gas line near the water heater. A union is recommended for ease of service.

To trap dirt or foreign material in the gas supply, a dirt (drip) leg shall be installed in the piping at the heater.

Apply joint compound (pipe dope) to the male ends of the threads before joining pipe sections. Use only compounds that are compatible with natural gas and propane fuels. To prevent damage to the gas valve, do not over-tighten.

where ignition may occur. To avoid risk of fire or explosion ensure the area is well-ventilated and all sources of ignition are de- activated. Contact your local gas authority for local requirements.

IMPORTANT: Disconnect the water heater from the gas piping during any high pressure testing above 0.5 psi. Perform a leak test at normal gas pressure on all fittings after all connections have been made and the gas has been turned on. Soap test all connections of the gas system - bubbles indicate leaks.

IV) WATER PIPE CONNECTIONS

Pipe and fittings should be installed in compliance with the installation drawing. Have the installer show you where the water shutoff valve is installed so that you know where and how to shut the water off. It is recommended that such a valve be located in close proximity to the cold water inlet of the water heater. Water piping and fittings should be installed as shown in Figure 5.

NOTE: THE FITTINGS SUPPLIED WITH THIS WATER HEATER ARE 3/4” NPT.

1.Close main water supply and drain the piping system where water heater is to be connected.

2.Connect the cold water supply to the fitting marked ‘COLD’, and the hot water outlet to the fitting marked ‘HOT’.

3.When attaching solder (sweat) fittings, DO NOT APPLY

HEAT DIRECTLY TO THE WATER HEATER NIPPLES or the plastic liners will be damaged. Sweat adapters to the first section of the water piping before threading onto the water heater. Use a good grade of pipe joint compound that is certified for use with potable water on the threaded fittings.

4.Install a manual shut-off valve in the cold water supply line. It is good plumbing practice to include unions at the hot and cold connections as shown. (Figure 5)

Gas Pressure

5. IMPORTANT: Before putting the water heater into service,

GSW Water Heating Company recommends that the gas supply

 

make sure that a properly rated and sized temperature and

 

pressure relief valve is installed in the designated fitting in the

pressure, as measured on the inlet side of the water heater

 

water heater. See Temperature and Pressure Relief Valve

control, be set at 7.0“ water column for natural gas and 11.0“ water

 

section below.

column for propane gas. The above pressures must be measured

 

The relief valve is necessary to avoid excessive water pressure

during water heater operation. The gas control supplied with this

 

 

or water temperature from developing. Such a condition could

water heater is designed for a maximum inlet pressure of 0.5 psi

 

 

cause serious personal injury due to scalding or serious

(14” water column). For natural and propane gas do not exceed

 

 

physical damage to the water heater. This safety device shall

0.5 psi (14” water column).

 

 

be checked annually for proper operation.CHECK

 

 

WARNING

 

LOCAL CODES!

6. With water piping installed, check that a hot water faucet

Exposure to a higher gas supply pressure may cause damage to

 

served by the water heater is open and that the heater drain

the control, resulting in explosion or fire. Consult your local gas

 

 

valve is closed. Open the cold water supply valve and fill the

supplier and gas authorities. DO NOT PUT INTO SERVICE IF

 

 

water heater and piping system with water. When an

OVER-PRESSURIZATION HAS OCCURRED.

 

 

uninterrupted stream of water flows from the faucet, the system

The minimum inlet gas pressure required is 4.5 “ water column

 

 

is full. Close faucet. Check for leaks and repair as necessary.

for natural gas and 11.0 “ water column for propane gas.

 

 

 

NEVER OPERATE THE HEATER IF IT IS NOT

Purging Caution:

 

COMPLETELY FILLED WITH WATER.

 

 

7. Connect a hose to the drain valve and connect to drain.

Gas line purging is required to eliminate air from the piping

 

Open drain and let water run until clear to flush out any

system. Purging should be performed by persons experienced in

 

 

foreign matter that may have entered the system. Once

this type of gas service. Do not purge in confined areas or space

 

 

flushed, close the drain valve and disconnect hose.

 

 

– 5 –

Image 5
Contents Read these instructions thoroughly before starting For Your SafetyIntroduction ROUGH-IN Dimensions Installation Instructions Location and ClearancesAir Opening Requirements Combustion Air Supply DuctsLouvers and Grills IV Water Pipe Connections III GAS ConnectionsGas Pressure Purging CautionPressure BUILD-UP in a Water System Thermal Expansion Temperature Pressure Relief ValveT&PVenting Discharge lineFor Your Safety Read Before Lighting VI Lighting After InstallationLighting Instructions for Heater with SIT GAS Controls To Turn Off the Gas ControlOUT of Fuel Special Note on Propane Fuel GAS is Heavier than AIRVII Service and Maintenance Water Temperature RegulationHigher Setting Increases the Risk of Scald Injury Performance ChecksVent Maintenance Cathodic Protection Anode MaintenanceBurner Maintenance Tank FlushingViii Heating and Space Heating Combo Heating MaintenanceInstallation GSW-TECH ~ Certificate of Warranty ~