Fan Cycling Head Pressure Controls

Condenser fans are cycled to maintain adequate head pressure. . Ambient and pressure fan cycling are available as optional equipment...

.

Ambient fan cycling cycles fans in response to the ambient air temperature. .This control is ideal for multi-circuited condensers or for systems operating in mild ambient conditions. .See table

3 for minimum ambient temperatures for fan cycling. .Set points for thermostats will vary depending on the number of fans and condenser design T..D. .See table 4 for recommended set points...

.

Pressure fan cycling cycles fans in response to condenser pressure. .This style of control is more appropriate where the load on the condenser will vary due to multiple compressor operation or stages of unloading or systems incorporating heat reclaim or hot gas defrost..

Flooding Head Pressure Controls

Another means of head pressure control is to change the condenser capacity by filling the inside of the condenser with liquid refrigerant. .Flooding controls are ideal for condensers operating in low ambient conditions (beyond the limits of fan cycling controls) or under partial load conditions. .These controls require additional refrigerant charge to flood the condenser. . This additional refrigerant charge can often be reduced by incorporating the flooded control with one of the fan cycle controls previously described...

.

Several styles of flooding valves or combinations of valves are available. .Contact the valve manufacturer for specific recommendations..

Variable Speed

Condenser head pressure control is provided by varying the air flow through the condenser by changing the RPM of the condenser fan. .This control package is offered in combination with ambient fan cycling. .The fan motor next to the header end of the condenser is the variable speed fan...

.

The remainder of the fans are constant speed and are cycled separately using ambient sensing thermostats. .On condensers with two rows of fans, two variable speed fans are provided (one per unit) and the remainder of the fans are constant speed and are cycled in pairs..

Refrigerant Charge

The refrigerant charge for summer operation can be found in table 8. .This table also contains the additional charge required by flooding style controls...

.

Table 7 contains the recommended flooding charge required when combining fan cycling with flooding valves..

Splitting Controls

Additional head pressure can be provided by valving off a portion of the condenser circuit and removing that portion from the refrigeration circuit. .This is often referred to as splitting a condenser. .In addition to providing a means of head pressure control, this control will reduce the amount of refrigerant required to operate the condenser with a flooded head pressure control...

.

Condenser splitting is recommended as a seasonal adjustment controlled by ambient temperature. .An initial setting of 50° to 55° F with a 20° F differential is recommended. .A pressure switch is also provided as a backup control to prevent high head pressures

from occurring during heavy load conditions...

.

On condensers with a single row of fans the control package consists of an ambient sensing thermostat, a pressure switch sensing condensing pressure and a splitting relay. .The splitting relay provides a set of dry contacts to control the valves required to split the condenser (valves supplied by others)...

.

On condensers with double rows of fans, additional controls and contactors are provided to cycle all of the fans on the side of the condenser which has been split off...

.

Except as noted above, the splitting packages do not control fan cycling. .It is recommended that fan cycling be controlled by combining the splitting package with pressure fan cycling..

Image 9
Contents Air-Cooled Condensers Installation Operation Guide Installation System WarrantyInspection Sound VibrationDrawing 1. Rigging Instructions Walls or Obstructions Space and Location RequirementsMultiple Units Units in PitsTypical Arrangements Installation, Refrigerant PipingCondensing Temperature Correction Factor Electrical WiringDischarge Lines Tons of RefrigerationPage Fan Cycling Discharge Gas PulsationWinter Operation Head Pressure Control Flooding Head Pressure Controls Fan Cycling Head Pressure ControlsVariable Speed Splitting ControlsMinimum Ambient for Fan Cycling Mechanical Fan Cycling Thermostat SettingsPressure Chart Electronic Fan Cycling Thermostat SettingsModel Summer Charge Refrigerant Charge. Lbs. R-22 for Flooded CondenserCleaning Instructions MaintenanceFlooded Charge Temperature Difference Factor Model Cross ReferenceIn-Warranty Return Material Procedure InterLink Condenser Parts ListParts by InterLink Fan Motor PartExternal Control Signal Speed Adjustment CharacteristicsSeries Motors with Integrated Variable Speed Be sure that the unit is isolatedHead Pressure Setpoint Reverse acting or direct acting mode of operationMinimum Output Throttling rangeProtective Features Master/Slave ConfigurationPhase failure EC Motor WiringFAN 1 Header FAN FAN Motor Identification Installation Check List

none specifications

Heatcraft Refrigeration Products is a recognized leader in providing innovative and energy-efficient cooling solutions. The company specializes in manufacturing an extensive array of refrigeration systems designed to meet the demands of various commercial applications. With a strong commitment to quality and sustainability, Heatcraft integrates advanced engineering principles in every product, ensuring reliability and performance.

One of the standout features of Heatcraft products is their versatility. The company offers a wide range of refrigeration units, including condensing units, evaporators, and packaged systems, designed to accommodate different operational requirements. Whether it's for supermarkets, restaurants, or cold storage facilities, Heatcraft provides solutions that ensure optimal temperature control and energy efficiency.

Heatcraft places a significant emphasis on energy efficiency, developing technologies that help reduce operational costs while minimizing the environmental impact. Their products often incorporate advanced compressor systems, environmentally friendly refrigerants, and intelligent controls that adjust performance based on real-time conditions. This focus on energy-saving innovations not only benefits the planet but also boosts the bottom line for businesses that rely on refrigeration.

Furthermore, Heatcraft is known for its user-friendly design and ease of installation. Their systems are engineered for straightforward setup and maintenance, allowing businesses to minimize downtime and ensure seamless operations. This design philosophy extends to the company’s extensive catalog of components and accessories, providing customers with a comprehensive suite of options tailored to their specific needs.

Heatcraft also prioritizes customer support and service, offering resources and training for technicians to enhance their expertise in handling refrigeration systems. With a strong distribution network and support from knowledgeable representatives, customers can be assured that help is always accessible.

In addition, Heatcraft values innovation and continuously invests in research and development to stay ahead of industry trends. This dedication to advancement ensures that their products not only conform to current regulations but also anticipate future needs in the refrigeration sector.

Overall, Heatcraft Refrigeration Products exemplifies excellence in design, efficiency, and support, establishing itself as a trusted partner in the HVAC and refrigeration industries. Their commitment to quality and sustainability positions them as a frontrunner, meeting the evolving demands of a diverse market.