Reliance Water Heaters N85390NE, N71120NE Water heater installation, Water Line Connections

Page 20

water heater installation

Water Line Connections

This manual provides detailed installation diagrams (see pages 34-48 of this manual) for typical methods of application for the water heater(s).

The water heater may be installed by itself, or with a separate storage tank, on both single and two-temperature systems. When used with a separate storage tank, the circulation may be either by gravity or by means of a circulating pump. When a circulating pump is used it is important to note that the flow rate should be slow so that there will be a minimum of turbulence inside the heater.

Water (potable) Heating And Space Heating

1.All piping components connected to this unit for space heating applications shall be suitable for use with potable water.

2.Toxic chemicals, such as those used for boiler treatment, shall NEVER be introduced into this system.

3.This unit may NEVER be connected to any existing heating system or component(s) previously used with a non-potable water heating appliance.

4.When the system requires water for space heating at temperatures higher than required for domestic water purposes, a tempering valve must be installed. Please refer to installation diagrams on pages 34-48 of this manual for suggested piping arrangements.

Thermometers (not Supplied)

Thermometers should be obtained and field installed as shown in the installation diagrams.

Thermometers are installed in the system as a means of detecting the temperature of the outlet water supply.

Water Piping Diagrams

This manual provides detailed water piping diagrams for typical methods of application for the water heaters, see Water Piping Diagrams beginning on page 34.

The water heater may be installed by itself, or with a separate storage tank. When used with a separate storage tank, the circulation may be either by gravity or by means of circulating pump. When a circulating pump is used, it is important to note that the flow rate should be slow so that there will be a minimum of turbulence inside the water heater storage tank.

Adjust flow by throttling a full port ball valve installed in the circulating line on the outlet side of the pump. Never throttle flow on the suction side of a pump. See the Water Piping Diagrams beginning on page 34.

Note: In addition to the factory installed Temperature-Pressure Relief Valve (T&P valve) on the water heater, each remote storage tank that may be installed and piped to a water heating appliance must also have its own properly sized, rated and approved Temperature-Pressure Relief Valve installed.

Call the toll free technical support phone number listed on the back cover of this manual for further assistance in sizing a T&P valve for remote storage tanks.

T&P Valve Discharge Pipe

Explosion Hazard

Temperature-Pressure Relief Valve must comply with ANSI Z21.22- CSA 4.4 and ASME code.

Properly sized temperature- pressure relief valve must be installed in opening provided.

Can result in overheating and excessive tank pressure.

Can cause serious injury or death.

This water heater is provided with a properly rated/sized and certified combination temperature - pressure (T&P) relief valve by the manufacturer. See Temperature-Pressure Relief Valve on pages 12-13 for information on replacement and other requirements.

CAUTION

Water Damage Hazard

Temperature-Pressure Relief Valve discharge pipe must terminate at adequate drain.

Install a discharge pipe between the T&P valve discharge opening and a suitable floor drain. Do not connect discharge piping directly to the drain unless a 6” (15.2 cm) air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in adequate quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage.

T&P Valve Discharge Pipe Requirements:

Shall not be smaller in size than the outlet pipe size of the valve, or have any reducing couplings or other restrictions.

Shall not be plugged or blocked.

Shall not be exposed to freezing temperatures.

Shall be of material listed for hot water distribution.

Shall be installed so as to allow complete drainage of both the Temperature-Pressure Relief Valve and the discharge pipe.

Must terminate a maximum of six inches above a floor drain or external to the building. In cold climates, it is recommended that the discharge pipe be terminated at an adequate drain inside the building.

Shall not have any valve or other obstruction between the relief valve and the drain.

20

Image 20
Contents Installation Operation Service Commercial gas water heatersTable Of Contents Safe Installation, Use and Service ApprovalsGeneral Safety Information Fire and Explosion HazardHydrogen Gas Flammable PrecautionsGrounding Instructions Qualified Installer or Service Agency IntroductionAbbreviations Used QualificationsHydro Cannon self-cleaning system High limit switchLow Gas Pressure Switch Electronic ignition controlInstallation considerations Rough In DimensionsROUGH-IN-DIMENSIONS Recovery CAPACITIES, based on 80% efficiencyLocating the water heater ClearancesInstallation on combustible flooring Insulation BlanketHard Water Circulation pumpsHigh Altitude Installations Installation Requirements Power SupplyWater Temperature Control and Mixing Valves Gas pressure requirementsTemperature-pressure relief valve Dishwashing MachinesClosed Water Systems Thermal ExpansionValve Discharge Pipe Requirements Contaminated AirAir requirements Venting Unconfined SpaceConfined Space Multiple heater manifold Fresh Air Openings For Confined SpacesOutdoor Air Through Two Openings Outdoor Air Through One OpeningOutdoor Air Through Two Vertical Ducts Air From Other Indoor SpacesType B GAS Vent Multiple Gas Fired Tank-Type HeatersTechnical Data Venting Valve Discharge Pipe Water heater installationWater Line Connections Tube Inlet Installation Heater wiring GAS Piping GAS Supply Pipe Lengths in FeetPurging GAS Pressure RegulatorFilling AdjustmentsGeneral Lighting & Operation Label Check the Igniter Assembly Igniter AssemblyChecking Venting Main BurnerChecking the Input MAINTENANCE Remote storage tank temperature controlTemperature-Pressure relief Valve test Venting systemAnode rod inspection Draining and flushingTo Drain the Water Heater Storage Tank To Flush the Water Heater Storage TankDeliming solvents Tank Cleanout ProcedureDeliming Using FLO-JUG Method System diagnostics Ignition module systemHigh Water Temperature Shut OFF System For Your InformationElectrical Servicing Start up conditionsSequence of Operation Flow Chart Operational checklist Complaint Cause Remedy User Service AgentDiagrams Water PipingTemperature & Pressure Temperature & Pressure Relief Valve Circulating Pump Multi Flue 2 Units Multi Flue 2 Units with Vertical Storage Tank Multi Flue 2 Units with Vertical Storage Tank Return from Multi Flue 2 Units TWO Temperature Multi Flue 2 Units with Booster TWO Temperature MULTI-FLUE 3 Units MULTI-FLUE 3 Units with Vertical Storage Tank MULTI-FLUE 3 Units with Horizontal Storage Tank Multi Flue Flue 4 Units MULTI-FLUE 4 Units with Vertical Storage Tank MULTI-FLUE 4 Units with Horizontal Storage Tank Manifold Kits Page Page Page Page Limited Warranty Tennessee Waltz Parkway, Ashland City, TN Tech Support Parts

N71120NE, N85390NE specifications

Reliance Water Heaters has established itself as a trusted name in the water heating industry, consistently delivering high-quality products that meet the diverse needs of consumers. Among their offerings, the Reliance N71120NE and N85390NE models stand out due to their advanced features and innovative technologies.

The Reliance N71120NE is known for its efficient heating capabilities, boasting a 40-gallon capacity that is ideal for medium-sized households. This model features a durable glass-lined tank that provides exceptional resistance to rust and corrosion, ensuring longevity and durability. One of its standout characteristics is the built-in energy-saving mode, which optimizes energy consumption without compromising performance. This unit operates on electricity, making it a versatile option for various settings. Additionally, the N71120NE is designed with a temperature control thermostat, allowing users to set and maintain their desired water temperature with ease.

On the other hand, the Reliance N85390NE model offers a larger capacity of 50 gallons, making it suitable for larger families or homes with increased hot water demands. Similar to the N71120NE, this model comes with a glass-lined tank for superior protection against corrosion. One of the advanced technologies featured in the N85390NE is the High-Quality Insulation System, which minimizes heat loss and maintains water temperature efficiently. This model also includes a self-diagnostics system, providing users with real-time updates on performance and maintenance needs. The innovative anode rod in this unit extends the lifespan of the tank by sacrificially corroding instead of the tank itself.

Both models are designed with safety in mind, featuring a pressure relief valve that prevents pressure buildup, making them safe for residential use. Moreover, each unit adheres to the latest energy efficiency standards, contributing to reduced utility bills and a smaller carbon footprint.

Reliance Water Heaters emphasizes user-friendly installation and maintenance, making it easy for homeowners to enjoy the benefits of these advanced water heaters. Overall, the Reliance N71120NE and N85390NE models represent excellence in water heating technology, offering efficient, reliable, and user-friendly solutions for modern households. Choosing either of these models ensures that users can enjoy hot water on demand while benefiting from enhanced efficiency and durability.