Trion HE Plus 2000, HE Plus 1400 Location Selection, Direction of Airflow Through the AIR Cleaner

Page 13

Installation

For Qualified HVAC

Installer Only

LOCATION SELECTION

Remember to select a location that is readily accessible for periodic inspection and cleaning of the the Pre- filters and Ionizing-Collecting Cells. Allow a minimum of 24” clearance in front and 12” clearance above the air cleaner for component removal and service space.

DIRECTION OF AIRFLOW THROUGH THE AIR CLEANER

For left to right airflow:

This air cleaner is factory set for left to right airflow when you are facing the Front Panel Assembly.

For right to left airflow:

1.Remove the Pre-filters and Ionizing Collecting Cells from the cabinet. A plastic positioning spacer is located inside the bottom of the cabinet. This spacer is secured to the cabinet by a #6 Phillips drive screw to assure installation of the Cells in the correct position with respect to air flow.

2.Remove the screw and reposition the spacer in the alternate hole in the bottom of the cabinet.

3.Replace the screw to ensure the plastic spacer is not accidentally dislodged during normal maintenance. The spacer must be installed in the hole provided nearest to the air leaving side of the cabinet.

4.Remove the Ionizing-Collecting Cell handle and re-attach to the opposite end of the cell(s). Turn Cells around, reversing their orientation and replace in cabinet and replace Pre-filters on the air entering side of the air cleaner. The directional arrows on the cell end plates must point in the direction of airflow.

Installation

For Qualified HVAC

Installer Only

The following section is to be used by a qualified HVAC

contractor or installer ONLY.

These procedures are not to be attempted by any person not qualified to work with high voltage or familiar with the installation of this type of air cleaner. Seller cannot be held responsible for any injury or damage by any person not qualified to install this product.

INSTALLER HELP LINE

If you have any questions on installation issues or problems, please call

Technical Support 866-829-2440

Technical Specifications

 

 

 

 

 

 

 

 

 

Model

 

HE Plus 1400

HE Plus 1400

 

HE Plus 2000

 

 

 

 

 

 

 

 

 

 

Size

 

(16x25)

(20x20)

 

(20x25)

 

 

 

 

 

 

 

 

 

 

Part Number 120V/50-60Hz

 

455601-001

455603-001

 

455600-001

 

 

 

 

 

 

 

 

 

 

Part Number 240V/50-60Hz

 

455601-010

455603-010

 

455600-010

 

 

 

 

 

 

 

 

 

 

Maximum Rated Airflow

 

1400 CFM (2380m/hr)

1400 CFM (2380m/hr)

 

2000 CFM (3400m/hr)

 

 

 

 

 

 

 

 

 

 

Maximum Pressure Drop

 

.11 inch w.g. @1400 CFM

.11 inch w.g. @1400 CFM

 

.14 inch w.g. @2000 CFM

 

 

 

 

 

 

 

 

 

 

Cell Weight

 

10 lbs ea. (4.5 kg)

9 lbs ea. (4.1 kg)

 

12 lbs ea. (5.5 kg)

 

 

(2 Cells in ea. unit)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Weight

 

32 lbs. (14.6 kg)

36 lbs. (16.4 kg)

 

36 lbs. (16.4 kg)

 

 

 

 

 

 

 

 

 

 

Maximum Power

 

40 watts

40 watts

 

48 watts

 

 

Consumption

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electrical Output

 

2.5 MADC @ 6200 VDC

2.5 MADC @ 6200 VDC

 

3.2 MADC @ 6200 VDC

 

 

 

 

 

 

 

 

 

 

Classification

 

UL/CE

UL/CE

 

UL/CE

 

 

 

 

 

 

 

 

 

 

Optional Accessories

 

Charcoal After Filter

Charcoal After Filter

 

Charcoal After Filter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

11

Image 13
Contents Electronic AIR Cleaner Limited THREE-YEAR Warranty WarrantyParts List Table of ContentsIntroduction TroubleshootingIntroduction Unit Components Secondary Circuit Power SupplySecondary Circuit IONIZING-COLLECTING Cell OperationRegular Dusting and White Dust OzonePrimary Circuit with Hvac System Blower Operating High Altitude OperationPrimary Circuit with Hvac System Blower not Operating Maintenance Replacing the Ionizing Wires InstallationCleaning the AIR Flow Sensor System CheckoutCommon Questions and Answers Electrical InstallationGreen Black to Black White to White Blower CompartmentScrews Mounting Holes Installer Help Line InstallationPhysical Installation of the AIR Cleaner SymptomAir cleaner shown shaded in illustrations Unit DimensionsTypical Mounting Positions Technical Specifications Direction of Airflow Through the AIR CleanerLocation Selection For left to right airflowDo not Install the AIR Cleaner in the Discharge AIR Duct