Installation
For Qualified HVAC
Installer Only
INSTALLATION
CAUTION:
Only a trained, experienced servicer should install this Electronic Air Cleaner. The Front Panel Assembly, Power Tray Assembly,
INSTALLER HELP LINE
If you have any questions on installation issues or problems, please call
Technical Support
Prior to installing this Electronic Air Cleaner:
1.Read instructions carefully for safe operation. Failure to follow instructions can damage the product or cause a hazardous condition and may result in physical harm.
2.Check the ratings stated on the product data label to make sure it is suitable for your application.
3.Select a location for the air cleaner.
4.Remove the old furnace filter and discard.
5.The air cleaner cannot remove existing dirt from the blower and ducts. Clean the area thoroughly before you begin installation.
6.Remove unit’s Front Panel Assembly and slide the
PHYSICAL INSTALLATION OF THE AIR CLEANER
This Electronic Air Cleaner can be installed in any position, except with the Front Panel Assembly facing UP or DOWN. The section TYPICAL MOUNTING POSITIONS illustrates examples of proper air cleaner mounting with a variety of furnace installations.
Common Troubleshooting Techniques |
| Troubleshooting |
| ||||
|
|
| |||||
|
|
|
|
| |||
| SYMPTOM |
| POSSIBLE CAUSES | CORRECTIVE ACTION |
| ||
| Rapid Arcing or |
| Broken or loose ionizing wire (s) | Remove broken or loose wire and replace |
| ||
| Zapping |
|
| ||||
|
|
| with new wire |
| |||
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| Dirty | Clean the |
| |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| Damaged or bent collector plates | Straighten plates with needle nose pliers |
| |
|
|
|
|
|
| ||
|
|
|
|
| or replace entire |
| |
|
|
|
|
|
|
|
|
|
|
|
| Dirty insulator caps on Ionizing- | Clean with warm soapy water and rinse |
| |
|
|
|
| well |
| ||
|
|
|
| Collecting Cell |
| ||
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| Excessive Ozone |
| Defective Air Flow Sensor | Clean or replace Air Flow Sensor |
| ||
|
|
|
|
|
| ||
| Smell |
|
|
|
|
| |
| Loose high voltage connections | Rewire Air Cleaner to the HVAC system |
| ||||
|
|
|
|
| |||
|
|
|
| blower by qualified HVAC contractor |
| ||
|
| Radio or Television |
| Poor electrical ground | Uncommon occurrence- check for good |
| |
| Interference |
|
| ||||
|
|
|
| ||||
|
|
|
|
| common ground for air cleaner |
| |
|
|
|
|
|
|
|
|
|
|
|
| Poor electrical contact in the secondary | Ensure that there is a good connection |
| |
| Hissing or Sizzling |
| electrical circuit | between the top of the |
| ||
|
|
|
| ||||
|
|
| Cell and the bottom of the contact board |
| |||
| Noise |
|
|
| |||
|
|
|
|
|
| ||
|
|
|
|
| Contact HVAC contractor |
| |
|
|
|
|
|
|
|
|
|
|
|
| No power available | Reset circuit breaker |
| |
|
|
|
|
| Replace fuse |
| |
| Green LED Light is |
|
|
|
|
| |
| Loose wiring at ON/OFF switch | Check for secure connection |
| ||||
| not On |
|
|
|
|
| |
| Defective ON/OFF switch | Replace ON/OFF switch |
| ||||
|
|
|
|
| |||
|
|
|
| ON/OFF switch not in ON position | Turn the unit ON |
| |
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
| Red LED Light is |
| Loose wiring within power pack | Check for secure connections |
| ||
| not On |
| Contact HVAC contractor |
| |||
|
| assembly |
| ||||
|
|
|
|
| |||
|
|
|
| Broken or shorted electrical | Contact HVAC contractor |
| |
|
|
|
|
|
|
| |
|
|
|
| component |
|
|
|
|
|
|
| Excessive dirt | Clean wires with alcohol and allow to dry |
| |
|
|
|
| wires | thoroughly before turning the unit ON |
| |
|
|
|
|
|
|
|
|
|
|
|
| Contact board assemblies are corroded | Replace contact board assembly |
| |
|
|
|
| or carbonized |
|
|
|
|
|
|
| Broken ionizing wire | Remove broken wire and replace with new wire |
| |
|
|
|
|
|
|
|
|
|
|
|
| Dirty | Clean the |
| |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| Foreign object located between | Remove object from |
| |
|
|
|
| collector plates |
| ||
|
|
|
|
|
|
| |
|
|
|
| Damaged or bent collector plates | Straighten plates with needle nose pliers |
| |
|
|
|
| or replace entire |
| ||
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| Insulators are corroded or carbonized | Replace insulators or |
| |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
16 | 9 |
|