Smith Cast Iron Boilers 19A SERIES Correct, Incorrect Sealing Hydrostatic Test, Steam Piping

Page 5

PAGE 5

19A SERIES BOILER

INSTALLATION INSTRUCTIONS

TABLE 3

STEP 1

UPPER RIGHT

5 FT. LBS.

STEP 2

LOWER LEFT

5 FT. LBS.

STEP 3

UPPER LEFT

5 FT. LBS.

STEP 4

LOWER RIGHT

5 FT. LBS.

STEP 5

UPPER RIGHT

25 FT. LBS.

STEP 6

LOWER LEFT

25 FT. LBS.

STEP 7

UPPER RIGHT

50 FT. LBS.

STEP 8

LOWER LEFT

50 FT. LBS.

STEP 9

UPPER LEFT

10 FT. LBS.

STEP 10

LOWER RIGHT

10 FT. LBS.

 

 

 

Prepare additional intermediate sections and install in the same manner described above. Be sure each section is properly sealed against water leakage and flue gas exfiltration. Be certain the angle rails remain level and provide support for each section as it is assembled. Check each section for vertical position.

When all sections, including the front section or back are in place, check all draw rods to insure iron-to-iron contact at ports. DO NOT APPLY EXCESSIVE TORQUE. See TABLE 3 for recommended torques.

HYDRONIC

SEAL

CORRECT

HYDRONIC

SEAL

INCORRECT

SEALING

FIGURE 3

7.HYDROSTATIC TEST

Plug tappings, fill boiler with water and vent air from top of boiler. Check for leaks. Leakage at seals may be due to misalignment of hydronic seals. Loosen draw rods, reposition seals and retest as above.

All completed boilers shall satisfactorily pass the hydrostatic tests as prescribed by A.S.M.E., Code Section IV.

1.Steam Boilers – The assembled boiler shall be subjected to a hydrostatic test of not less than 45 PSIG.

2.Water Boilers – The assembled boiler shall be subjected to a hydrostatic test pressure not less than 1-1/2 times the maximum allowable working pressure.

3.The required test shall not exceed the test pressure by more than 10 PSI.

Excessive torque on draw rods may damage castings. Do not exceed the torque shown in TABLE 3.

In a cold environment, hydronic seals may not quickly conform to sealing surfaces when properly compressed. Under such conditions, hydrostatic testing with cold water might show weeping or leaking at the seals. To avoid this possibility, delay filling the boiler with cold water for a few hours after assembly, or use warm water, if available, for the tests.

If there is seepage about chaplets or minor leakage, consult the Smith Company representative for advice regarding A.S.M.E. Code approved repairs by peening or plugging.

8.STEAM PIPING

A steam piping schedule is shown in TABLE 4. Pitch piping to allow condensate to flow in the same direction as steam. Makeup water connections must be made to the return piping, not directly to the boiler. Install blow-down valves as required.

See FIGURE 4 for recommended acceptable steam piping arrangement.

TABLE 4

BOILER SIZE

NO. OF 3" RISERS

HEADER

EQUALIZER

3 THRU 5 SECTION

1

3"

1-1/2"

6 THRU 10 SECTION

2

4"

2"

11 AND 12 SECTION

2

5"

2-1/2"

STEAM SUPPLY

TO SYSTEM

GATE VALVE

 

3" STEAM RISER(S)

SUPPORT DISCHARGE

 

PIPE

STEAM HEADER

EQUALIZER

*

CONNECTION

 

TERMINATE DISCHARGE

BOILER WATER LINE

PIPE SO AS TO AVOID

41 1/4" ABOVE FLOOR

DISCHARGE ON PERSONS

 

GATE VALVE

 

ALTERNATE RETURN

 

CONNECTION

2" BELOW MINIMUM

C.W. MAKEUP

BOILER WATER LINE

CONNECTION

 

GATE VALVE

* SAFETY VALVE

 

RETURN

BLOWDOWN VALVE

CONNECTION

TO DRAIN

 

TYPICAL STEAM PIPING DIAGRAM

FIGURE 4

Image 5
Contents 19A Series Boiler 19A Series Boiler Installation Instructions Boiler Location GeneralCodes and Regulations Chimney and BreechingCombustion and Ventilation AIR Assembly of SectionsSteam Piping CorrectIncorrect Sealing Hydrostatic Test Smoke Hood Water PipingTankless Heaters Burner Mounting Plate & Target Wall Tankless PipingSafety and Relief Valves Cleanout CoversControl Locations JacketOwners Instructions Cleaning Boiler WaterwaysSeries 19A Boiler Steam Tapping and Control Locations Symptoms of CO poisoning include the following WESTCAST, INC

19A SERIES specifications

Smith Cast Iron Boilers 19A SERIES is renowned for its durability, efficiency, and innovative technology, making it a popular choice among residential and commercial heating solutions. This series is designed to provide reliable and efficient hydronic heating, catering to various applications.

One of the standout features of the 19A SERIES is its robust cast iron construction. Smith Cast Iron has a long-standing reputation for producing boilers with exceptional strength and longevity. The cast iron design not only contributes to the boiler's durability but also enhances heat retention, ensuring optimal performance over time. This quality construction helps to minimize heat loss, which is crucial for energy efficiency.

The 19A SERIES boiler is equipped with a range of technologies that enhance its performance and efficiency. A noteworthy feature is its advanced combustion system, which maximizes fuel utilization and reduces emissions. This system ensures that the boilers operate at peak efficiency, reducing fuel costs and environmental impact. Additionally, the series includes an electronic ignition system, which simplifies operation and increases reliability, eliminating the need for standing pilots and enhancing safety.

Another important characteristic of the 19A SERIES is its modular design, which allows for flexible installation and maintenance. The boilers are designed to accommodate a variety of configurations, making them suitable for different spaces and heating requirements. This versatility ensures that they can be easily integrated into existing heating systems or installed as standalone units.

Smith Cast Iron also prioritizes user-friendly features in the 19A SERIES. The boilers come with an intuitive control panel that provides clear display options for monitoring and adjusting settings with ease. This user-centric design allows homeowners and facilities managers to optimize their heating system's performance quickly.

The 19A SERIES is engineered with energy efficiency in mind, meeting stringent industry standards and exceeding most regulatory requirements. By investing in this series, users can expect significant savings on energy bills while contributing to a more sustainable environment.

In summary, the Smith Cast Iron Boilers 19A SERIES stands out for its durable construction, innovative technologies, and energy-efficient design. With its combination of reliability, user-friendly features, and flexibility, this series is an excellent choice for anyone seeking a high-quality hydronic heating solution. Whether for residential or commercial use, the 19A SERIES continues to deliver the performance that has made Smith Cast Iron a trusted name in the industry.