Smith Cast Iron Boilers 19A SERIES Water Piping, Tankless Heaters, Smoke Hood

Page 6

PAGE 6

19A SERIES BOILER

INSTALLATION INSTRUCTIONS

TABLE 5

NUMBER

EVAPOR.

WATER 1"

MIN. FEED

CONDENSATE

OF

RATE

BELOW WATER WATER PUMP

RECEIVER

SECTIONS

GPM

LEVEL GAL.

RATE-GPM

CAP.-GAL.

3

.61

1.4

1.22

12

4

.85

1.9

1.70

16

5

1.19

2.4

2.37

22

6

1.52

2.9

3.04

29

SYSTEM SUPPLY

CHECK VALVE

CONNECTIONS

 

 

CIRCULATOR

GATE VALVE

 

 

EXPANSION

RELIEF VALVE

TANK

 

 

AIR REMOVAL

SUPPORT RELIEF VALVE

PIPING

DISCHARGE PIPE

GATE

 

VALVE

7

1.86

3.3

3.71

35

8

2.19

3.8

4.38

41

9

2.53

4.3

5.05

47

10

2.86

4.8

5.72

54

11

3.20

5.2

6.39

60

12

3.53

5.7

7.06

66

Feed water makeup requirements.

NOTE

These recommendations are considered normal for compact buildings on the basis of 80% receiver use. Where buildings are spread out, additional receiver capacity may be necessary because of the extended

TERMINATE DISCHARGE PIPE SO AS TO AVOID DISCHARGE ON PERSONS

SYSTEM RETURN

CONNECTION

GATE VALVE

BLOWDOWN VALVE TO DRAIN

C.W. MAKEUP

CONNECTION

PRESSURE

REGULATING

VALVE

TYPICAL WATER PIPING DIAGRAM

time required for condensation to return to the receiver.

9.WATER PIPING

See FIGURE 5 for acceptable water piping diagram. TABLE 6 gives pumping rate and supply & return sizing for standard installations.

TABLE 6

BOILER SIZE

GPM

RETURN CONN.

SUPPLY CONN.

 

 

 

 

3

30

2"

2"

4

41

2"

2"

5

58

2-1/2"

2-1/2"

6

74

3"

3"

7

90

3"

3"

8

106

3"

3"

9

123

3"

3"

10

139

3"

3"

11

155

3"

4"

12

171

3"

4"

 

 

 

 

Based on 20° F system temperature drop.

NOTE

Boiler supplied with 4" water supply tapping and 3" return tapping.

FIGURE 5

10. TANKLESS HEATERS

Heater openings are provided for below-the-water-line tankless heater coils in all special intermediate sections when ordered. See TABLE 2 for the conr•ct placement of these heater sections. Install the low limit temperature control in the 3/4" tap located in the center of the coil.

If the heater sections are installed in an order other than in TABLE 2 the jacket panels will not match.

11. SMOKE HOOD

Install smoke hood with the correct size smoke pipe connecting collar using the 5/16" x 1-1/2" studs and hex nuts furnished in screw seats in the back section. Apply self- adhesive insulating tape (Items 21 and 22 in Parts detail drawing on Page 2) to smoke hood flange and damper angle Item 23. Fasten the slide damper in the open position for starting the burner adjustment process.

See FIGURE 6 for recommended “L” coil piping and FIGURE 7 for SM9-18 single and/or dual piping arrangements.

Image 6
Contents 19A Series Boiler 19A Series Boiler Installation Instructions Codes and Regulations GeneralBoiler Location Chimney and BreechingAssembly of Sections Combustion and Ventilation AIRCorrect Incorrect Sealing Hydrostatic TestSteam Piping Water Piping Tankless HeatersSmoke Hood Tankless Piping Burner Mounting Plate & Target WallControl Locations Cleanout CoversSafety and Relief Valves JacketCleaning Boiler Waterways Owners InstructionsSeries 19A Boiler Steam Tapping and Control Locations Symptoms of CO poisoning include the following WESTCAST, INC

19A SERIES specifications

Smith Cast Iron Boilers 19A SERIES is renowned for its durability, efficiency, and innovative technology, making it a popular choice among residential and commercial heating solutions. This series is designed to provide reliable and efficient hydronic heating, catering to various applications.

One of the standout features of the 19A SERIES is its robust cast iron construction. Smith Cast Iron has a long-standing reputation for producing boilers with exceptional strength and longevity. The cast iron design not only contributes to the boiler's durability but also enhances heat retention, ensuring optimal performance over time. This quality construction helps to minimize heat loss, which is crucial for energy efficiency.

The 19A SERIES boiler is equipped with a range of technologies that enhance its performance and efficiency. A noteworthy feature is its advanced combustion system, which maximizes fuel utilization and reduces emissions. This system ensures that the boilers operate at peak efficiency, reducing fuel costs and environmental impact. Additionally, the series includes an electronic ignition system, which simplifies operation and increases reliability, eliminating the need for standing pilots and enhancing safety.

Another important characteristic of the 19A SERIES is its modular design, which allows for flexible installation and maintenance. The boilers are designed to accommodate a variety of configurations, making them suitable for different spaces and heating requirements. This versatility ensures that they can be easily integrated into existing heating systems or installed as standalone units.

Smith Cast Iron also prioritizes user-friendly features in the 19A SERIES. The boilers come with an intuitive control panel that provides clear display options for monitoring and adjusting settings with ease. This user-centric design allows homeowners and facilities managers to optimize their heating system's performance quickly.

The 19A SERIES is engineered with energy efficiency in mind, meeting stringent industry standards and exceeding most regulatory requirements. By investing in this series, users can expect significant savings on energy bills while contributing to a more sustainable environment.

In summary, the Smith Cast Iron Boilers 19A SERIES stands out for its durable construction, innovative technologies, and energy-efficient design. With its combination of reliability, user-friendly features, and flexibility, this series is an excellent choice for anyone seeking a high-quality hydronic heating solution. Whether for residential or commercial use, the 19A SERIES continues to deliver the performance that has made Smith Cast Iron a trusted name in the industry.