Honeywell GM-1 System Description continued, System Specifications, Signal input: 4/20 mA

Page 6
1 System Description continued

1 System Description continued

System Specifications

Electrical Power: 120 VAC, 50/60 Hz at 0.35 amp (230 VAC 50/60 Hz is available as an option)

Signal input: 4/20 mA

DC Power available for sensors: Heavy-duty internal 24 VDC, 1 amp maximum regulated supply

Display: 20-segment LED bargraph

Light Outputs and Relays:

Alarm Light and Relay

Setpoint field adjustable

Alarm Light and Relay independently latchable by board mounted DIP switch

10 second on delay, 2 second off delay Warning Light and Relay

Setpoint field adjustable

Warning Light and Relay are NOT latchable

10 second on delay, 2 second off delay Fault Light and Relay

Setpoint NOT adjustable — all mA signals below 1.4 mA will initiate fault output

Fault Light and Relay always latch

10 second on delay

Note: All relays are normally energized and monitored by individual LEDs for

ease of troubleshooting

Relay Ratings: 3 amps at 24 VDC or 120 VAC Form C providing NO (normally open) or NC (normally closed) option

Enclosure: 14 gauge steel, gasketed, 10" high x 8" wide x 4" deep, NEMA 1 rated enclosure with plexiglass window

Weight: 11 lbs.

Operating Ambient Temperature range: 0o F to

+120o F

Operating Humidity: 5-95% Relative Humidity, non- condensing

Options: Down-scale Alarm for oxygen

Push-button Controls:

Silence — Silences internal horn

Reset — Clears signal, latched functions, and relays. If warning, alarm, or fault condition exists, indications will return after a short time delay.

Note: The Manning GM-1 is for use only in non-classified areas.

Manning GM-1 Gas Monitoring Alarm System 19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved.

6

Image 6
Contents Manning GM-1 Instruction and Installation ManualGas Monitoring Alarm System Release D DraftNotices and Trademarks Copyright 2009 by Honeywell International IncRelease D July About This Document Symbol DefinitionsSymbolDefinition World Wide WebSerial number ContentsIntroduction Section1 System Description ease of troubleshooting System SpecificationsSignal input: 4/20 mA Weight 11 lbs2 Installation ALocating the Manning GM-1AC Power Wiring 2 Installation continuedBWiring Relay Wiring2 Installation continued Risk of electrical shock Potential hazard3 Operation BReset and Silence SwitchesCDIP Switch Setting ADisplay PanelFTroubleshooting DSignal and SetpointsEStart-UpProcedures 3 Operation continued3 Operation continued G MaintenanceH Replacement Parts mVDC2.Exclusions 4 Limited Warranty1.Limited Warranty 4.Disclaimer of Unstated Warranties