1 System Description continued
System Specifications
Electrical Power: 120 VAC, 50/60 Hz at 0.35 amp (230 VAC 50/60 Hz is available as an option)
Signal input: 4/20 mA
DC Power available for sensors:
Display:
Light Outputs and Relays:
Alarm Light and Relay
•Setpoint field adjustable
•Alarm Light and Relay independently latchable by board mounted DIP switch
•10 second on delay, 2 second off delay Warning Light and Relay
•Setpoint field adjustable
•Warning Light and Relay are NOT latchable
•10 second on delay, 2 second off delay Fault Light and Relay
•Setpoint NOT adjustable — all mA signals below 1.4 mA will initiate fault output
•Fault Light and Relay always latch
•10 second on delay
Note: All relays are normally energized and monitored by individual LEDs for
ease of troubleshooting
Relay Ratings: 3 amps at 24 VDC or 120 VAC Form C providing NO (normally open) or NC (normally closed) option
Enclosure: 14 gauge steel, gasketed, 10" high x 8" wide x 4" deep, NEMA 1 rated enclosure with plexiglass window
Weight: 11 lbs.
Operating Ambient Temperature range: 0o F to
+120o F
Operating Humidity:
Options:
Push-button Controls:
Silence — Silences internal horn
Reset — Clears signal, latched functions, and relays. If warning, alarm, or fault condition exists, indications will return after a short time delay.
Note: The Manning
Manning | 6 |