Barnet Ensign Ross ED810 manual Contact EDL for Further information, Solenoid Valve

Page 5
7

10

9

8

7

6

5

4

3

2

1

In addition to the zener barrier fuses (which cannot be replaced) each sensor is individually fused on the base board PCB. If a sensor fails to respond the nominal 5V between blue and brown terminals should be checked and the 160mA quick blow (F) changed if necessary.

Sensor Wiring: The Sensor cable should meet the following specification as listed in the Zener Barrier (ZB1) certificate, see page 16. The total capacitance of the cable must not exceed 6.8uF for EDS/C and EDS/P or 8.8uF for the EDF sensor. Also the inductance or inductance to resistance (L/R) ratio should not exceed 0.06mH or 14uH/Ω respectively.

Typical output wiring: Fig 2 shows the terminal connections and Fig 3 shows typical wiring of output functions. A fused 12V or 24V supply is available on terminal 2 for the operation of low power sounders and beacons, the installation engineer must provide the links to

 

 

C

 

 

NON

20

 

 

 

 

 

 

 

HAZARDOUS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALARM

 

 

 

 

 

 

 

 

AREA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

provide the

required functions. Remember any sounders or beacons located in the Hazardous

 

 

NO

 

ACCEPT

19

 

 

 

 

 

 

 

COMMON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Area must be

certified Flameproof or Intrinsically Safe if fed via an external zener barrier

 

 

 

 

 

 

CONTACTS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC

 

 

18

-

 

VALVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

contact EDL for

further information.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONNECTIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

17

+

 

12VDC EDL MODEL ONLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

A1 CONTACTS

16

 

 

 

NC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC

 

 

15

 

 

 

C

A2 CONTACTS

BL

G/Y

BR

BL

G/Y

BR

BL

G/Y

BR

BL

G/Y

BR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(+VE)

(O/P)

(-VE)

(+VE)

(O/P)

(-VE)

(+VE)

(O/P)

(-VE)

(+VE)

(O/P)

(-VE)

 

 

 

 

 

 

14

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0V

 

 

 

 

 

 

 

 

 

 

 

 

SENSOR 1

 

 

 

SENSOR 2

 

 

 

SENSOR 3

 

 

 

SENSOR 4

 

 

 

 

 

 

 

13

 

 

 

NC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FUSED 0/P

12

 

 

 

C

FAULT CONTACTS

 

 

 

 

 

 

 

 

HAZARDOUS AREA WIRING

 

 

 

 

 

 

 

 

+VE I/P

 

11

 

 

 

NO

 

 

 

FIG 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SAFE AREA WIRING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

34

5 6

SOUNDER/BEACON

12

13

15

11

16

10

14

8

RELAY TO DRIVE

SHUT DOWN FUNCTIONS,

FANS, ETC.

9

FIG 3

Relay contact rating: 2A at 240VAC Non Inductive

SOLENOID VALVE

It is important that only a 12VDC solenoid valve is used regardless of the input supply voltage. Further more, solenoid valves must be exactly the same specification as the low consumption type supplied by EDL to prevent damage to the circuit board components.

ED810 INSTRUCTION MANUAL 27-02-07

5

Image 5
Contents ED810 GAS Detector Electronic Deviceslimited Atex Essential Safety Requirements General MarkingInstallation Solenoid Valve Contact EDL for Further informationSensors Calibration Operating InstructionsEDS/C ED810EDS/P