Aprilaire 60 & 62 Determine Location for Humidifier Control and Mount Control, Figure C

Page 4

STEP 4: Determine Location for Humidifier Control and Mount Control

Humidifier Control must be mounted on the Return Duct, at least

6 inches upstream of the following (see Figure C):

Humidifier

Humidifier Bypass Ductwork (if applicable)

Fresh Air Intake Ductwork (if applicable)

Ambient operating temperature of the Humidifier Control is to be from 20°F to 120°F to prevent damage to the control display.

DUCT (SHEET METAL) MOUNT:

After location for Control is selected, drill a 3/4 inch hole for the RH sensor (the RH sensor extends from the back of the Humidifier Control).

Use 2 sheet metal screws, 3/4 inch long (not provided), to mount the Humidifier Control. Use the mounting slot to level the Control, then secure the Control with the second sheet metal screw.

Make sure the Humidifier Control sensor gasket is seated tightly around the drilled hole. Do not install Control without gasket.

DUCT (FIBER BOARD) MOUNT:

RETURN

DUCT

6" MIN.

HUMIDIFIER

CONTROL

FRESH AIR

INTAKE

BYPASS

CONNECTION

Figure C

HUMIDIFIER

COIL

90-1137

After location for Control is selected, cut a rectangular hole in the duct board, no smaller than 6-9/16 inches long by 4-3/8 inches wide.

Cut a rectangular piece of sheet metal to fit behind the hole in duct board for mounting the Humidifier Control.

Drill a 3/4 inch hole for the RH sensor (the RH sensor extendsfrom the back of the Humidifier Control) into the sheet metal plate.

Use 2 sheet metal screws, 3/4 inch long (not provided), to mount the Humidifier Control.

Make sure the Humidifier Control sensor gasket is seated tightly around the drilled hole. Do Not Install Control Without Gasket.

Secure the sheet metal plate, with the Humidifier Control mounted, inside the duct (see FigureD).

CONTROL REPLACEMENT:

When replacing an existing control, the duct opening left by the removed control must be covered completely. Locate and install the new control as instructed previously in Step 4.

6

7

Image 4
Contents Automatic Digital HumidifierControl Model 60 Table of Contents Installation Check the Change Water Panel IndicatorSettingUnpack the Humidifier Control Carton Disassemble the Humidifier ControlDetermine Location for Humidifier Control and Mount Control Figure CFigure E Digital Humidifier Control 24V Terminals Locate Existing Access Hole to Outside Determine Location for Outdoor Temperature SensorAlternate Location for Outdoor Temperature Sensor Attach Sensor Wire to Humidifier Control Route the Wire from Control to SensorSecure the sensor bracket with a #8 screw Wiring Description Minimum VA required is 2.0 VA90-1511 System Checkout Setting the Humidifier ControlBlower Activation Test Troubleshooting Guide Humidifier does not operate in Test/Reset mode Figure MHumidifier operates only in Test/Reset mode Yellow Change Water Panel light is blinking see Figure MHumidifier operates constantly Research Products Corporation