Beckett AFII manual Burner Controls, GeniSys Model 7505 Control Fire or Explosion Hazard, Features

Page 10

Section: Burner Controls

Burner Controls

GeniSys Model 7505 Control

Fire or Explosion Hazard

Can cause severe injury, death, or property damage.

yThe control can malfunction if it gets wet, leading to accumulation of oil or explosive oil vapors.

yNever install where water can flood, drip or condense on the control.

yNever use a control that has been wet - replace it.

Features

Thermostat / Operating and Limit Control Compatible

Welded Relay Protection

Limited Recycle

Limited Reset

3 Status Lights

Valve-On Delay / Motor-Off Delay (Field programmable with 52067 GeniSys Display)

15 Second Lockout Time

Interrupted or Intermittent Duty Ignition

Technician Pump Priming Mode

Disable Function

Communication Ports

Figure 7 - 7505 Control

Reset Button with Red Light

Yellow Light

Green Light

Wiring

Explosion, Fire, Scald, and

Burn Hazard

All heating appliances must have HIGH LIMIT protection to interrupt electrical power and shutdown the burner if operating or safety controls fail and cause a runaway condition.

yFollow the appliance manufacturer’s wiring diagrams and note all required safety controls.

yTypical safety controls include high temperature or pressure limits, low water cutoffs, pressure relief valves and blocked flue sensing switches.

yVerify all limit and safety controls are installed and functioning correctly, as specified by the manufacturer, applicable safety standards, codes and all authorities having jurisdiction.

yEnsure that the appliance is free of oil and oil vapor before starting or resetting the burner.

Incorrect Wiring Will

Result in Improper Control

Operation

yGeniSys wiring label colors may not match the wire colors of the burner or other manufacturers’ controls.

yThe GeniSys Control should be wired according to the appliance manufacturer’s instructions.

Wiring

Connections

Cad Cell

Connections

Thermostat Terminals

Communication Port 2

 

Communication Port 1

Optional Components:

Contractor’s Tool: Hand-held device for programming and diagnostics

Display Module:

Permanent device for programming and diagnostics

Alarm Module:

For adding isolated low voltage alarm contacts to the base control. See Alarm Module Instructions for specifications.

10

Image 10
Contents Potential for Fire, Smoke and Asphyxiation Hazards To the Homeowner or Equipment OwnerPage Contents General Information Inspect/Prepare Installation Site Air Tube Combinations ATC & Dimensions Fire, Smoke & Asphyxiation HazardDirect/Sidewall Venting Application Outside Air ConnectionFuel Line Valves and Filter Prepare the BurnerDo Not Use Teflon Tape GeneralSpecial wiring required with covered burners Wire BurnerBurner installed at jobsite Mount Burner on ApplianceIncorrect Wiring Will Result in Improper Control Operation FeaturesWiring Explosion, Fire, Scald, Burn Hazard Burner ControlsValve-on delay Reset Button Operation Status LightsControl System Features Start Up Burner and Set Combustion Wire BurnerHot Gas Puff-Back Heavy Smoke Hazard Annual Professional Service Required Section Perform Regular MaintenanceNozzle Installation Nozzle Flow Rate by SizeBlower Wheel Replacement Check/Adjust ElectrodesCombinations HLX Firing Rate HLX Air Dial SettingFBX Air Dial Setting FBX Firing RateReplacement Parts Description Kit NoLimited Warranty Information