Section: Inspect/Prepare Installation Site
Eventually the blockage could prevent exhausting the flue gases. Instead, the flue gases could vent out the barometric damper into the living space.
Therefore, it is strongly recommended that an approved insulated stainless steel liner be installed.
Combustion Air Supply Information
Adequate Combustion
and Ventilation Air Supply
Required
Failure to provide adequate air supply could seriously affect the burner performance and result in damage to the equipment, asphyxiation, explosion or fire hazards.
yThe burner cannot properly burn the fuel if it is not supplied with a reliable combustion air source.
yFollow the guidelines in the latest editions of the NFPA 31 and
Appliances located in confined spaces: All confined spaces should have two (2) permanent openings; one near the top of the enclosure and one near the bottom of the enclosure. Each opening must have a free area of not less than one (1) square inch per 1,000 BTU’s per hour of the total input rating of all appliances within the enclosure. The openings should have free access to the building interior, which should have adequate infiltration from the outside.
Exhaust fans and other
the burner or provide a sealed enclosure for the burner and supply it with its own combustion air supply.
Direct/Sidewall Venting Application
○When sidewall venting appliances, carefully follow appliance and power venter instructions for installation and wiring.
○AFII burners are equipped with a removable air inlet to allow use of a 4” duct to supply outside air for combustion. Do not exceed 50 equivalent feet. Allow 6 feet for each elbow.
1.Remove the inlet cover.
2.Insert 4” duct into the inlet ring.
3.Fasten duct into place using at least 3 sheet metal screws evenly spaced around the inlet ring. Refer to Figure 3.
4.Remove the barometric draft control unless it is in the same atmospheric pressure zone as the inlet.
Figure 3. Outside Air Connection
Air
Inlet
Elbow
4 inch Duct
1/4” Mesh Screen
SK8810
Inlet Ring
Figure 2 - Chimney Design - Above the Roof |
|
|
| ||
|
|
| |||
NOTE: Correct |
|
|
| ||
|
|
| |||
chimney design is | Minimum Clearence: |
| 2 FT. | ||
| |||||
shown by dotted lines. |
|
|
| ||
Incorrect chimney |
|
|
|
|
|
|
|
|
| ||
design, as shown by |
|
|
| ||
the solid lines, may |
|
|
| ||
result in |
|
|
|
AFII Burner Manual
7