Beckett AFII manual Direct/Sidewall Venting Application, Outside Air Connection

Page 7

Section: Inspect/Prepare Installation Site

Eventually the blockage could prevent exhausting the flue gases. Instead, the flue gases could vent out the barometric damper into the living space.

Therefore, it is strongly recommended that an approved insulated stainless steel liner be installed.

Combustion Air Supply Information

Adequate Combustion

and Ventilation Air Supply

Required

Failure to provide adequate air supply could seriously affect the burner performance and result in damage to the equipment, asphyxiation, explosion or fire hazards.

yThe burner cannot properly burn the fuel if it is not supplied with a reliable combustion air source.

yFollow the guidelines in the latest editions of the NFPA 31 and CSA-B139 regarding providing adequate air for combustion and ventilation.

Appliances located in confined spaces: All confined spaces should have two (2) permanent openings; one near the top of the enclosure and one near the bottom of the enclosure. Each opening must have a free area of not less than one (1) square inch per 1,000 BTU’s per hour of the total input rating of all appliances within the enclosure. The openings should have free access to the building interior, which should have adequate infiltration from the outside.

Exhaust fans and other air-using devices: Size air openings large enough to supply all air-using devices in addition to the minimum size required for combustion air. If there is any possibility of the equipment room developing a negative pressure due to exhaust fans, clothes dryers, etc., either pipe combustion air directly to

the burner or provide a sealed enclosure for the burner and supply it with its own combustion air supply.

Direct/Sidewall Venting Application

When sidewall venting appliances, carefully follow appliance and power venter instructions for installation and wiring.

AFII burners are equipped with a removable air inlet to allow use of a 4” duct to supply outside air for combustion. Do not exceed 50 equivalent feet. Allow 6 feet for each elbow.

1.Remove the inlet cover.

2.Insert 4” duct into the inlet ring.

3.Fasten duct into place using at least 3 sheet metal screws evenly spaced around the inlet ring. Refer to Figure 3.

4.Remove the barometric draft control unless it is in the same atmospheric pressure zone as the inlet.

Figure 3. Outside Air Connection

Air

Inlet

Elbow

4 inch Duct

1/4” Mesh Screen

SK8810

Inlet Ring

Figure 2 - Chimney Design - Above the Roof

 

 

 

 

 

 

NOTE: Correct

 

 

 

 

 

 

chimney design is

Minimum Clearence:

 

2 FT.

 

shown by dotted lines.

 

 

 

Incorrect chimney

 

 

 

 

 

 

 

 

 

design, as shown by

 

 

 

the solid lines, may

 

 

 

result in down-drafts.

 

 

 

AFII Burner Manual

7

Image 7
Contents To the Homeowner or Equipment Owner Potential for Fire, Smoke and Asphyxiation HazardsPage Contents General Information Inspect/Prepare Installation Site Fire, Smoke & Asphyxiation Hazard Air Tube Combinations ATC & DimensionsOutside Air Connection Direct/Sidewall Venting ApplicationGeneral Prepare the BurnerDo Not Use Teflon Tape Fuel Line Valves and FilterMount Burner on Appliance Wire BurnerBurner installed at jobsite Special wiring required with covered burnersBurner Controls FeaturesWiring Explosion, Fire, Scald, Burn Hazard Incorrect Wiring Will Result in Improper Control OperationValve-on delay Status Lights Reset Button OperationControl System Features Start Up Burner and Set Combustion Wire BurnerHot Gas Puff-Back Heavy Smoke Hazard Section Perform Regular Maintenance Annual Professional Service RequiredNozzle Flow Rate by Size Nozzle InstallationBlower Wheel Replacement Check/Adjust ElectrodesCombinations FBX Firing Rate HLX Air Dial SettingFBX Air Dial Setting HLX Firing RateDescription Kit No Replacement PartsLimited Warranty Information